1SDA073380R1 ABB E6.2V/f 6300 Ekip G Hi-Touch LSIG 4p WMP View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

1SDA073380R1 ABB E6.2V/f 6300 Ekip G Hi-Touch LSIG 4p WMP

1SDA073380R1

ABB

E6.2V/f 6300 Ekip G Hi-Touch LSIG 4p WMP

More details


Low-voltage industrial components > Power circuit-breaker for trafo/generator/installation protection

Rack "Megamax-Emax" > E6.2

Brand new product in its original packaging covered by the warranties and certifications provided by ABB

Total: $77,631.45
Unit price: $77,631.45
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions9AKK108468A2364
Environmental Product Declaration - EPD9AKK108468A1905
9AKK108468A1913
Extended Product LifetimeLifetime Extension Services are Offered
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 77 %
Material Compliance
REACH Declaration9AKK108466A1425
RoHS Declaration9AKK108466A1424
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
Toxic Substances Control Act - TSCA9AKK108467A8326
SCIP33cd6e47-d519-4cc5-952e-6d4eb62e66bc Italy
Simplified SCIP0644f634-086b-4b34-9e0e-10e8b2cce95a Germany
da45963e-c0d3-4513-873a-ac1c5b3ab73d Hungary
003fccf3-836b-49a3-b838-368e5d2f454b France
a10e98b7-7161-415d-8f36-8a7d2b4ea033 Hungary
f32f44e7-df08-4326-9e7b-ae5829d9a95a Sweden
1955924b-775a-4da5-885c-347c0f111dd8 Bulgaria
032e6906-8c5f-4cf3-8e55-10ab5c5c979b Portugal
ee16c2fd-f177-47c4-8aff-1a8288b9d2a3 Poland
01a07276-ef42-4ebb-8985-7a843adcf6cc Poland
512d0d9c-d485-4b70-a87d-a81e1d8bcab1 Czech Republic
7a8a2b44-2baa-46ba-98b2-96fbb92f36ea Spain
6f15f8e7-bd83-47b7-ae9b-2fccdfd36c79 Belgium
61fb3060-040f-49b5-8d54-1480d67d13ab France
5cf1229a-55fc-46c1-a11f-740426676dad Sweden
a7b1956c-6b6f-4e64-84db-0fac23999b46 Estonia
4ad2cc15-584b-4819-b404-e1495c644d77 Finland
c68cad60-8c3f-4c8e-a05a-ceb551ec887a Netherlands
9a4054f5-7e93-4aac-b3ed-53cfe701dee7 Belgium
e8294e02-ed54-459c-ad1b-f67cdb2c83b5 Germany
d7dc3dad-7f69-47fb-9ddc-bc9d5b59da8c Germany
64f8e085-5673-4a3d-8933-b5d5a778cfa5 Greece
42e86b41-e32d-4004-86a9-4573526dcfc8 Denmark
a39ba834-1288-4fc8-9228-3a148c5f118d Germany
87495152-dd54-4b5e-9769-7d22fcb8d3c4 Croatia
35a27a85-205d-4d61-8572-f6433e7dde77 Germany
973bc054-6dc3-4d2f-8bb7-4d91779980d2 Norway
2235d73e-4fa4-42a7-a46d-172b3ce95aa0 Poland
Environmental
Environmental Information9AKK108467A6707
Ordering
Order Code US and CanadaZEVYETAQ000A000000XX
EAN8015644772307
Minimum Order Quantity1 piece
Customs Tariff Number85362090
Dimensions
Product Net Width1069 mm
Product Net Height425 mm
Product Net Depth / Length383 mm
Product Net Weight148 kg
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width515 mm
Package Level 1 Height610 mm
Package Level 1 Depth / Length1257 mm
Package Level 1 Gross Weight159 kg
Package Level 1 EAN8015644772307
Additional Information
Product Main TypeSACE Emax 2
Product NameAir Circuit Breaker
Product TypeAir Circuit Breaker
VersionW
Technical
Connecting Capacity6000 mm²
Current TypeAC
Electrical DurabilityUe =< 440 V 2000 cycle
Ue = 500 ... 690 V 2000 cycle
10 cycles per hour
Mechanical Durability12000 cycle
60 cycles per hour
Neutral Pole Current ([%Iu])100 %
Number of Poles4 / f
Power Loss1550 W
Rated Current (In)6300 A
Rated Impulse Withstand Voltage (Uimp)acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)AC 1000 V
Rated Operational Voltage690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 150 kA
(230 V AC) 150 kA
(380 V AC) 150 kA
(400 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 150 kA
(500 V AC) 130 kA
(660 V AC) 100 kA
(690 V AC) 100 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100 %
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 100 kA
for 3 s 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 150 kA
(415 V AC) 150 kA
(440 V AC) 150 kA
(500 V AC) 130 kA
(525 V AC) 130 kA
(690 V AC) 100 kA
Rated Uninterrupted Current (Iu)6300 A
Rated Voltage (Ur)690 V
Recommended Screw DriverM12
ReleaseEkip G Hi-Touch LSIG
Release TypeEL
Short-Circuit Performance LevelV
StandardsIEC
Sub-typeE6.2
Suitable for IT NetworksYes, 690V
Certificates and Declarations
Data Sheet, Technical Information1SDC200023D0209
Declaration of Conformity - CE9AKK106713A5544
EU Data Act Compliance Declaration1SDH002560A1001
Instructions and Manuals1SDH001000R0002
Instructions and Manuals (Part 2)1SDH001316R1002
External Classifications and Standards
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification CodeQ
WEEE Category4. Large Equipment (Any External Dimension More Than 50 cm)
eClassV11.1 : 27370409

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.