EMR6-AWN170-E-1

184768

EATON-MOELLER

Phase monitoring relays, Multi-functional, 90 - 170 V AC, 50/60 Hz

EMR6-AWN170-E-1

Eaton Moeller® series EMR6 Phase monitoring relays, Multi-functional, 90 - 170 V AC, 50/60 Hz

More details


Relays > Phase monitoring relay

Relay timers (KETR, KEMR, KESR)

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $267.08
Unit price: $267.08

Quantity Price
1+$267.08
2+$241.97
3+$231.75
4+$227.53
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



General specifications

Product Name
Eaton Moeller® series EMR6 Phase monitoring relay
Catalog Number
184768
Model Code
EMR6-AWN170-E-1
EAN
4015081788040
Product Length/Depth
103.7 mm
Product Height
85.6 mm
Product Width
22.5 mm
Product Weight
0.16 kg
Certifications
CCC
IEC
CSA
UL
GL

Features & Functions

Electric connection type
Screw connection
Features
Automatic phase sequence correction (can be disabled)
Imbalance threshold values adjustable 2 - 25 % of mean value of phase voltages
Functions
Over voltage detection
Under voltage detection
Multi-functional
Phase failure detection
Monitoring function
Neutral cable break
Phase sequence (can be deactivated)
Undervoltage
Phase imbalance monitoring
Imbalance
Phase failure
Overvoltage
Phase sequence monitoring
Voltage measurement - min
90 V
Voltage measurement - max
170 V

General

Degree of protection
Terminals: IP20
Enclosure: IP50
Lifespan, mechanical
30,000,000 Operations
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product category
EMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)
4000 V AC
Shock resistance
Class 2
LED indicator
Status indication of Delay time running: Yellow, flashing light
Status indication of Undervoltage: Red LED (F2 on)
Status indication of Undervoltage: F2 red, solid light
Status indication of Open neutral conductor: F1 red, solid light and F2 red, flashing light
Status indication of Phase sequence fault: Red, flashing light (F1 and F2 alternating)
Status indication of energized output relay: Green flashing (R)
Status indication of Imbalance: Red, solid light (F1 and F2)
Status indication of Overvoltage: Red LED (F1 on)
Status indication of Phase failure: F1 red, solid light and F2 red, flashing light
Status indication of Overvoltage: F1 red, solid light
Status indication of Supply voltage: Green LED (R on)
Status indication of Relay energized: Yellow, solid light
Status indication of Supply voltage: Green, solid light
Suitable for
Single-phase networks as well
Type
Phase monitoring relay
Voltage type
AC
Voltage type
AC

Climatic environmental conditions

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30

Electro magnetic compatibility

Air discharge
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulse
According to IEC/EN 61000-4-4, level 3
Electromagnetic compatibility
According to IEC/EN 60947-6-2
Immunity to line-conducted interference
Level 3 (according to IEC/EN 61000-4-6)
Immunity to radiation
Level 3 (according to IEC/EN 61000-4-3)
Surge rating
According to IEC/EN 61000-4-5 Level 4

Terminal capacities

Connection type
Snap fixing, top-hat rail IEC/EN 60715
Terminal capacity
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule
1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid
Screwdriver size
5.5 x 0.8 mm, Terminal screw
Tightening torque
Min. 0.6 Nm, Screw terminals
0.8 Nm, Screw terminals

Timing cycle

Delay time
On-delay/off-delay: none = 0 or adjustable between 0.1 - 30 s
0.2 s, Response delay time
Timing cycle
0.06 %/°C, Time error within temperature range
Adjustable from 0.1 – 30 s, Reset delay/Off-delay time
0.5 % Error within supply voltage (Measuring circuits)
0.5 %, Time error within supply voltage

Power supply

Duty factor
100 %, Power supply
Power consumption
3 VA
Rated control supply voltage (Us) at AC, 50 Hz - min
90 V
Rated control supply voltage (Us) at AC, 50 Hz - max
170 V
Rated control supply voltage (Us) at AC, 60 Hz - min
90 V
Rated control supply voltage (Us) at AC, 60 Hz - max
170 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Supply voltage
90 - 170 V AC, 50/60 Hz
Voltage tolerance
0.85 x Uc
1.1 x Uc

Measuring circuits

Hysteresis
0 - 5 %
Measuring cycle
50 ms
Temperature error
0.06 %/°C, Measuring circuits

Relay output contacts

Number of contacts (change-over contacts)
2
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Lifespan, electrical
100,000 Operation (at 230 V, AC-12, 4 A)
Rated operational current (Ie)
4 A at AC-12, 230 V
3 A at AC-15, 230 V
2 A at DC-13, 24 V
4 A at DC-12, 24 V
Rated operational voltage (Ue) at AC - max
250 V
Short-circuit protection rating
Max. 10 A Fast/gL, Fuse, Relay output contacts
Short-circuit protection rating
Max. 10 A Fast/gL, Fuse, Relay output contacts

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.