Product successfully added to your shopping cart
1SBH141001R8022
ABB
1
N... contactor relays are used for switching auxiliary circuits and control circuits - Poles: 4-pole contactor relays (mechanically linked contact elements available) - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
Service Breakers
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
b'
N22E 220-230V 50Hz / 230-240V 60Hz
1SBH141001R8022
3471522010803
N22E 220-230V 50Hz / 230-240V 60Hz Contactor Relay
N... contactor relays are used for switching auxiliary circuits and control circuits - Poles: 4-pole contactor relays (mechanically linked contact elements available) - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
India (IN)
No
Active
No
INABB003EXPU
Product under warranty must be returned
1 piece
85364900
44 mm
74 mm
74 mm
0.34 kg
2
2
Devices complying with international standards IEC 947-5-1 / 947-4-1 and European standards EN 60 947-5-1 / 60 947-4-1. Electromagnetic compatibility (EMC) according to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1
Main Circuit 690 V
Supply Circuit 50 60 Hz
acc. to IEC 60947-5-1, q = 40 °C 16 A
(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
gG Type Fuses 10 A
(24 V) 6 / 144 A
(48 V) 2.8 / 134 A
(72 V) 1 / 72 A
(125 V) 0.55 / 69 A
(250 V) 0.3 / 75 A
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
acc. to UL/CSA 600 V
8 kV
> 20 million
6000 cycles per hour
50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Average Holding Value 50 / 60 Hz 8 2 V·A
Average Pull-in Value 50 Hz 74 V·A
Average Pull-in Value 60 Hz 70 V·A
Holding at Max. Rated Control Circuit Voltage 50 Hz 8 2 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 8 2 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 70 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 80 V·A
Between Coil De-energization and NC Contact Closing 9 ... 16 ms
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NC Contact Opening 7 ... 21 ms
Between Coil Energization and NO Contact Closing 10 ... 26 ms
Flexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Screw Terminals
Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C
Near Contactor for Operation in Free Air (Uc) -40 ... +70 °C
acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
3000 m
Closed, Shock Direction: B1 10 K40
Open, Shock Direction: B1 5 K40
Shock Direction: A 20 K40
Shock Direction: B2 15 K40
Shock Direction: C1 20 K40
Shock Direction: C2 20 K40
Following EU Directive 2011/65/EU
1 piece
78 mm
79 mm
47 mm
0.34 kg
3471522010803
box 63 piece
300 mm
245 mm
308 mm
21.42 kg
1220 piece
K
EC000196 - Contactor relay
EC000196 - Contactor relay
EC000196 - Contactor relay
EC000196 - Contactor relay
39121500
3709215
| Title: | Size: | Type: |
|---|---|---|
| PDF CIRCUIT BREAKERS TMAX XT.pdf | 26 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.