Burst impulse
According to IEC/EN 61000-4-4
2 kV, Supply cable
1 kV, Signal cable
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Rated impulse withstand voltage (Uimp)
Ambient operating temperature - max
Ambient operating temperature - min
Ambient operating temperature (enclosed) - max
Ambient operating temperature (enclosed) - min
Ambient storage temperature - max
Ambient storage temperature - min
Conventional thermal current ith of auxiliary contacts (1-pole, open)
Equipment heat dissipation, current-dependent Pvid
Heat dissipation capacity Pdiss
Heat dissipation per pole, current-dependent Pvid
Number of contacts (change-over contacts)
Number of contacts (normally closed contacts)
Number of contacts (normally open contacts)
Number of measuring circuits
Product category
EMT6 thermistor overload relay for machine protection
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated control supply voltage (Us) at AC, 50 Hz - max
Rated control supply voltage (Us) at AC, 50 Hz - min
Rated control supply voltage (Us) at AC, 60 Hz - max
Rated control supply voltage (Us) at AC, 60 Hz - min
Rated control supply voltage (Us) at DC - max
Rated control supply voltage (Us) at DC - min
Rated operational current (Ie)
3 A at AC-15, 220 V 230 V 240 V (NO)
1 A at AC-15, 380 V 400 V 415 V (NO)
3 A at AC-15, 220 V 230 V 240 V
3 A at AC-14, 380 V 400 V 415 V (NO)
3 A at AC-14, 400 V (NC)
Functions
Test function via separate button
Notifications of mains and faults via LED display
Screwdriver size
1 x 6 mm, Terminal screw, Standard screwdriver
2, Terminal screw, Pozidriv screwdriver
Shock resistance
10 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Contact discharge
6 kV, Electrostatic discharge (ESD)
Short-circuit protection rating
Max. 6 A gG/gL, Fuse, Contacts
Surge rating
2 kV, symmetrical, power pulses (Surge), EMC
4 kV, asymmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
Electromagnetic fields
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Safe isolation
250 V AC, Between the contacts, According to EN 61140
250 V AC, Between the contacts and power supply, According to EN 61140
Rated insulation voltage (Ui)
Rated operational current for specified heat dissipation (In)
Rated operational voltage (Ue) - max
Resistance measuring range - max
Resistance measuring range - min
Static heat dissipation, non-current-dependent Pvs
Temperature measuring range - max
Temperature measuring range - min
Terminal capacity
2 x (0.5 - 1.5) mm², solid
20 - 14 AWG, solid or stranded
2 x (0.5 - 1.5) mm², flexible with ferrule
1 x (0.5 - 2.5) mm², solid
1 x (0.5 - 2.5) mm², flexible with ferrule
Supply voltage at AC, 50 Hz - min
Supply voltage at AC, 50 Hz - max
Supply voltage at AC, 60 Hz - min
Supply voltage at AC, 60 Hz - max
Supply voltage at DC - min
Supply voltage at DC - max
Operating voltage at AC, 50 Hz - min
Operating voltage at AC, 50 Hz - max
Operating voltage at AC, 60 Hz - min
Operating voltage at AC, 60 Hz - max
Operating voltage at DC - min
Operating voltage at DC - max
Voltage type of supply voltage
Voltage type of operating voltage
Connection type (auxiliary circuit)