Standards
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
35.5 (2 PE) x 90 x 58 mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Relative humidity, non-condensing (IEC/EN 60068-2-30)Air humidity, non-condensing, min.
5 %
Relative humidity, non-condensing (IEC/EN 60068-2-30)Air humidity, non-condensing, max.
95 %
Air pressure (operation)
795 - 1080 hPa
Max. installation altitude above sea level, observe derating with higher altitudes
2000 m
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Air discharge
8 kV
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst pulses (IEC/EN 61000-4-4, level 3)
2 kV
Power pulses (surge) (IEC/EN 61000-4-5)
2 (supply cables, symmetrical) kV
High-energy pulses (surge) (IEC/EN 61000-4-5, level 2), 24 V
0.5 (outgoer cables symmetrical, EASY…DC) kV
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Surge voltage (EN 50178), 24 V
6 kV
Clearance in air and creepage distances
EN 50178
Insulation resistance
EN 50178
Protection class Uoutto Uin
Class II to IEC 60536
Potential isolation primary/secondary
Yes, SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178
Rated voltage
100/120/230/240 (-15/+10 %) V
Protective switches AC
FAZ-C1/1 or FAZ-B6/1
Voltage range
85 - 264 V AC
Frequency range
47 - 63 Hz
Mains failure bridging 115/230 V (IEC/EN 61000-4-11)
> 10/> 20 ms
Power consumption
Normally 7 W
Power loss [P]
Normally 1 W
Input current nominal 115/240 V
Approx. 170/80 mA
Inrush current at 25 °C 230 V
< 5 A
12 V DC (reference voltage)Rated value
12 V DC
12 V DC (reference voltage)Tolerance
± 4 %
12 V DC (reference voltage)Switching peaks
< 7 mVSS
12 V DC (reference voltage)Effect of input voltage
± 1 %
12 V DC (reference voltage)Effect with 25 - 100 % load change
± 1 %
24 V DCRated value
24 V DC
24 V DCSwitching peaks 115/230
< 50/30 mVPP
24 V DCEffect of input voltage
± 1 %
24 V DCEffect with 25 - 100 % load change
± 1 %
12 V DC (reference voltage)Output current
0 - 20 mA
12 V DC (reference voltage)Effectiveness of current limitation
20 mA
12 V DC (reference voltage)Reduction of output voltage after current limitation
< 12 V
12 V DC (reference voltage)Overload proof
Yes, by current limitation permanently short-circuit proof
12 V DC (reference voltage)Proof against sustained short circuit
Yes
24 V DCOutput current
0 - 0.35 A
24 V DCEffectiveness of current limitation
> 0.4 A
24 V DCOverload proof
Yes, by current limitation
24 V DCProof against sustained short circuit
Yes, hickup-mode
Lamp load, cold, 24 V DC
2 W
Behaviour on emergency-stop in 24 V circuit, disconnection with contactor (contactor load, no damage)
6 W
Indication of output voltage (LED, continuous green light = OK)
24 V DC