Product successfully added to your shopping cart
1SDA100833R1
ABB
1
XT7S 1600 Ekip Dip LSI In=1600A 3p F F
Low-voltage industrial components > Power circuit-breaker for trafo/generator/installation protection
Molded case "Isomax-Tmax"
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2357 |
| Environmental Product Declaration - EPD | 9AKK108468A1895 |
| 9AKK108468A4404 | |
| Extended Product Lifetime | Product Modularity |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 64.1 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| SCIP | 938d120b-bb0c-4029-b0ab-af7f28f5d64b Italy |
| Simplified SCIP | 64da3202-f206-4342-bba1-3dc4de88a57b Germany |
| f7bde48c-d693-4f25-83cd-c4819ec966b7 Belgium | |
| 8980f39e-78c3-47c9-9da2-979357e284fe Estonia | |
| 764e7332-6c5d-4064-b5c2-47b28afdafa8 Greece | |
| 957e041a-e468-4958-8e3f-75dcac9d6cdd Portugal | |
| f179e1d2-8fdd-4a87-a260-6cc161bc9e8a Bulgaria | |
| b3e4aa42-32c9-46db-a7df-8fa85ab4e64f Sweden | |
| 72cfd452-e828-4393-abc0-adfcce6d0e57 Hungary | |
| 618cdcd5-324c-4d2a-9bc6-d6652a61d23f Poland | |
| bdbfd276-6f6f-4287-85e6-517cf73a38f1 Norway | |
| 30ec7140-af44-43b1-a5cd-a6aa4128ffc2 Poland | |
| b58a7c51-b535-433a-9581-37ca979360d7 Denmark | |
| 3af11875-89e3-41fc-8d46-c3d00e5c1000 Finland | |
| 975fd852-6aba-41e0-b882-4039fdf484bb France | |
| 4bcf67b0-0834-4263-8b7a-5f85dd82378c Sweden | |
| 3ecb51c3-92b5-41a1-83c4-1fc34c697d34 Croatia | |
| 203a83c3-64a2-4409-95fb-2dfa94d4df24 Germany | |
| 68d8c8db-b15e-478e-92b5-af84019af82c Germany | |
| 4382c240-f3d8-443e-913f-8522e85321d9 Czech Republic | |
| 665a1b50-da68-498d-80db-d352bd54d32b Belgium | |
| 0a3c2c60-41e8-4259-a8ae-e565185ffe83 Netherlands | |
| 4063d69f-b3bc-4580-82d5-ba0f46759b96 Poland | |
| 25589cac-44a9-4ce7-8f3d-e371e6c92348 Germany | |
| dae3c2c9-3f0f-4aa3-a672-ef78fb1fbdac France | |
| 56a03dbf-0ba5-41e2-a00b-d788fb43b771 Spain | |
| d2684dbc-104b-4576-a155-887e4a5b3025 Germany | |
| c7d00536-617e-4b02-ac18-e0a4a1f7db34 Hungary | |
| Environmental | |
| Ambient Air Temperature | Operation -40 ... 125 °C |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT7SE316FFFF000XXX |
| E-Number (Norway) | 4380622 |
| EAN | 8056221008877 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 166 mm |
| Product Net Weight | 9.7 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 280 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Gross Weight | 11.2 kg |
| Package Level 1 EAN | 8056221008877 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002065A1336 |
| 1SDH002065A1338 | |
| Technical | |
| Current Type | AC |
| Electrical Durability | 3000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 10000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 94 W |
| Rated Current (In) | 1600 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 45 kA | |
| (525 V AC) 45 kA | |
| (690 V AC) 30 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (240 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 50 kA | |
| (500 V AC) 45 kA | |
| (525 V AC) 45 kA | |
| (690 V AC) 30 kA | |
| Rated Uninterrupted Current (Iu) | 1600 A |
| Release | Ekip Dip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | S |
| Standards | IEC60947-2 |
| Sub-type | XT7 |
| Terminal Connection Type | Front |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK107046A9648 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| Mechanical Drawings | 1SDH002013A1101 |
| Wiring Diagram | 1SDM000002A1001 |
| Instructions and Manuals | 1SDH002013A1001 |
| 1SDH002013A1002 | |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |
| Feature Name | Feature Value |
|---|---|
| Rated permanent current Iu (EF001389) | 1600 A |
| Rated voltage (EF003977) | 690 V |
| Overload release current setting (EF002336) | 1600 A |
| Adjustment range short-term delayed short-circuit release (EF007129) | 1600 A |
| Adjustment range undelayed short-circuit release (EF007131) | 1600 A |
| Integrated earth fault protection (EF007296) | No |
| Type of electrical connection of main circuit (EF006819) | Bolt connection |
| Device construction (EF008240) | Built-in device fixed built-in technique |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | No |
| DIN rail (top hat rail) mounting optional (EF008904) | No |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 |
| With switched-off indicator (EF007006) | No |
| With integrated under voltage release (EF001390) | No |
| Number of poles (EF001391) | 3 |
| Position of connection for main current circuit (EF006671) | Front |
| Type of control element (EF006976) | Toggle |
| Complete device with protection unit (EF008906) | Yes |
| Motor drive integrated (EF006697) | No |
| Motor drive optional (EF007386) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG ABB TMAX XT EN.pdf | 70 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.