ANUNCIAR
NZM3-4-XKS 266780 Y7-266780 EATON ELECTRIC Screw connection, 4p, standard, size 3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NZM3-4-XKS 266780 Y7-266780 EATON ELECTRIC Screw connection, 4p, standard, size 3

NZM3-4-XKS

266780

Y7-266780

EATON-MOELLER

Screw connection, 4p, standard, size 3

NZM3-4-XKS

Eaton Moeller series NZM - Molded Case Circuit Breaker. Screw connection, 4p, standard, size 3

Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: part no. contains parts for a terminal located at top or bottom for 3 or 4 pole switches. Standard connection with all NZM3, PN3 and N3 circuit-breakers. Conversion kit for circuit-breaker with box terminal. Use special cable lug narrow version. fitted within the switch housing. If a busbar is used, insulation (400mm) heat-shrink tubing and a cover NZM3(-4)-XKSA are required. U e ≧ 525 VAC . For all other connection types use cover NZM3(-4)-XKSA. Can be used for: NZM3(-4), PN3(-4), N(N/O)3(-4)

More details


Low-voltage industrial components > Wiring set for power circuit breaker

Circuit Breakers NZM

Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total: $36.05
Unit price: $36.05
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



General specifications

Product Name
Eaton Moeller series NZM connection type
Catalog Number
266780
Model Code
NZM3-4-XKS
EAN
4015082667801
Product Length/Depth
80 mm
Product Height
35 mm
Product Width
80 mm
Product Weight
0.212 kg
Compliances
IEC
RoHS conform

Product specifications

Used with
NZM3-4, PN3-4, N(S)3-4
Type
AccessoryScrew connectionTerminal
Amperage Rating
≦ 400 A
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Frame
NZM3
Suitable for
Copper cable lugs
Aluminum cable lug
Four-pole
Number of poles
Four-pole
Terminal capacity (copper strip)
10 segments of 32 mm x 1 mm + 5 segments of 32 mm x 1 mm
Model
Other
Terminal capacity (stranded cable)
10 mm² - 120 mm² (1x)
4 - 350 AWG/kcmil (1x)
10 mm² - 120 mm² (2x)
350 AWG/kcmil (2x)
Terminal capacity (copper busbar)
30 mm x 10 mm + 30 mm x 5 mm

ETIM for 266780 Low-voltage industrial controls and switchgear (EC002050)
Feature Name Feature Value
Suitable for number of poles (EF001589) 4
Model (EF000010) Other

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.