Product name
Eaton Moeller series xEffect - PXS24 current monitoring relay
Product Length/Depth
127 millimetre
Product height
93 millimetre
Product width
18 millimetre
Product weight
0.118 kilogram
Compliances
UL508
CE
RoHS conform
Certifications
EN45545-2
IEC 61373
Product Tradename
xEffect - PXS24
Product Type
Current monitoring relay
Type
Automation engineering 24V
Technical Data - Electrical
Voltage rating
24 VDC (15 VDC - 30 VDC)
Rated control supply voltage (Us) at AC, 50 Hz - min
0 V
Rated control supply voltage (Us) at AC, 50 Hz - max
0 V
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Rated control supply voltage (Us) at DC - min
15 V
Rated control supply voltage (Us) at DC - max
30 V
Rated operational current (Ie) fix
2 A
Current measurement - min
0 A
Current measurement - max
2.6 A
Overload current and short-circuit current trip
Type 1.3 x IN with active current limitation
Electric connection type
Plug-in connection
Adjustable delay-on energization time - min
0 s
Permitted delay-on energization time - max
0 s
Adjustable off-delay time - min
0 s
Permitted off-delay time - max
0 s
Capacitive load
Up to 20,000 µF
Technical Data - Mechanical
Mounting method
Snap-fit on DIN rail (EN 60715)
Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
1
Busbar type
LINE (+) and GND (-); max 60A in various lengths of up to 1m
Output terminals
3x LOAD (+) and 3x GND (-)
Terminal type
Push in terminals
Terminal capacity
2.5 mm² (flexible with ferrules)
4 mm² (rigid)
Design verification as per IEC/EN 61439 - technical data
Rated operational current for specified heat dissipation (In)
2 A
Equipment heat dissipation, current-dependent
0.4 W
Ambient operating temperature details
-30° C - 55° C
Permitted storage and transport temperature - min
-40 °C
Permitted storage and transport temperature - max
100 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Features
Green = OK; Red = Triggered
OFF = Channel not in operation
Two-colored
Functions
DC-voltage over current
Special features
Inductive loads: up to 13 A
On/Off/Reset
Text field type
17.5 mm x 6 mm