10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Operating frequency
5000 mechanical Operations/h (AC operated)
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Connection to SmartWire-DT
Rated impulse withstand voltage (Uimp)
Utilization category
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
AC-3: Normal AC induction motors: starting, switch off during running
Ambient operating temperature - max
Ambient operating temperature - min
Ambient operating temperature (enclosed) - max
Ambient operating temperature (enclosed) - min
Ambient storage temperature - max
Ambient storage temperature - min
Assigned motor power at 115/120 V, 60 Hz, 1-phase
Assigned motor power at 200/208 V, 60 Hz, 3-phase
Assigned motor power at 230/240 V, 60 Hz, 1-phase
Assigned motor power at 230/240 V, 60 Hz, 3-phase
Assigned motor power at 460/480 V, 60 Hz, 3-phase
Assigned motor power at 575/600 V, 60 Hz, 3-phase
Conventional thermal current ith (1-pole, enclosed)
Conventional thermal current ith (3-pole, enclosed)
Conventional thermal current ith at 55°C (3-pole, open)
Conventional thermal current ith of main contacts (1-pole, open)
Heat dissipation capacity Pdiss
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Electrical connection type of main circuit
Screwdriver size
3.0 x 0.5 mm, Terminal screw
3 x 0.5 mm, Terminal screw
Number of auxiliary contacts (normally closed contacts)
Number of auxiliary contacts (normally open contacts)
Number of contacts (normally closed contacts)
Number of contacts (normally closed) as main contact
Number of contacts (normally open contacts)
Number of main contacts (normally open contact)
Rated breaking capacity at 220/230 V
Rated breaking capacity at 380/400 V
Rated breaking capacity at 500 V
Rated breaking capacity at 660/690 V
Rated control supply voltage (Us) at AC, 50 Hz - max
Rated control supply voltage (Us) at AC, 50 Hz - min
Rated control supply voltage (Us) at AC, 60 Hz - max
Rated control supply voltage (Us) at AC, 60 Hz - min
Lifespan, mechanical
10,000,000 Operations (AC operated)
Power consumption, pick-up, 50 Hz
52 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Safe isolation
400 V AC, Between the contacts, According to EN 61140
400 V AC, Between coil and contacts, According to EN 61140
Power consumption, pick-up, 60 Hz
67 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Power consumption, sealing, 50 Hz
7.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Power consumption, sealing, 60 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
Rated operational current (Ie)
Terminal capacity (flexible with ferrule)
1 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
Shock resistance
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
6.5 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
8 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
2 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms
Terminal capacity (solid)
1 x (0.5 - 0.25) mm²
2 x (1 - 6) mm²
1 x (1 - 6) mm²
2 x (0.5 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)
18 - 8, Main cables
20 - 14
Terminal capacity (flexible)
2 x (0.5 - 2.5) mm²
1 x (1 - 10) mm²
2 x (1-6) mm²
1 x (0.5 - 2.5) mm²
Rated control supply voltage (Us) at DC - max
Rated control supply voltage (Us) at DC - min
Rated insulation voltage (Ui)
Rated making capacity up to 690 V (cos phi to IEC/EN 60947)
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
Rated operational current (Ie) at AC-3, 440 V
Rated operational current (Ie) at AC-3, 500 V
Rated operational current (Ie) at AC-3, 660 V, 690 V
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V
Rated operational current (Ie) at AC-4, 400 V
Rated operational current (Ie) at AC-4, 440 V
Rated operational current (Ie) at AC-4, 500 V
Rated operational current (Ie) at AC-4, 660 V, 690 V
Rated operational power at AC-3, 240 V, 50 Hz
Rated operational power at AC-3, 380/400 V, 50 Hz
Rated operational power at AC-3, 415 V, 50 Hz
Rated operational power at AC-4, 220/230 V, 50 Hz
Rated operational power at AC-4, 240 V, 50 Hz
Rated operational power at AC-4, 380/400 V, 50 Hz
Rated operational power at AC-4, 415 V, 50 Hz
Rated operational power at AC-4, 440 V, 50 Hz
Rated operational power at AC-4, 500 V, 50 Hz
Rated operational power at AC-4, 660/690 V, 50 Hz
Rated operational power (NEMA)
Rated operational voltage (Ue) at AC - max
Switching time (AC operated, make contacts, closing delay) - max
Switching time (AC operated, make contacts, closing delay) - min
Switching time (AC operated, make contacts, opening delay) - max
Switching time (AC operated, make contacts, opening delay) - min
Short-circuit current rating (high fault at 480 V)
65 kA, CB, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA)
Suitable for
Also motors with efficiency class IE3
Operating voltage at AC, 50 Hz - min
Operating voltage at AC, 50 Hz - max
Operating voltage at AC, 60 Hz - min
Operating voltage at AC, 60 Hz - max