VAL-MS-T1/T2 1000DC-PV/3+V/32 1044183 PHOENIX CONTACT Descarregador de correntes de descargas/supressor de d.. Ver maior
As imagens são só a título ilustrativo. Por favor, consulte a ficha técnica.

VAL-MS-T1/T2 1000DC-PV/3+V/32 1044183 PHOENIX CONTACT Descarregador de correntes de descargas/supressor de d..

VAL-MS-T1/T2 1000DC-PV/3+V/32

1044183

PHOENIX_CONTACT

32

Descarregador de correntes de descargas/supressor de dispositivo de proteção para 2-pos. isolado 1000 V DC tensão de sistemas, para montagem em trilho DIN, 4-pos. elemento base, quatro conectável com temperatura monitorada elementos de protecção, mensagem de status em cada ficha.

Lightning current arrester/surge protective device for 2-pos. isolated 1000 V DC voltage systems, for DIN rail mounting, 4-pos. base element, four pluggable temperature-monitored protective elements, status message at each plug.

Mais detalhes


Aterramento, proteção contra raios e sobretensões > Pára-raios para a técnica energética

Trabtech (TT)

* Produto novo em sua embalagem original com todas as garantias e certificações de PHOENIX_CONTACT

* Este artigo pode estar obsoleto. Se você estiver interessado, insira seu e-mail e informaremos se há unidades disponíveis. Caso não existam mais, um dos nossos técnicos procurará uma alternativa fornecivel com características semelhantes.

Se o nosso preço não é o melhor, peça-nos uma cotação Solicitar uma cotação

Best sellers

Mais informação



Dados comerciais

Chave de encomenda1044183
Quantidade de embalagem32 UNID
Quantidade mínima de encomenda32 UNID
ObservaçãoProduzido sob encomenda (sem devolução)
Página de catálogoPágina 50 (C-4-2019)
GTIN (EAN)4055626620657
Peso por unidade (exclusive embalagem)506,660 g
Número do imposto alfandegário85363030
País de origemDE (Alemanha)

Desenhos



Dimensional drawing

Dimensional drawing

Circuit diagram

Circuit diagram



Voltar para cima

Dimensions

Height89.8 mm
Width71.2 mm
Depth65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch4 Div.
Voltar para cima

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 3000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5-500 Hz/2.5 h/XYZ)
Voltar para cima

General

IEC test classificationPV I / II
PV T1 / T2
EN typeT1 / T2
SPD failure behaviorOCM (Open-circuit mode)
Connection configurationY configuration
Installation locationInterior
AccessibilityAccessible
Installation location of the disconnect deviceInternal
Mode of protection(DC+) - (DC-)
(DC+/DC-) - PE
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6-FR
PBT-FR
Degree of pollution2
Distance between live and grounded parts8 mm
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Surge protection fault messageoptical
Voltar para cima

Additional descriptions

NoteThe device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area.
Voltar para cima

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV1170 V DC
Short-circuit current rating ISCPV2000 A
Continuous operating current ICPV< 20 µA
Rated load current IL80 A
Residual current IPE≤ 40 µA DC
≤ 700 µA AC
Standby power consumption PC≤ 25 mVA
Nominal discharge current (8/20) µs15 kA
Maximum discharge current Imax(8/20) µs40 kA
Impulse discharge current (10/350) µs, charge2.5 As
Impulse discharge current (10/350) µs, specific energy6.25 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp5 kA
Total discharge current Itotal(8/20) µs40 kA
Total discharge current Itotal(10/350) µs10 kA
Response time tA≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)
Voltar para cima

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²
Voltar para cima

Standards and Regulations

Standards/regulationsEN 50539-11 2013
Voltar para cima

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Voltar para cima

Classificações

eCl@ss

eCl@ss 4.027130800
eCl@ss 4.127130800
eCl@ss 5.027130800
eCl@ss 5.127130800
eCl@ss 6.027130800
eCl@ss 7.027130802
eCl@ss 8.027130802
eCl@ss 9.027130802
Voltar para cima

ETIM

ETIM 5.0EC000381
ETIM 6.0EC000381
ETIM 7.0EC000381
Voltar para cima

Datasheet - PDF

Título: Tamanho: Tipo:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Avaliações: (0)

Não há comentários do produto ainda.

Adicionar avaliação
ocultar formulário
Avaliação:
Nome:
Email:
Título:
Opinión:
  Captcha
  Adicionar avaliação

Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.