ANUNCIAR
STN0,1(*/*) 204939 Y7-204939 EATON ELECTRIC Control transformer, 100VA, 1p, non-standard voltage View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

STN0,1(*/*) 204939 Y7-204939 EATON ELECTRIC Control transformer, 100VA, 1p, non-standard voltage

STN0,1(*/*)

204939

Y7-204939

EATON-MOELLER

Control transformer, 100VA, 1p, non-standard voltage

STN0,1(*/*)

Eaton Moeller® series STN Control transformer, 0.1 kVA, Rated input voltage 100 – 690 ± 5 % V, Rated output voltage 12 – 250 V

Control transformer, Product range: Single-phase control transformers ST..., Basic function: Single-phase STN control transformers, Rated input voltage: 100 – 690 ± 5 % V, Rated output voltage: 12 – 250 V, Rated power: 0.1 kVA, Short-time rating: 0.16 kVA, Degree of Protection: IP00, Standards Built and tested to: IEC/EN 61558-2-2, VDE 0570 Part 2-2, Suitable for use to: IEC/EN 60204-1, ÖVE-EN 13, VDE 0113, VDE 0100 Part 410

More details


Low-voltage industrial components > One-phase control transformer

Transformers

Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total: $131.18
Unit price: $131.18
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



General specifications

Product Name
Eaton Moeller® series STN Control transformer
Catalog Number
204939
Model Code
STN0,1(*/*)
Product Length/Depth
75 mm
Product Height
91 mm
Product Width
85 mm
Product Weight
1.5 kg
Certifications
CE
VDE 0113, VDE 0100 Part 410
CSA-C22.2 No. 66.2-06
UL Recognized
IEC/EN 61558-2-2
CSA-C22.2 No. 66
IEC/EN 60204-1, ÖVE-EN 13
UL5085-1
UL 5085-2
UL Category Control No.: XPTQ2, XPTQ8
VDE 0570 Part 2-2
UL report applies to both US and Canada
Certified by UL for use in Canada
UL 506
CSA-C22.2 No. 66.1-06
UL File No.: E167225
Catalog Notes
Electrical characteristics: all details for no-load loss, short-circuit loss (copper losses), short-circuit voltage and efficiency values relate to a temperature of 20 °C

Features & Functions

Features
Fully Vacuum-impregnated
Separate windings

General

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
40 °C
Connection lug
Yes for > 115 A
Connection type
Terminations, < 115 A
Duty factor
100 %
Insulation class
B
Primary tapping
± 5 %
Product category
Single-phase control transformers ST
Suitable for
Branch circuits, (UL/CSA)
Type
Single-phase STN control transformers

Electrical rating

Efficiency
84 %
No-load losses
7 W
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated power
0.1 VA
Relative short-circuit voltage
10 %
Short-circuit losses
15 W
Short-time rating
0.16 kVA
Voltage rating - max
600 V

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
22 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 204939 Low-voltage industrial controls and switchgear (EC002486)
Feature Name Feature Value
Built as safety transformer (EF007235) No
Built as isolating transformer (EF007238) No
Built as energy saving transformer (EF007005) No
Primary voltage 1 (EF006125) 100 V
Primary voltage 2 (EF006126) 0 V
Primary voltage 3 (EF006127) 0 V
Primary voltage 4 (EF007410) 0 V
Primary voltage 5 (EF007411) 0 V
Primary voltage 6 (EF007412) 0 V
Primary voltage 7 (EF007413) 0 V
Primary voltage 8 (EF007414) 0 V
Primary voltage 9 (EF007415) 0 V
Primary voltage 10 (EF007409) 0 V
Secondary voltage 1 (EF007472) 12 V
Secondary voltage 2 (EF007474) 0 V
Secondary voltage 3 (EF007475) 0 V
Secondary voltage 4 (EF007476) 0 V
Secondary voltage 5 (EF007477) 0 V
Secondary voltage 6 (EF007478) 0 V
Secondary voltage 7 (EF007479) 0 V
Secondary voltage 8 (EF007480) 0 V
Secondary voltage 9 (EF007481) 0 V
Secondary voltage 10 (EF007473) 0 V
Rated apparent power (EF008864) 100 VA
Power consumption in standby mode (EF012331) 11 W
Type of insulation material according to IEC 85 (EF007299) B
Short-circuit-proof (EF007332) No
Relative short circuit voltage (EF007452) 10 %
Width (EF000008) 85 mm
Height (EF000040) 91 mm
Depth (EF000049) 75 mm
Degree of protection (IP) (EF005474) IP00
Ring core (EF006170) No
Suitable for mounting on PCB (EF006157) No
Modular version (EF001126) No
Conductor material (EF001622) Copper

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.