ANUNCIAR
QUINT4-SYS-PS/1AC/24DC/2.5/SC 2904614 PHOENIX CONTACT Fonte de alimentação central central QUINT POWER, cone.. Ver maior
As imagens são só a título ilustrativo. Por favor, consulte a ficha técnica.

QUINT4-SYS-PS/1AC/24DC/2.5/SC 2904614 PHOENIX CONTACT Fonte de alimentação central central QUINT POWER, cone..

QUINT4-SYS-PS/1AC/24DC/2.5/SC

2904614

PHOENIX_CONTACT

Fonte de alimentação central central QUINT POWER, conexão por parafuso, montagem em trilho DIN, alimentação de dispositivo possível via conectores TBUS DIN rail, tinta protetora, entrada: monofásica, saída: 24 V DC/2,5 A

Fontes de alimentação comutada primária, QUINT POWER, Conexão do parafuso, suporte ferroviário, entrada: 1 fase, saída: 24 V DC / 2.5 A

Primary-switched power supply, QUINT POWER, screw connection, DIN rail mounting, supply of devices possible via the TBUS DIN rail connector, protective coating, input: single-phase, output: 24 V DC/2.5 A

Mais detalhes


Aparelhos elétricos de baixa tensão > Fonte de alimentação CC

Fontes de alimentação

Produto novo em sua embalagem original com todas as garantias e certificações de PHOENIX_CONTACT

Preço total: $373.47
Preço unitário: $373.47
Este preço é por unidade e mostra o valor líquido (excluindo impostos indirectos se aplicável).

Se o nosso preço não é o melhor, peça-nos uma cotação Solicitar uma cotação

Related products

Best sellers

Mais informação



Dados técnicos

Input data
AC operation
Nominal input voltage range100 V AC ... 240 V AC
Input voltage range100 V AC ... 240 V AC -15 % ... +10 %
Electric strength, max.300 V AC 30 s
Typical national grid voltage120 V AC
230 V AC
Voltage type of supply voltageAC/DC
Inrush currenttyp. 10 A (at 25 °C)
Inrush current integral (I2t)typ. 0.1 A2s
Inrush current limitation10 A
Frequency range (fN)50 Hz ... 60 Hz ±10 %
16.7 Hz (acc. to EN 50163)
Mains buffering timetyp. 31 ms (120 V AC)
typ. 31 ms (230 V AC)
Current consumption0.85 A (100 V AC)
0.7 A (120 V AC)
0.39 A (230 V AC)
0.37 A (240 V AC)
Protective circuitTransient surge protection; Varistor
Typical response time500 ms
Input fuse4 A (slow-blow, internal)
Recommended breaker for input protection6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE< 0.25 mA (264 V AC, 60 Hz)
< 0.22 mA
DC operation
Input voltage range110 V DC ... 250 V DC -20 % ... +40 %
Voltage type of supply voltageAC/DC
Current consumption0.75 A (110 V DC)
0.33 A (250 V DC)

Output data
Efficiencytyp. 93 % (120 V AC)
typ. 94 % (230 V AC)
Nominal output voltage24 V DC
Setting range of the output voltage (USet)24 V DC ... 27 V DC (constant capacity)
Nominal output current (IN)2.5 A
Static Boost (IStat.Boost)3.125 A (≤ 40°C)
Dynamic Boost (IDyn.Boost)4 A (≤ 60 °C (on ≤ 5 s/off ≥ 5 s))
Feedback voltage resistance≤ 32 V DC
Protection against overvoltage at the output (OVP)≤ 30 V DC ±2 %
Control deviation< 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple< 40 mVPP(with nominal values)
Short-circuit-proofyes
No-load proofyes
Output power60 W
75 W
96 W
Maximum no-load power dissipation< 1 W (120 V AC)
< 1 W (230 V AC)
Power loss nominal load max.< 5 W (120 V AC)
< 4 W (230 V AC)
Crest factortyp. 1.8 (120 V AC)
typ. 1.84 (230 V AC)
Rise time50 ms (UOut= 10 % ... 90 %)
Signal (configurable)
Digital0 V DC 24 V DC 30 mA
Default24 V DC 30 mA 24 V DC for UOut> 0.9 x USet

Connection data
Input
Connection methodScrew connection
Conductor cross section, rigid min.0.14 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.14
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm
Output
Connection methodScrew connection
Conductor cross section, rigid min.0.14 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.14
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm
Signal
Connection methodScrew connection
Conductor cross section, rigid min.0.14 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.14
Stripping length8 mm
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Signaling
Types of signalingLED
Signal output
POut> PThr(LED lights up yellow, output power > PThr, depending on the rotary selector switch setting)
UOut> 0.9 x USet(LED lights up green)
< 0.9 x USet(LED flashes green)

Electrical properties
Number of phases1.00
Insulation voltage input/output4 kV AC (type test)
3 kV AC (routine test)
Switching frequency90 kHz ... 110 kHz (Auxiliary converter stage)
50 kHz ... 195 kHz (Main converter stage)
60 kHz ... 360 kHz (PFC stage)

Product properties
Product typePower supply
Product familyQUINT POWER
MTBF (IEC 61709, SN 29500)> 2000000 h (25 °C)
> 1161000 h (40 °C)
> 514000 h (60 °C)
Environmental protection directiveRoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection classII
Degree of pollution2
Life expectancy (electrolytic capacitors)
Current2.5 A
Temperature40 °C
Time323000 h
Additional text120 V AC
Life expectancy (electrolytic capacitors)
Current2.5 A
Temperature40 °C
Time346000 h
Additional text230 V AC
Life expectancy (electrolytic capacitors)
Current2.5 A
Temperature25 °C
Time915000 h
Additional text120 V AC
Life expectancy (electrolytic capacitors)
Current2.5 A
Temperature25 °C
Time980000 h
Additional text230 V AC

Dimensions
Width40 mm
Height99 mm
Depth114 mm
Installation dimensions
Installation distance right/left (active)15 mm / 15 mm (POut≥50% )
Installation distance right/left (passive)5 mm / 5 mm (POut≥50% )
Installation distance right/left (active, passive)0 mm / 0 mm (POut≤50 %)
Installation distance top/bottom (active)30 mm / 30 mm (POut≥50% )
Installation distance top/bottom (passive)30 mm / 30 mm (POut≥50% )
Installation distance top/bottom (active, passive)30 mm / 30 mm (POut≤50 %)

Mounting
Mounting typeDIN rail mounting
With protective coatingNo

Material specifications
Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing materialPlastic
Type of housingPolycarbonate
Hood versionPolycarbonate

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude≤ 5000 m (> 2000 m, observe derating)
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)

Standards and regulations
Rail applicationsEN 50121-3-2
EN 50121-4
EN 50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard – Safety extra-low voltageIEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolationIEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory useIEC 61010-1
IEC 61010-2-201 (SELV)
Standard - Safety of transformersEN 61558-2-16
Overvoltage category
EN 61010-1II (≤ 5000 m)
EN 62477-1III (≤ 2000 m)

Approvals
ATEX
IdentificationUL 21 ATEX 2597 X
 II 3 G   Ex ec nC IIC T4 Gc
IECEx
IdentificationIECEx ULD 21.0023X
Ex ec nC IIC T4 Gc
UKEX
IdentificationUL21UKEX2208X
UL
IdentificationUL Listed UL 61010-1
UL
IdentificationUL Listed UL 61010-2-201
UL
IdentificationUL 1310 Class 2 Power Units
UL
IdentificationANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
SIQ
IdentificationCB scheme (IEC 61010-1, IEC 61010-2-201)

EMC data
Interference emissionInterference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise immunityImmunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (power supply)
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
EMC requirements, power plantIEC 61850-3
EN 61000-6-5
Conducted noise emissionEN 55016
EN 61000-6-3 (Class B)
Noise emissionAdditional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Noise emissionEN 55016
EN 61000-6-3 (Class B)
Harmonic currents
Standards/regulationsEN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range0 kHz ... 2 kHz
Flicker
Standards/regulationsEN 61000-3-3
Frequency range0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulationsEN 61000-4-2
Electrostatic discharge
Contact discharge8 kV (Test Level 4)
Discharge in air15 kV (Test Level 4)
CommentsCriterion A
Electromagnetic HF field
Standards/regulationsEN 61000-4-3
Electromagnetic HF field
Frequency range80 MHz ... 1 GHz
Test field strength20 V/m (Test Level X)
Frequency range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A
Fast transients (burst)
Standards/regulationsEN 61000-4-4
Fast transients (burst)
Input4 kV (Test Level 4 - asymmetrical)
Output4 kV (Test Level X - asymmetrical)
Signal4 kV (Test Level X - asymmetrical)
CommentsCriterion A
Surge voltage load (surge)
Standards/regulationsEN 61000-4-5
Input2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
CommentsCriterion A
Conducted interference
Standards/regulationsEN 61000-4-6
Conducted interference
I/O/Sasymmetrical
Frequency range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)
Power frequency magnetic field
Standards/regulationsEN 61000-4-8
Frequency16.67 Hz
50 Hz
60 Hz
Test field strength100 A/m
Additional text60 s
CommentsCriterion A
Frequency50 Hz
60 Hz
Frequency range50 Hz ... 60 Hz
Test field strength1 kA/m
Additional text3 s
Frequency0 Hz
Test field strength300 A/m
Additional textDC, 60 s
Voltage dips
Standards/regulationsEN 61000-4-11
Voltage100 V AC
Frequency60 Hz
Voltage dip70 %
Number of periods0.5 / 1 / 30 periods
Additional textTest Level 2
CommentsCriterion A
Voltage dip40 %
Number of periods5 / 10 / 50 periods
Additional textTest Level 2
CommentsCriterion B
Voltage dip0 %
Number of periods0.5 / 1 / 5 / 50 periods
Additional textTest Level 2
CommentsCriterion B
Pulse-shape magnetic field
Standards/regulationsEN 61000-4-9
Test field strength1000 A/m
CommentsCriterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulationsEN 61000-4-12
Input2 kV (symmetrical)
4 kV (asymmetrical)
CommentsCriterion A
Asymmetrical conducted disturbance variables
Standards/regulationsEN 61000-4-16
Test level 116.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage30 V (10 s)
Test level 216.67 Hz 50 Hz 60 Hz (Test Level 2)
Voltage300 V (1 s)
CommentsCriterion A
Attenuated oscillating wave
Standards/regulationsEN 61000-4-18
Voltage1 kV (symmetrical)
2.5 kV (asymmetrical)
1 kV (symmetrical)
CommentsCriterion A
Criteria
Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Criterion CTemporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

ETIM for 2904614 Componentes industriais para Baixa Tensão (EC002540)
Característica Valor
Tipo de tensão de alimentação (EF002991) AC/DC
1a tensão de saída (EF006792) 24 V
Máx. corrente de saída 1 (EF008284) 4 A
Tensão secundária ajustável (EF007002) Sim
Valor nominal tensão de saída 1 (EF009393) 24 V
Valor nominal corrente de saída 1 (EF009396) 2.5 A
Protegido contra curtos-circuitos (EF007332) Sim
Tensão de alimentação nominal em AC 50 Hz (EF007076) 100 V
Tensão nominal de alimentação em AC 60 Hz (EF007077) 100 V
Tensão de alimentação nominal em DC (EF007078) 110 V
Tensão de saída estabilizada (EF003092) Sim
Potência à saída (EF003034) 60 W
Estabilizado (EF005302) Sim
Acabamento da conexão elétrica (EF003961) Ligação com parafuso
Possível montagem em calha (EF003972) Sim
Possível montagem na parede (EF003973) Não
Versão modular (EF001126) Não
Altura embutida (EF000332) 99 mm
Possibilidade de montagem direta (EF005689) Não
Largura (EF000008) 40 mm
Altura (EF000040) 99 mm
Profundidade (EF000049) 114 mm
Adequado para funções de segurança (EF001597) Sim
SIL de acordo com IEC 61508 (EF009889) Nenhum
Nível de desempenho de acordo com EN ISO 13849-1 (EF007399) Nenhum
Grau de proteção (IP) (EF005474) IP20
Grau de proteção (NEMA) (EF011959) Outro

Datasheet - PDF

Título: Tamanho: Tipo:
PDF CATALOG PHOENIX PROTECTION EN .pdf 27 Mbytes

Avaliações: (0)

Não há comentários do produto ainda.

Adicionar avaliação
ocultar formulário
Avaliação:
Nome:
Email:
Título:
Opinión:
  Captcha
  Adicionar avaliação

Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.