Standards
IEC/EN 60947, VDE 0660, UL, CSA, CCC
Lifespan, mechanicalAC operated [Operations]
5 x 106
Lifespan, mechanicalDC operated [Operations]
5 x 106
Operating frequency, mechanicalAC operated [Operations/h]
1000
Operating frequency, mechanicalDC operated [Operations/h]
1000
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-40 - +60 °C
Ambient temperatureStorage
- 40 - + 80 °C
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/C contact
8 g
Terminal capacity main cableBusbar [Width]
100 mm
Main cable connection screw/bolt
M12
Terminal capacity control circuit cablesSolid
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesSolid or stranded
18 - 14 AWG
Control circuit cable connection screw/bolt
M3.5
ToolMain cableWidth across flats
18 mm
ToolControl circuit cablesPozidriv screwdriver
2 Size
ToolControl circuit cablesStandard screwdriver
0.8 x 5.5/1 x 6 mm
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
1000 V AC
Rated operational voltage [Ue]
1000 V AC
Safe isolation to EN 61140between coil and contacts
500 V AC
Safe isolation to EN 61140between the contacts
500 V AC
Making capacity (p.f. to IEC/EN 60947)
9840 A
Breaking capacity220 V 230 V
8200 A
Breaking capacity380 V 400 V
8200 A
Breaking capacity500 V
8200 A
Breaking capacity660 V 690 V
8200 A
Breaking capacity1000 V
5800 A
Component lifespan
AC1: See → Engineering, characteristic curves
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
3185 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 50 °C [Ith=Ie]
2847 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 55 °C [Ith=Ie]
2716 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 60 °C [Ith=Ie]
2600 A
AC-1Rated operational currentConventional free air thermal current, 1 poleNote
at maximum permissible ambient air temperature
AC-1Rated operational currentConventional free air thermal current, 1 poleopen [Ith]
6500 A
Current heat loss at Ieto AC-3/400 V
0.012 W
Voltage toleranceUS
230 - 250 V 50/60 Hz
230 - 350 V DC
Voltage toleranceAC operated [Pick-up]
0.7 x US min- 1.15 x US max
Voltage toleranceDC operated [Pick-up]
0.7 x US min- 1.15 x US max
Voltage toleranceAC operated [Drop-out]
0.2 x US max- 0.6 x US min
Voltage toleranceDC operated [Drop-out]
0.2 x US max- 0.6 x US min
Power consumption of the coil in a cold state and 1.0 x USNote on power consumption
Control transformer with uk≦ 7%
Power consumption of the coil in a cold state and 1.0 x USPull-in power [Pick-up]
1600 VA
Power consumption of the coil in a cold state and 1.0 x USPull-in power [Pick-up]
1400 W
Power consumption of the coil in a cold state and 1.0 x USSealing power [Sealing]
36.5 VA
Power consumption of the coil in a cold state and 1.0 x USSealing power [Sealing]
17.3 W
Changeover time at 100 % US(recommended value)Main contactsClosing delay
70 ms
Changeover time at 100 % US(recommended value)Main contactsOpening delay
40 ms
Behaviour in marginal and transitional conditionsSealingVoltage interruptions(0 … 0.2 x Uc min) ≦ 10 ms
Time is bridged successfully
Behaviour in marginal and transitional conditionsSealingVoltage interruptions(0 … 0.2 x Uc min) > 10 ms
Drop-out of the contactor
Behaviour in marginal and transitional conditionsSealingVoltage drops(0.2 … 0.6 x Uc min) ≦ 12 ms
Time is bridged successfully
Behaviour in marginal and transitional conditionsSealingVoltage drops(0.2 … 0.6 x Uc min) > 12 ms
Drop-out of the contactor
Behaviour in marginal and transitional conditionsSealingVoltage drops(0.6 … 0.7 x Uc min)
Contactor remains switched on
Behaviour in marginal and transitional conditionsSealingExcess voltage(1.15 … 1.3 x Uc max)
Contactor remains switched on
Behaviour in marginal and transitional conditionsSealingPick-up phase(0 … 0.7 x Uc min)
Contactor does not switch on
Behaviour in marginal and transitional conditionsSealingPick-up phase(0.7 x Uc min… 1.15 x Uc max)
Contactor switches on with certainty
Admissible transitional contact resistance (of the external control circuit device when actuating A11)
≦ 500 mΩ
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)High
15 V
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)Low
5 V
Electromagnetic compatibility (EMC)
Electromagnetic compatibility
This product is designed for operation in industrial environments (environment A). Its use in residential environments (environment B) may cause radio-frequency interference, requiring additional noise suppression measures.
Rating data for approved types
Switching capacityGeneral use
2600 A
Auxiliary contactsPilot DutyAC operated
A600
Auxiliary contactsPilot DutyDC operated
P300
Auxiliary contactsGeneral UseAC
600 V
Auxiliary contactsGeneral UseAC
15 A
Auxiliary contactsGeneral UseDC
250 V
Auxiliary contactsGeneral UseDC
1 A
Special Purpose RatingsResistance Air Heating480V 60Hz 3phase, 277V 60Hz 1phase
2600 A
Special Purpose RatingsResistance Air Heating600V 60Hz 3phase, 347V 60Hz 1phase
2600 A