ESR5-NO-21-24VAC-DC 118700 EATON MOELLER Safety relay emergency stop/protective door, 24VDC/AC, 2 enabling p.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ESR5-NO-21-24VAC-DC 118700 EATON MOELLER Safety relay emergency stop/protective door, 24VDC/AC, 2 enabling p..

ESR5-NO-21-24VAC-DC

118700

EATON - MOELLER

Available

Ship on today

Safety relay emergency stop/protective door, 24VDC/AC, 2 enabling paths

More details


Safety

ESR5 safety relays - EATON - MOELLER

ESR5 safety relay - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$125.25
2+$121.92
3+$120.27
4+$119.21
6+$118.26
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme
Product range
  Electronic safety relays
Basic function
  Emergency stop; emergency switching off
Protective door
Feedback circuit
Features
   
Mounting width
 mm22.5
 
  Automatic reset
Operation
  single-channel
dual-channel
Supply voltage
Us 24 V DC
24 V AC, 50/60 Hz
Approval
  
General
Intended use
  Sicherheitsrelais zur Überwachung von Not-Halt- und Schutztürschaltern.
Mit Hilfe dieses Modules werden Stromkreise sicherheitsgerichtet unterbrochen.
Policies List
  EMV 2004/108/EG, Maschinen 2006/42/EG
Standards
  EN ISO 13849-1:2008,
EN 62061:2005+AC:2010,
EN 61508, Parts 1-7:2001,
EN 50178:1997,
EN 60204-1:2006+A1:2009
Dimensions (W x H x D)
  mm22.5 x 114.5 x 99
Mounting width
 mm22.5
Weight
 kg0,22
Mounting position
  As required
Mounting
  Top-hat rail IEC/EN 60715, 35 mm
Connection type
  M3 screw terminals
Lifespan, mechanical
Operationsx 10610
Terminal capacity
   
Solid
 mm21x (0.2 – 2.5)
2x (0.2 – 1)
Flexible with ferrule
 mm21x (0.25 – 2.5)
2x (0.25 – 1)
Solid or stranded
 AWG24 - 12
Terminal screw
 Nm 
Pozidriv screwdriver
 Size2
Standard screwdriver
 mm0.6 x 3.5
Max. tightening torque
 Nm0.6
Stripping length
 mm7
Material
  Housing: polyamide PA not reinforced
Contacts: Material: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
Duty factor
  % DF100
Operating conditions
   
Climatic environmental conditions
   
Climatic proofing
  Cold to EN 60068-2-1
Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Ambient temperature
   
Operation
ϑ°C-20 - +55
Storage
ϑ°C-40 - +70
Condensation
  Non-condensing
Atmospheric conditions
   
relative humidity
 %Max. 75
Air pressure (operation)
 hPa795 - 1080
Altitude
Above sea levelm2000
Power loss
PW5.16
Ambient conditions, mechanical
Degree of protection to VDE 0470-1
   
Enclosures
  IP20
Terminals
  IP20
Degree of Protection
  Installation location: ≥ IP54
B10d [switching cycles]
  300000
Protection against direct contact when actuated from front (EN 50274)
  Finger and back-of-hand proof
Vibrations (IEC/EN 60068-2-6)
  10 - 150 Hz

Amplitude: 0.15 mm

Acceleration: 2 g
Clearance in air and creepage distances
  EN 50178, UL 508, CSA C22.2, No. 14-95
Rated impulse withstand voltage
UimpV AC6000
Insulation
  Safe isolation
Reinforced insulation
Overvoltage category/pollution degree
  III/2
Stop category
according to EN60204-1 5,05
Technical safety parameters:
   
Values according to EN ISO 13849-1
   
Performance level
according to EN ISO 13849 PL e
Category
according to EN ISO 13849 Kat. 4
Safety integrity level claim limit
in accordance with 62061 SILCL 3
Safety integrity level
In accordance with IEC 61508 SIL 3
Probability of failure per hour
PFHdx 10-105.05
Prooftest High Demand
 Months240
Demand level
 Months< 12
Prooftest Low Demand
 Months66
Lifetime
 Months240
Rated operational voltage
UeV AC230
Rated operational voltage
UeV24 V AC, 24 V DC
Permissible range
  0.85 - 1.1 x Ue
Rated insulation voltage
UiV AC250
Quadratic summation current
  A272 A2 (ITH2 = I12 + I22)
Notes
  Observe derating curve
→ Engineering
Inrush current
 Amin - max0.025 - 6
Minimum switching capacity
 W0.4
Control circuit
Power supply circuit
   
AC operated 50/60 Hz
 W3.4
DC operated
 W1.6
Fuse for control circuit supply
   
24 V
  short-circuit proof
Input data
Rated current
 mAS12, S22:30, S34:45
Current consumption
 mAAC: 140
DC: 65
Voltage at input, starting and feedback circuit
 V DCApprox. 24
Max. resistive load of the cable
R
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA0
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW0
Static heat dissipation, non-current-dependent
PvsW5.16
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C55
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Meets the product standard's requirements.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Relays (EG000019) / Device for monitoring of safety-related circuits (EC001449)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Device for monitoring of safety-related circuits ([email protected] [ACO304008])
Model
  Basic device
Suitable for monitoring of position switches
  Yes
Suitable for monitoring of emergency-stop circuits
  Yes
Suitable for monitoring of valves
  No
Suitable for monitoring of optoelectronic protection equipment
  No
Suitable for monitoring of tactile sensors
  No
Suitable for monitoring of magnetic switches
  No
Suitable for monitoring of proximity switches
  No
Type of electric connection
  Screw connection
Rail mounting possible
  Yes
Rated control supply voltage Us at AC 50HZ
 V0 - 26.4
Rated control supply voltage Us at AC 60HZ
 V0 - 0
Rated control supply voltage Us at DC
 V0 - 0
Voltage type for actuating
  AC/DC
With detachable clamps
  Yes
Evaluation inputs
  1-channel
With start input
  Yes
With muting function
  No
With feedback circuit
  Yes
Release-delay
 s0 - 0
Number of outputs, safety related, undelayed, with contact
  2
Number of outputs, safety related, delayed, with contact
  0
Number of outputs, safety related, undelayed, semiconductors
  0
Number of outputs, safety related, delayed, semiconductors
  0
Number of outputs, signalling function, undelayed, with contact
  1
Number of outputs, signalling function, delayed, with contact
  0
Number of outputs, signalling function, undelayed, semiconductors
  0
Number of outputs, signalling function, delayed, semiconductors
  0
Category according to EN 954-1
  4
Type of safety acc. IEC 61496-1
  -
Stop category acc. to IEC 60204
  0
Performance level acc. to EN ISO 13849-1
  Level e
SIL according to IEC 61508
  3
With approval for TÜV
  Yes
With approval for BG BIA
  No
With approval according to UL
  Yes
Width
 mm22.5
Height
 mm99
Depth
 mm114.5
Approvals
Product Standards  IEC/EN see Technical Data; UL 508; CSA-C22.2 No. 14-95; CE marking
UL File No.  E29184
UL Category Control No.  NKCR; NKCR7
CSA File No.  UL report applies to both US and Canada
CSA Class No.  3211-83; 3211-03
North America Certification  UL listed, certified by UL for use in Canada
Degree of Protection  IEC: IP20, UL/CSA Type: -
Characteristics
>PU05907001Z safety manual
Characteristic curves
   
IL05013027Z operator manual for electricians
 
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or