| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC175975_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101036M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 70 mm |
| Product Net Depth / Length | 116 mm |
| Product Net Height | 125.5 mm |
| Product Net Weight | 1.22 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60335-2-40 LZGH2 A2L, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22 |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 130 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 125 A |
| (690 V) 60 °C 100 A | |
| (690 V) 70 °C 85 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 80 A |
| (440 V) 60 °C 80 A | |
| (500 V) 60 °C 65 A | |
| (690 V) 60 °C 49 A | |
| (1000 V) 60 °C 25 A | |
| (380 / 400 V) 60 °C 80 A | |
| (220 / 230 / 240 V) 60 °C 80 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 80 A |
| (440 V) 60 °C 80 A | |
| (500 V) 60 °C 65 A | |
| (690 V) 60 °C 49 A | |
| (380 / 400 V) 60 °C 80 A | |
| (220 / 230 / 240 V) 60 °C 80 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 125 A |
| (110 V) 2 Poles in Series, 60 °C 100 A | |
| (110 V) 2 Poles in Series, 70 °C 85 A | |
| (110 V) 3 Poles in Series, 40 °C 125 A | |
| (110 V) 3 Poles in Series, 60 °C 100 A | |
| (110 V) 3 Poles in Series, 70 °C 85 A | |
| (220 V) 3 Poles in Series, 40 °C 125 A | |
| (220 V) 3 Poles in Series, 60 °C 100 A | |
| (220 V) 3 Poles in Series, 70 °C 85 A | |
| (72 V) 1-Pole, 40 °C 125 A | |
| (72 V) 1-Pole, 60 °C 100 A | |
| (72 V) 1-Pole, 70 °C 85 A | |
| (72 V) 2 Poles in Series, 40 °C 125 A | |
| (72 V) 2 Poles in Series, 60 °C 100 A | |
| (72 V) 2 Poles in Series, 70 °C 85 A | |
| (72 V) 3 Poles in Series, 40 °C 125 A | |
| (72 V) 3 Poles in Series, 60 °C 100 A | |
| (72 V) 3 Poles in Series, 70 °C 85 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 125 A |
| (110 V) 2 Poles in Series, 60 °C 100 A | |
| (110 V) 2 Poles in Series, 70 °C 85 A | |
| (110 V) 3 Poles in Series, 40 °C 125 A | |
| (110 V) 3 Poles in Series, 60 °C 100 A | |
| (110 V) 3 Poles in Series, 70 °C 85 A | |
| (220 V) 3 Poles in Series, 40 °C 125 A | |
| (220 V) 3 Poles in Series, 60 °C 100 A | |
| (220 V) 3 Poles in Series, 70 °C 85 A | |
| (72 V) 1-Pole, 40 °C 125 A | |
| (72 V) 1-Pole, 60 °C 100 A | |
| (72 V) 1-Pole, 70 °C 85 A | |
| (72 V) 2 Poles in Series, 40 °C 125 A | |
| (72 V) 2 Poles in Series, 60 °C 100 A | |
| (72 V) 2 Poles in Series, 70 °C 85 A | |
| (72 V) 3 Poles in Series, 40 °C 125 A | |
| (72 V) 3 Poles in Series, 60 °C 100 A | |
| (72 V) 3 Poles in Series, 70 °C 85 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 125 A |
| (110 V) 2 Poles in Series, 60 °C 100 A | |
| (110 V) 2 Poles in Series, 70 °C 85 A | |
| (110 V) 3 Poles in Series, 40 °C 125 A | |
| (110 V) 3 Poles in Series, 60 °C 100 A | |
| (110 V) 3 Poles in Series, 70 °C 85 A | |
| (220 V) 3 Poles in Series, 40 °C 125 A | |
| (220 V) 3 Poles in Series, 60 °C 100 A | |
| (220 V) 3 Poles in Series, 70 °C 85 A | |
| (72 V) 1-Pole, 40 °C 125 A | |
| (72 V) 1-Pole, 60 °C 100 A | |
| (72 V) 1-Pole, 70 °C 85 A | |
| (72 V) 2 Poles in Series, 40 °C 125 A | |
| (72 V) 2 Poles in Series, 60 °C 100 A | |
| (72 V) 2 Poles in Series, 70 °C 85 A | |
| (72 V) 3 Poles in Series, 40 °C 125 A | |
| (72 V) 3 Poles in Series, 60 °C 100 A | |
| (72 V) 3 Poles in Series, 70 °C 85 A | |
| Rated Operational Power AC-3 (Pe) | (400 V) 37 kW |
| (415 V) 45 kW | |
| (440 V) 45 kW | |
| (500 V) 45 kW | |
| (690 V) 45 kW | |
| (1000 V) 35 kW | |
| (380 / 400 V) 37 kW | |
| (220 / 230 / 240 V) 22 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 45 kW |
| (440 V) 45 kW | |
| (500 V) 45 kW | |
| (690 V) 45 kW | |
| (380 / 400 V) 37 kW | |
| (220 / 230 / 240 V) 22 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 780 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 1000 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-2 / AC-4) 150 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V |
| 60 Hz 48 ... 130 V | |
| DC Operation 48 ... 130 V | |
| Coil Consumption | Average Holding Value 50 / 60 Hz 4 V·A |
| Average Holding Value 50 Hz 4 V·A | |
| Average Holding Value 60 Hz 4 V·A | |
| Average Holding Value DC 2 W | |
| Average Holding Value, from Warm State 2 W | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 7.6 W |
| at Rated Operating Conditions AC-3 per Pole 3 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 19 ... 105 ms |
| Between Coil De-energization and NO Contact Opening 17 ... 100 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 95 ms | |
| Between Coil Energization and NO Contact Closing 42 ... 100 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 6 ... 50 mm² |
| Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² | |
| Rigid Stranded 1x 6 ... 70 mm² | |
| Rigid Stranded 2x 6 ... 50 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Control Circuit 10 mm |
| Main Circuit 17 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | |
| Recommended Screw Driver | Pozidriv PZ |
| Tightening Torque | Control Circuit 1.2 N·m |
| Main Circuit 6 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| NEMA Size | 3 |
| Continuous Current Rating NEMA | 90 A |
| Horsepower Rating NEMA | (200 V AC) Three Phase 25 Hp |
| (230 V AC) Three Phase 30 Hp | |
| (460 V AC) Three Phase 50 Hp | |
| (575 V AC) Three Phase 50 Hp | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 105 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 7-1/2 hp |
| (200 ... 208 V AC) Three Phase 25 hp | |
| (220 ... 240 V AC) Three Phase 30 hp | |
| (240 V AC) Single Phase 15 hp | |
| (440 ... 480 V AC) Three Phase 60 hp | |
| (550 ... 600 V AC) Three Phase 75 hp | |
| Connecting Capacity Main Circuit UL/CSA | Rigid Stranded 1/2x 6-1 AWG |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
| Main Circuit 53 in·lb | |
| Full Load Amps Motor Use | (120 V AC) Single Phase 80 A |
| (200 ... 208 V AC) Three Phase 78.2 A | |
| (220 ... 240 V AC) Three Phase 80 A | |
| (240 V AC) Single Phase 68 A | |
| (440 ... 480 V AC) Three Phase 77 A | |
| (550 ... 600 V AC) Three Phase 77 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -40 ... 70 °C |
| Close to Contactor without Thermal O/L Relay -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 25 g |
| Closed, Shock Direction: B1 25 g | |
| Closed, Shock Direction: B2 15 g | |
| Closed, Shock Direction: C1 25 g | |
| Closed, Shock Direction: C2 25 g | |
| Open, Shock Direction: B1 5 g | |
| Resistance to Vibrations | 3g Closed Position & 3g Open Position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | e872df34-2ae2-4338-bce5-e2d7fdb14c29 France |
| Simplified SCIP | 26577f56-7b04-41be-8b54-b16f198571be Czech Republic |
| f03f390e-b2e1-400e-a1d4-39b05aee7588 Poland | |
| b6626d18-bf0e-4188-ac41-98f5f6f26f2f Netherlands | |
| 66bc4922-4407-4c7a-9361-4f5e2fab7511 Poland | |
| f772ec71-9bb2-4988-8f70-8a6b7ebe7de4 Sweden | |
| 6cbefbf6-fe44-474c-af89-69361878eb3d France | |
| 32ec3e6c-8834-4cd0-9616-186eac295e46 Sweden | |
| a13903bc-67d0-40f8-9e7e-9d62a6ddf840 Hungary | |
| e79e8198-2668-4932-822c-3bb6dd8e653b Germany | |
| 4da9aaf6-b2e1-4025-86fd-c052cb03635f Germany | |
| a51b0f9f-3b4b-47d6-b4d7-50596c35c474 Spain | |
| c2591a89-837f-4b81-9060-611b20e04076 Belgium | |
| 1acc554c-6950-42a2-b6f1-d46a72134a47 Denmark | |
| ad575596-9f98-46c6-bfbd-89250e8383ac Croatia | |
| d552b1d1-90dd-4f13-9e14-0a140a270897 Germany | |
| fd64798e-c651-4535-a5c6-8c6b79e2a8ff Germany | |
| 5ecb2e1d-c6c3-4e46-9954-f7910ac25027 Hungary | |
| e33be7cc-444c-49fa-96c3-ce2e1fb79592 Norway | |
| 66000da9-ce31-46cb-9092-b9510a881571 Estonia | |
| 6e432897-860d-45bd-aff5-be71466b4189 Greece | |
| 323e43e6-1131-4f55-9ce9-b24563d95ee3 Bulgaria | |
| 71bc6d6d-4040-4c54-ab83-d5115b843309 Portugal | |
| 9d5d9344-c30a-4c42-a045-e08fabe49b57 Italy | |
| 0c00fc9d-b734-4512-aba4-7d4958d0c4b6 Belgium | |
| c0598862-df8d-4e59-bc56-4c3ae4ce5018 Poland | |
| 230c055c-c457-473c-857b-c543b89d5ad6 Finland | |
| e150f0fe-5aa7-42a0-813a-68ca8b0389d1 Germany | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101081M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E2000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 91.9 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4890 |
| 9AKK108469A4892 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H36994B2 |
| CB Certificate | CB_SE-116522 |
| CCC Certificate | CCC_2024010304656667 |
| Declaration of Conformity - CCC | 2020980304001255 |
| Declaration of Conformity - CE | 1SBD250000U1000 |
| Declaration of Conformity - UKCA | 1SBD250031U1000 |
| DNV Certificate | DNV_TAE00001AF-4 |
| KC Certificate | KC_HW02016-15011C |
| LR Certificate | LRS_LR23403517TA-02 |
| RINA Certificate | RINA_ELE084013XG |
| RMRS Certificate | RMRS_1802705280 |
| UL Certificate | UL-US-L312527-1141-10303102-19 |
| UL-CA-L312527-4141-10303102-19 | |
| UL Listing Card | UL_E312527 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 150 mm |
| Package Level 1 Depth / Length | 150 mm |
| Package Level 1 Height | 103 mm |
| Package Level 1 Gross Weight | 1.34 kg |
| Package Level 1 EAN | 3471523132924 |
| Package Level 2 Units | box 8 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 300 mm |
| Package Level 2 Gross Weight | 10.72 kg |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Finland) | 3707121 |
| E-Number (Sweden) | 3210052 |
| Feature Name | Feature Value |
|---|---|
| Rated control supply voltage AC 50 Hz (EF003978) | 48 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 48 V |
| Rated control supply voltage DC (EF003980) | 48 V |
| Voltage type for actuating (EF008242) | AC/DC |
| Rated operation current Ie at AC-1, 400 V (EF001393) | 125 A |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 80 A |
| Rated operation power at AC-3, 400 V (EF001364) | 37 kW |
| Rated operation power NEMA (EF011960) | 37.2850 kW |
| Modular version (EF001126) | No |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Number of normally closed contacts as main contact (EF001375) | 0 |
| Number of normally open contacts as main contact (EF001374) | 3 |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
| AF80-30-00-12 48-130V50/60HZ-DC Contactor - ABB - AF80-30-00-12 - 1SBL397001R1200 | 99 Kbytes |
![]() |
| AF80-30-00-12 1SBL397001R1200 ABB AF80-30-00-12 48-130V50/60HZ-DC Contactor | 80 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.