Product name
Eaton Moeller® series ES4P Safety relay
Product Length/Depth
72 millimetre
Product height
90 millimetre
Product width
108 millimetre
Product weight
0.344 kilogram
Certifications
EN ISO 13849-1
CSA
CSA-C22.20.4-04
EN 50178
EN 50156-2
UL Category Control No.: NRAQ
IEC/EN 61000-6-2
CE
CSA Class No.: 2252-81; 2252-01
UL File No.: CSA report applies to both US and Canada
CSA File No.: 012528
EN 50156-1
IEC 61508
IEC/EN 61000-6-3
EN 50581
CSA-22.2 No. 142-MI1987
IEC/EN 61000-4-2
UL 508
IEC 62061
Features
Expandable
Safety/standard circuit diagram
Fitted with:
Timer
Display
Expandable standard inputs/outputs
Keypad
Relay output
Expandable standard bus systems
Real time clock
Functions
Thermal cutout
Redundancy
Indication
LCD-display used as Output status indication of Transistor outputs
Inscription
Individual laser inscriptions possible
Accuracy
± 5 s/day depending on the ambient temperature
± 2 s/day (± 0.5 h⁄year), Real-time clock, normally
Cable length
100 m, unscreened, Digital inputs 24 V DC
50 m, unscreened, Transistor outputs
1000 m, shielded, Single cable length of test signal output to the device input, Digital inputs 24 V DC
3000 m, shielded, Total of single cable lengths from one test signal output to the device inputs, Digital inputs 24 V DC
Display temperature - min
0 °C
Display temperature - max
55 °C
Duty factor
100 % (Inductive load to EN 60947-5-1, With external suppressor circuit)
T0.95 ≈ 3 x T0.65 = 3 x L/R (Inductive load to EN 60947-5-1, Without external suppressor circuit)
T0.95 = Time in ms, until 95 % of the steady-state current has been reached (Inductive load to EN 60947-5-1, Without external suppressor circuit)
Insulation resistance
According to EN 50178
Lifespan, mechanical
10,000,000 Operations (Relay outputs)
10,000,000 Operations
Mounting method
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Rail mounting possible
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Operating frequency
13500 Operations/h at resistive load
900 Operations/h at input (does not apply to I1, I2, if function block SM or OM is used)
Resistive load < 100 kΩ, depending on program and load
Product category
Control relays for safety applications
Rated impulse withstand voltage (Uimp)
6 kV (contact-coil)
Residual ripple
5 % (transistor outputs)
≤ 5 %
Resolution
1 min (Range H:M)
1 s (Range M:S)
50 ms (Range S)
Suitable for
Safety functions
Switching capacity
AC: R300 (in accordance with UL 508), Relay outputs
DC-13, 24 V DC, 0.1 Hz: 40000 operations (in accordance with IEC 60947-5-1), Relay outputs
AC-15, 230 V AC, 3 A: 80000 operations (in accordance with IEC 60947-5-1), Relay outputs
DC: B300 (in accordance with UL 508), Relay outputs
Switching frequency
15 Hz, Relay outputs
0.5 Hz, Transistor outputs, Inductive load to EN 60947-5-1, with external suppressor circuit, Max. switching frequency, max. duty factor = 50%
Type
easy800 with safety function blocks
Ambient conditions, mechanical
Constant acceleration
2 g, 57 - 150 Hz
Constant amplitude
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
3.5 mm / 1 g, According to IEC/EN 60068-2-6
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
55 °C
Environmental conditions
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142, EN 60664-1:2003
Condensation: prevent with appropriate measures
Relative humidity
5 - 95 % (non-condensing, IEC 60068-2-30, IEC 60068-2-78)
Electro magnetic compatibility
Burst impulse
4 kV, Supply cable
4 kV, Signal cable
According to IEC/EN 61000-4-4
Electromagnetic compatibility
Increased EMC requirements for safety-relevant functions (according to ICE 62061)
Electromagnetic fields
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
30 V/m (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
20 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 55022)
Class B (EN 55011)
Surge rating
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
2 kV, Supply cables, symmetrical, power pulses (Surge), EMC
4 kV, semi-conductor outputs, symmetrical, power pulses (Surge), EMC
Voltage dips
≤ 10 ms
According to EN 61131-2
Terminal capacity
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (AWG 22 - 12), solid
Tightening torque
0.6 Nm, Screw terminals
Screwdriver size
3.5 x 0.8 mm, Terminal screw
Conventional thermal current ith of auxiliary contacts (1-pole, open)
6 A
Input current
< 250 mA (at 115/230 V AC)
5.7 mA (Digital inputs, at 24 V DC, at signal 1, I1 - I6)
Output voltage
24 V DC (test signal outputs)
Output Voltage@≤ 2.4 V (at signal 0 at external load < 10 MΩ, transistor outputs)
U = Uₑ - 1 V (signal 1 at Iₑ = 0.5 A, transistor outputs)
Peak short-circuit current
16 A
Rated control supply voltage
24 V DC (Us)
Rated insulation voltage (Ui)
250 V
Rated operational current (Ie)
Max. 0.5 A at signal „1” DC per channel
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
24 V DC (digital inputs)
> 15 V DC on 1 signal
250 V AC
20.4 - 28.8 V DC
24 V DC (transistor outputs)
20.4 - 28.8 V DC (Transistor outputs)
< 5 V DC on 0 signal
Short-circuit current
8 A, Transistor outputs
Short-circuit protection
Yes, Transistor outputs
≤ 8 A, Back-up fuse, Transistor outputs
Short-circuit tripping current
0.7 ≤ Ie ≤ 2 per output, For Ra ≤ 10 mΩ, Transistor outputs
Supply current
50/50 mA, Normally⁄max., On 0 signal, Transistor outputs
60/100 mA, Normally⁄max., On 1 signal, Transistor outputs
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
20.4 V DC
Supply voltage at DC - max
28.8 V DC
Bus termination
First and last station, easyNet
Data transfer rate
500 kBit/s, 25 m, easyNet
1000 kBit/s, 6 m, easyNet
20 kBit/s, 700 m, easyNet
250 kBit/s, 40 m, easyNet
125 kBit/s, 125 m, easyNet
50 kBit/s, 300 m, easyNet
10 kBit/s, 1000 m, easyNet
LED indicator
Status indication of Digital inputs 24 V DC: LCD Display
Memory
100,000,000,000,000 Write cycles of the retentive memory
Module interface
easyNet/easyLink
Protocol
Other bus systems
Capacitive load
0.6 µF max., Transistor outputs
Lamp load
5 W (without Rv per channel)
Number of inputs (analog)
0
Number of inputs (digital)
14
Number of outputs (analog)
4
Number of outputs (digital)
5
Output
Relay outputs in groups of 1
4 Transistor Outputs
4 Test signal outputs (T1 - T4)
Parallel switching
Not permitted
Pulse characteristics
1 ms (max. duration of external test pulse)
1 ms (Off test pulse)
Utilization factor
1 (Inductive load to EN 60947-5-1, With external suppressor circuit)
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Between easyNet and Outputs: yes
Safe isolation according to EN 50178: 300 V AC (Relay outputs)
Between easyNet and Power supply: yes
Between Digital inputs 24 V DC and easyNet: yes
Between easyNet and PC interface: yes
Between Relay outputs and Interface: yes
Between easyNet and Memory card: yes
Between Power supply and easyNet: yes
Between Relay outputs and Inputs: yes
Between easyNet and Inputs: yes
Between Relay outputs and Power supply: yes
Between Digital inputs 24 V DC and Outputs: yes
Basic isolation: 600 V AC (Relay outputs)
Between Relay outputs and Digital inputs: yes
Between Relay outputs and easyNet: yes
Between Inputs and internal Power supply: Yes
Between Transistor output and interface: yes
Between Transistor outputs and easyLink: yes
Between Power supply and Inputs: yes
Between Power supply and Outputs: yes
Protection
!
Protection of an Output relay - Fuse: 6 A gL/gG, Circuit-breaker with C characteristic: 4 A (only permissible with 24V DC), Short-circuit current IK: < 250 A
Protection against polarity reversal
Yes
Safe isolation
Between coil and contacts in accordance with EN 50178
300 V AC, Between coil and contacts, According to EN 50178
Safety function/level
Feedback circuit
According to EN 50156
OSSD input
Highest speed monitoring
Stopping in the event of an emergency
Zero speed monitoring
3 redundant relay outputs, 6 months test interval
Two-hand control
Safety timing relay
Enabling switch
ESPE with muting function
Protective door
Mode selection
Safety parameter (EN ISO 13849-1)
PL e, Performance level
Cat. 4, Category
Safety parameter (IEC 62061)
SILCL 3, Safety integrity level claim limit
SIL 3, Safety integrity level, In accordance with IEC 61508
23 x 10-10, PFHd, Probability of failure per hour
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
6 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.