Product successfully added to your shopping cart
04DILE
010256
Y7-10256
EATON-MOELLER
1
Auxiliary contact, 4 N/C, surface mounting, screw connection
Auxiliary Contact Block 4 NC Front Mount Connection To
Eaton Moeller® series DILE Auxiliary contact module, 4 pole, 4 NC, Front fixing, Screw terminals, DILE(E)M, DILER
Auxiliary contact module, with interlocked opposing contacts, Switching elements according to EN 50005, Switching elements according to EN 50012 are to be preferred., Version E combinations correspond to EN 50011 and are to be preferred., Function: for standard applications, 4 pole, Connection technique: Screw terminals, Rated operational current AC-15 220 V 230 V 240 V: Ie= 4 A, Rated operational current AC-15 380 V 400 V 415 V: Ie= 2 A, Contacts N/C = Normally closed: 4 NC, Mounting type: Front fixing, For use with: DILEM-10(-G)(…), DILEM-01(-G)(…), DILEM-4(-G)(…), DILER40(-G), DILER31(-G), DILER22, DILEEM-10(-G)(…), DILEEM-01(-G)(…) , DILEM12-10(-G)(…), DILEM12-01(-G)(…), Instructions: Interlocked opposing contacts according to IEC/EN 60947-5-1 appendix L, inside the auxiliary contact
Low-voltage industrial components > Auxiliary contact block
Contactors up to 170A
Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER
| Product Name | Eaton Moeller® series DILE Accessory Auxiliary contact module |
| Catalog Number | 010256 |
| Model Code | 04DILE |
| EAN | 4015080102564 |
| Product Length/Depth | 36 mm |
| Product Height | 32 mm |
| Product Width | 45 mm |
| Product Weight | 0.04 kg |
| Certifications | CE IEC/EN 60947-4-1 CSA-C22.2 No. 14-05 UL CSA Class No.: 3211-03 CSA File No.: 012528 UL 508 IEC/EN 60947 CSA UL Category Control No.: NKCR UL File No.: E29184 VDE 0660 |
| Electric connection type | Screw connection |
| Features | Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L) |
| Fitted with: | Interlocked opposing contacts Switching elements according to EN 50005 |
| Functions | For standard applications |
| Number of poles | Four-pole |
| Lifespan, mechanical | 10,000,000 Operations (AC operated) 20,000,000 Operations (DC operated) 200,000 Operations (at 240 V, AC-15) 150,000 Operations (at 240 V, DC, L/R = 50 ms: 2 contacts in series 0.5 A) |
| Model | Top mounting |
| Mounting method | Front fastening |
| Mounting position | As required (except vertical with terminals A1/A2 at the bottom) |
| Operating frequency | 9000 Operations/h |
| Overvoltage category | III |
| Pollution degree | 3 |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Shock resistance | 10 g, N/O contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 8 g, N/C contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 50 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 80 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 1.5) mm² 2 x (0.75 - 1.5) mm² |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) | Single 18 – 14, double 18 – 14 |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver 2, Terminal screw, Pozidriv screwdriver |
| Tightening torque | 1.2 Nm, Screw terminals |
| Rated operational voltage (Ue) at AC - max | 600 V |
| Rated insulation voltage (Ui) | 690 V |
| Rated operational current (Ie) | 1.5 A at 110 V, DC L/R ≤ 15 ms (with 3 contacts in series) 2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series) 2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series) 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series) |
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 4 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 2 A |
| Rated operational current (Ie) at AC-15, 500 V | 1.5 A |
| Safe isolation | 300 V AC, Between coil and auxiliary contacts, According to EN 61140 300 V AC, Between auxiliary contacts, According to EN 61140 |
| Short-circuit protection rating | 10 A fast, 500V, Maximum fuse, Short-circuit rating without welding, Contacts |
| Short-circuit protection rating without welding | 6 A gG/gL, 500 V, Max. Fuse, Contacts |
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) | 10 A |
| Switching capacity (auxiliary contacts, general use) | 0.5 A, 250 V DC, (UL/CSA) 10 A, 600 V AC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA) A600, AC operated (UL/CSA) |
| Code number | 35 in combination with DILER-31(-G) 26 in combination with DILER-22 44E |
| Control circuit reliability | < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 4 |
| Number of contacts (normally open contacts) | 0 |
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.24 W |
| Rated operational current for specified heat dissipation (In) | 4 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| Feature Name | Feature Value |
|---|---|
| Number of contacts as change-over contact (EF008257) | 0 |
| Number of contacts as normally open contact (EF008256) | 0 |
| Number of contacts as normally closed contact (EF008255) | 4 |
| Number of fault-signal switches (EF007613) | 0 |
| Rated operation current Ie at AC-15, 230 V (EF001385) | 4 A |
| Type of electric connection (EF003961) | Screw connection |
| Model (EF000010) | Clip-on |
| Mounting method (EF000003) | Front fastening |
| Lamp holder (EF000048) | None |
| Title: | Size: | Type: |
|---|---|---|
| PDF EATON SWITCHING PROTECTING MOTORS EN.pdf | 35 Mbytes |
|
| PDF CATALOGUE EATON EN .pdf | 38 Mbytes |
|
| 04DILE Y7-10256 010256 EN_230260.pdf | 1 Mbytes |
![]() |
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.