Selected parameters MAIN CHARACTERISTICS Output module HOUSING Decentral POWER SUPPLY Bus-powered I/O TYPE Relay output NUMBER OF I/O 1 Others MODULE TYPE Output module HOUSING 50 x 50 x 30 I/O TYPE 5A SPDT relay POWER SUPPLY Bus-powered MAIN CHARACTERISTICS Bus-powered decentral relay module for control of one roller blind motor

More details


Home Smart Intelligent Building Automation

Fieldbuses

Home and Building Automation Systems

* Brand new produt in its original packing covered by the warranties and certifications provided by CARLO GAVAZZI

QuantityPrice
1+181,12 €
2+176,45 €
3+174,14 €
4+172,66 €
5+171,89 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Output Module for Rollerblind Motor
Type G 8830 2149 230
Duline®
FieldbusInstallationbus
• Up/down control of 1 rollerblind motor
• Up/down interlocking for motor
• AC power supply
• Channel coding by GAP 1605
• Design for mounting in Euro box
Product Description Ordering Key
G 8830 2149 230
Dupline®output module for up/down control of one rollerblind motor. A built-in up/down interlocking function protects the motors. The motorrequires twoDupline® channels, one for“UP” and one for “DOWN”. For intelli-
gent control of the rollerblind motors it is recommended to use the Master Generator G3800x01x which has this function built in.
Type: Dupline® Housing Receiver
No. of channels Output type Power supply
Type Selection
Supply Ordering no.
2 channel
5 A/250 VAC
230 VACG 8830 2149 230
General Specifications
Supply Specifications
Power supply AC typesInstallations cat. III (IEC 60664) Rated operational voltage
through wire L & N 230230 VAC ± 15% (IEC 60038)
Frequency 45 to 65 Hz Drop-out tolerance≤ 40 ms Power consumptionTyp. 3.3 VA Power dissipation≤ 2 W
Transient protection volt. 2304 kV
Output OFF delay
Upon loss of Dupline®carrier 20 ms
Power ON delayTyp. 2 s Power OFF delay≤ 1 s Environment
Pollution degree3 (IEC 60664)
Operating temperature-20° to +50°C (-4° to +122°F) Storage temperature -50° to +85°C (-58° to +185°F)
Humidity (non-condensing)20 to 80%
Mechanical resistance
Shock15 G (11 ms) Vibration2 G (6 to 55 Hz)
Dimensions (h x w x d) 50 x 50 x 30
MaterialABS
Weight100 g
Insulation voltage
Supply - Dupline® ≥ 4 kVAC (rms) Supply - Outputs≥ 4 kVAC (rms) Dupline®- Outputs≥ 4 kVAC (rms)
Consumption on Dupline®
Normal consumption≤ 0.5 mA Consumption 1 relay on ≤ 1.8 mA Consumption 2 relay on ≤ 3.2 mA
Output Specifications
Outputs1 SPST relay & 1 SPDT relay
Resistive loads AC 15 A/250 VAC (1250 VA) DC 10.25 A/250 VDC (62 W)
or
Inductive loads AC 152.5 A/230 VAC DC 135 A/24 VDC
Mechanical lifetime ≥ 30 x 106 operations
Electrical lifetime
(at max load) AC 1≥ 2.0 x 105 operations Operating frequency ≤ 7200 operations/h Insulation voltage
Outputs - Dupline®≥ 4 kVAC (rms)
Response time1 pulse train
Specifications are subject to change without notice (23.01.2007) 1
Dupline®is a registered trademark. A product of the CARLO GAVAZZI Group

Datasheet - PDF

Title:Language:Size:Type:
pdf1-mostradoSelected parameters MAIN CHARACTERISTICS Output module HOUSING Decentral POWER SUPPLY - CARLO GAVEnglish109 Kbytespdf1-mostradoSelected parameters MAIN CHARACTERISTICS Output module HOUSING Decentral POWER SUPPLY - CARLO GAV
pdf1-Selected parameters MAIN CHARACTERISTICS Output module HOUSING Decentral POWER SUPPLY - CARLO GEnglish12 Mbytespdf1-mostradoSelected parameters MAIN CHARACTERISTICS Output module HOUSING Decentral POWER SUPPLY - CARLO GAV

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review