ESR5-NO-21-24VAC-DC 118700 0004133316 EATON ELECTRIC Safety relay emergency stop/protective door, 24VDC/AC, .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ESR5-NO-21-24VAC-DC 118700 0004133316 EATON ELECTRIC Safety relay emergency stop/protective door, 24VDC/AC, ..

ESR5-NO-21-24VAC-DC

118700

0004133316

EATON-MOELLER

Safety relay emergency stop/protective door, 24VDC/AC, 2 enabling paths

ESR5-NO-21-24VAC-DC

More details


Relays > Device for monitoring of safety-related circuits

Relay timers (KETR, KEMR, KESR)

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $241.65
Unit price: $241.65

Quantity Price
1+$241.65
2+$237.77
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Often bought together

More info



Safety relay emergency stop/protective door, 24VDC/AC, 2 enabling paths
Safety relay dual-channel, for implementing the basic functions emergency switching off, emergency stop, and protective door, supply voltage 24VDC or 24VAC 50/60Hz, 2 Enable current paths (IEC/EN 60204 Stop category 0), 1 signal current path, busbar tag shroud to EN 50274 with vertical actuation from the front finger- and back-of-hand proof, suitable for cat. 4 according to EN 954-1 / PL e according to EN ISO 13849-1 / SILCL 3 according to IEC 62061 / SIL 3 according to IEC 61508, degree of protection IP20, installation location IP54 minimum, TÜV tested, rated impulse voltage 6 kV / safe isolation, reinforced insulation

Delivery program

Product range
Electronic safety relays
Basic function
Emergency stop; emergency switching off
Protective door
Feedback circuit
Features
Mounting width
22.5 mm
Automatic reset
Operation
single-channel
dual-channel
Supply voltage [Us]
24 V DC
24 V AC, 50/60 Hz
Approval
0000SPC-127
Safety related characteristics
Cat. 4
PL e according to EN ISO 13849-1
SILCL 3 according to IEC 62061
SIL 3 according to IEC 61508
Number of enabling paths to EN 60204-1 Stop functions category
Enable current paths to IEC/EN 60204-1 Stop category 0
2
Signal current paths
1

Technical data

General
Intended use
Safety relay for monitoring emergency stop and protective door switch.
Module used to safely interrupt electrical circuits.
Policies List
EMV 2004/108/EG, Maschinen 2006/42/EG
Standards
EN ISO 13849-1:2008,
EN 62061:2005+AC:2010,
EN 61508, Parts 1-7:2001,
EN 50178:1997,
EN 60204-1:2006+A1:2009
Dimensions (W x H x D)
22.5 x 99 x 114.5 mm
Mounting width
22.5 mm
Weight
0,22 kg
Mounting position
As required
Mounting
Top-hat rail IEC/EN 60715, 35 mm
Connection type
M3 screw terminals
Lifespan, mechanical [Operations]
10 x 106
Terminal capacitySolid
1x (0.2 – 2.5)
2x (0.2 – 1) mm2
Terminal capacityFlexible with ferrule
1x (0.25 – 2.5)
2x (0.25 – 1) mm2
Terminal capacitySolid or stranded
24 - 12 AWG
Terminal screwPozidriv screwdriver
2 Size
Terminal screwStandard screwdriver
0.6 x 3.5 mm
Terminal screwMax. tightening torque
0.6 Nm
Stripping length
7 mm
Material
Housing: polyamide PA not reinforced
Contacts: Material: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
Duty factor
100 % DF
Operating conditionsClimatic environmental conditionsClimatic proofing
Cold to EN 60068-2-1
Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Operating conditionsAmbient temperatureOperation [ϑ]
-20 - +55 °C
Operating conditionsAmbient temperatureStorage [ϑ]
-40 - +70 °C
Operating conditionsAmbient temperatureCondensation
Non-condensing
Operating conditionsAtmospheric conditionsrelative humidity
Max. 75 %
Operating conditionsAtmospheric conditionsAir pressure (operation)
795 - 1080 hPa
Operating conditionsAtmospheric conditionsAltitude [Above sea level]
2000 m
Power loss [P]
5.16 W
Ambient conditions, mechanical
Degree of protection to VDE 0470-1Enclosures
IP20
Degree of protection to VDE 0470-1Terminals
IP20
Degree of protection to VDE 0470-1Degree of Protection
Installation location: ≥ IP54
Degree of protection to VDE 0470-1B10d [switching cycles]
300000
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Vibrations (IEC/EN 60068-2-6)
10 - 150 Hz
Amplitude: 0.15 mm
Acceleration: 2 g
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 14-95
Rated impulse withstand voltage [Uimp]
6000 V AC
Insulation
Safe isolation
Reinforced insulation
Overvoltage category/pollution degree
III/2
Stop category [according to EN60204-1]
5,05
Technical safety parameters:Values according to EN ISO 13849-1Performance level [according to EN ISO 13849-1]
PL e
Technical safety parameters:Values according to EN ISO 13849-1Category [according to EN ISO 13849-1]
Kat. 4
Safety integrity level claim limit [in accordance with 62061]
SILCL 3
Safety integrity level [In accordance with IEC 61508]
SIL 3
Probability of failure per hour [PFHd]
5.05 x 10-10
Prooftest High Demand
240 Months
Demand level
< 12 Months
Prooftest Low Demand
66 Months
Lifetime
240 Months
Rated operational voltage [Ue]
230 V AC
Rated operational voltage [Ue]
24 V AC, 24 V DC V
Permissible range
0.85 - 1.1 x Ue
Rated insulation voltage [Ui]
250 V AC
Quadratic summation current
72 A2(ITH2= I12+ I22) A2
Notes
Observe derating curve
→ Engineering
Inrush current
min - max0.025 - 6 A
Minimum switching capacity
0.4 W
Control circuit
Power supply circuitAC operated 50/60 Hz
3.4 W
Power supply circuitDC operated
1.6 W
Fuse for control circuit supply24 V
short-circuit proof
Input data
Rated current
S12, S22:30, S34:45 mA
Current consumption
AC: 140
DC: 65 mA
Voltage at input, starting and feedback circuit
Approx. 24 V DC
Max. resistive load of the cable [R]
≦ 50 Ω
Short-circuit current
2.3 A
Pick-up time (K1, K2) for UN automatic mode, typical [tA]
100 ms
Pick-up time
at Ue in automatic mode: normally 100 ms
Reset time (K1, K2) for UN, normally [tR]
45 (single-channel)
10 (dual-channel) ms
Recovery time [tW]
Approx. 1000 ms
Simultaneity for inputs 1/2 [tsync]
∞ ms
Maximum permissible total cable resistance (input and starting circuits for UN) [RL]
approx. 50 Ω
Maximum switching frequency
0.5 Hz
Status indication
Green LED
Output data
Contact typeNon-delayed enable current paths
2
Contact typeDelayed signal current path
1
Switching voltage
min – max15 - 250 V AC
15 - 250 V DC
Limiting continuous current
perN/O: 6
N/C: 6 A
Short-circuit protection for output circuits, external
Fuse 6 A gL/gG
Output fuseNEOZED (N/O)
10 gL/gG
Output fuseNEOZED (N/C)
6 gL/gG
Maximum breaking powerResistive load (τ = 0 ms)24 V DC
144 W
Maximum breaking powerResistive load (τ = 0 ms)48 V DC
288 W
Maximum breaking powerResistive load (τ = 0 ms)110 V DC
77 W
Maximum breaking powerResistive load (τ = 0 ms)220 V DC
88 W
Maximum breaking powerResistive load (τ = 0 ms)250 V AC
1500 VA
Maximum breaking powerInductive load (τ = 40 ms)24 V DC
48 W
Maximum breaking powerInductive load (τ = 40 ms)48 V DC
40 W
Maximum breaking powerInductive load (τ = 40 ms)110 V DC
35 W
Maximum breaking powerInductive load (τ = 40 ms)220 V DC
35 W
Switching capacity
In accordance with IEC 60947-5-1
Switching capacityAC-15230 V
4 A bei 360 S/h
3 A bei 3600S/h A
Switching capacityDC-1324 V
4 A bei 360 S/h
2.5 A bei 3600S/h A
Further information (flip catalog)
Electromagnetic compatibility (EMC)
Emitted interference
In accordance with EN 61000-6-4
Interference immunity
In accordance with EN 61000-6-2
EN 662061_x

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
5.16 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-20 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Relays (EG000019) / Device for monitoring of safety-related circuits (EC001449)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Device for monitoring of safety-related circuits ([email protected] [ACO304011])
Model
Basic device
Suitable for monitoring of position switches
Yes
Suitable for monitoring of emergency-stop circuits
Yes
Suitable for monitoring of valves
No
Suitable for monitoring of optoelectronic protection equipment
No
Suitable for monitoring of tactile sensors
No
Suitable for monitoring of magnetic switches
No
Suitable for monitoring of proximity switches
No
Type of electric connection
Screw connection
Rail mounting possible
Yes
Rated control supply voltage Us at AC 50HZ
0 - 26.4 V
Rated control supply voltage Us at AC 60HZ
0 - 0 V
Rated control supply voltage Us at DC
0 - 0 V
Voltage type for actuating
AC/DC
With detachable clamps
Yes
Evaluation inputs
1-channel
With start input
Yes
With muting function
No
With feedback circuit
Yes
Release-delay
0 - 0 s
Number of outputs, safety related, undelayed, with contact
2
Number of outputs, safety related, delayed, with contact
0
Number of outputs, safety related, undelayed, semiconductors
0
Number of outputs, safety related, delayed, semiconductors
0
Number of outputs, signalling function, undelayed, with contact
1
Number of outputs, signalling function, delayed, with contact
0
Number of outputs, signalling function, undelayed, semiconductors
0
Number of outputs, signalling function, delayed, semiconductors
0
Category according to EN 954-1
4
Type of safety acc. IEC 61496-1
None
Stop category acc. IEC 60204
0
Performance level acc. EN ISO 13849-1
Level e
SIL according to IEC 61508
3
With approval for TÜV
Yes
With approval for BG BIA
No
With approval according to UL
Yes
Width
22.5 mm
Height
99 mm
Depth
114.5 mm

Approvals

Product Standards
IEC/EN see Technical Data; UL 508; CSA-C22.2 No. 14-95; CE marking
UL File No.
E29184
UL Category Control No.
NKCR; NKCR7
CSA File No.
UL report applies to both US and Canada
CSA Class No.
3211-83; 3211-03
North America Certification
UL listed, certified by UL for use in Canada
Degree of Protection
IEC: IP20, UL/CSA Type: -

Characteristics

Characteristic curve
2131DIA-1
Derating curve

Dimensions

2131DIM-2

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.