ANUNCIAR
EU5E-SWD-4D4D 116382 Y7-116382 EATON ELECTRIC SWD Módulo de E / S Ver maior
As imagens são só a título ilustrativo. Por favor, consulte a ficha técnica.

EU5E-SWD-4D4D 116382 Y7-116382 EATON ELECTRIC SWD Módulo de E / S

EU5E-SWD-4D4D

116382

Y7-116382

EATON-MOELLER

SWD - Módulo de E / S

IP20 SWDT Módulo 4 Entradas Digitais + 4 Saídas Digitais 0.5A

Eaton EU5E SWD I/O module, 24 V DC, 4 digital inputs, 4 digital transistor -outputs 0, 0.5A

Módulo SmartWire-DT para conexão de quatro sinais digitais de entrada/saída, ajuste automático de direção, entradas de 24 V DC, saídas de transistor à prova de curto-circuito de 24 V DC / 0,5 A, conexão com terminais de entrada push-in tipo grampo

Mais detalhes


Controladores industriais (PLC) > Módulo de entrada/saída digital de periférico descentralizado de bus de campo

Smartwire Darwin

Produto novo em sua embalagem original com todas as garantias e certificações de EATON-MOELLER

Preço total: $184.08
Preço unitário: $184.08
Este preço é por unidade e mostra o valor líquido (excluindo impostos indirectos se aplicável).

Se o nosso preço não é o melhor, peça-nos uma cotação Solicitar uma cotação

geralmente comprados juntos

Best sellers

Mais informação



General specifications

Product Name
Eaton EU5E I/O module
Catalog Number
116382
EAN
4015081161126
Product Length/Depth
102 mm
Product Height
90 mm
Product Width
35 mm
Product Weight
0.09 kg
Certifications
UL File No.: E29184
IEC/EN 61131-2
UL Category Control No.: NKCR
CSA Class No.: 3211-07
CSA File No.: 2324643
CSA
UL
Model Code
EU5E-SWD-4D4D

Especificações do produto

Type
Digital modules
Features
Fieldbus connection over separate bus coupler possible
Overload proof (with diagnostics)
Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Electric connection type
Flat plug-in connection
Number of inputs (digital)
4
Pollution degree
2
Burst impulse
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3
Connection to SmartWire-DT
Yes
Air pressure
795 - 1080 hPa (operation)
Category (EN 954-1)
None
Explosion safety category for dust
None
Environmental conditions
Condensation: prevent with appropriate measures
Explosion safety category for gas
None
Output current
0.5 A
Mounting method
Wall mounting/direct mounting
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Current consumption
33 mA, SmartWire-DT network
Voltage type
DC
Mounting position
As required
Output
4 Transistor Outputs
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Overvoltage category
II
Safety performance level (EN ISO 13849-1)
None
SIL (IEC 61508)
None
Ambient operating temperature - max
55 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Input current at signal 1
4 mA
Number of HW-interfaces (industrial ethernet)
0
Number of HW-interfaces (other)
0
Number of HW-interfaces (parallel)
0
Number of HW-interfaces (RS-232)
0
Number of HW-interfaces (RS-422)
0
Number of HW-interfaces (RS-485)
0
Number of HW-interfaces (serial TTY)
0
Number of HW-interfaces (USB)
0
Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Surge rating
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
Potential isolation
Outputs to SmartWire-DT: yes
Inputs for SmartWire-DT: yes
Power loss
1.1 W
Electromagnetic fields
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
Protection against polarity reversal
Yes
Yes, for supply voltage (Siemens MPI optional)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Protocol
Other bus systems
Radio interference class
Class A (EN 55011)
Number of outputs (digital)
4
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
Connection type
Plug, 8-pole, SmartWire-DT
Connection plug: external device plug SWD4-8SF2-5, SmartWire-DT
Push in terminals, Supply and I/O sensor
Residual ripple
≤ 5 % (input voltage)
Data transmission type
Other
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
Data transfer rate
Setting automatically
250 kBit/s, SmartWire-DT
Degree of protection
IP20
Station
SmartWire-DT slave, SmartWire-DT network
Input delay
< 0.2 ms
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Short-circuit protection
Outputs are short-circuit proof
Short-circuit tripping current
Max. 1.2 A over 3 ms, Digital semi-conductor outputs
Lamp load
≤ 3 W (at RLL)
Functions
For connection of digital I/O signals
System accessory
Yes
Limit value type 1
High: > 15 V DC
Low: < 5 V DC
Input current
4 mA (at 24 V DC, Digital inputs)
Terminal capacity
0.2 - 1.5 mm² (AWG 24 - 16), solid, Terminal for I/O sensor
0.25 - 1.5 mm² (24 - 16 AWG), flexible with ferrule, Terminal for I/O sensor
LED indicator
Status indication of SmartWire-DT network: Green LED
Status indication of input: Yellow LED
Status indication of display outputs: Yellow LED
Number of HW-interfaces (wireless)
0
Number of interfaces (PROFINET)
0
Operating temperature - max
55 °C
Operating temperature - min
-25 °C
Permitted voltage at input - max
28.8 V
Permitted voltage at input - min
20.4 V
Permitted voltage at output - max
28.8 V
Permitted voltage at output - min
20.4 V
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.1 W
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 60 Hz - max
0 VAC
Supply voltage at AC, 60 Hz - min
0 VAC
Supply voltage at DC - max
28.8 VDC
Supply voltage at DC - min
20.4 VDC
Time delay at signal exchange - max
0 ms
Time delay at signal exchange - min
0 ms
Product category
SmartWire-DT slave
Switching capacity
IEC/EN 60947-5-1, utilization category DC-13, Digital outputs

ETIM for 116382 PLC's (EC001599)
Característica Valor
Supply voltage AC 50 Hz (EF007532) 0 V
Supply voltage AC 60 Hz (EF007533) 0 V
Supply voltage DC (EF007534) 20.4 V
Voltage type (supply voltage) (EF002991) DC
Number of digital inputs (EF001992) 4
Number of digital outputs (EF001993) 4
Digital inputs configurable (EF008516) false
Digital outputs configurable (EF008520) false
Input current at signal 1 (EF001428) 4 mA
Permitted voltage at input (EF007554) 20.4 V
Type of voltage (input voltage) (EF003033) DC
Type of digital output (EF003601) Other
Output current (EF003202) 0.5 A
Permitted voltage at output (EF007553) 20.4 V
Type of output voltage (EF008222) DC
Short-circuit protection, outputs available (EF003203) false
Number of HW-interfaces industrial Ethernet (EF003020) 0
Number of interfaces PROFINET (EF006932) 0
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 0
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces wireless (EF006933) 0
Number of HW-interfaces USB (EF003025) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) false
Supporting protocol for EtherCAT (EF017564) false
Supporting protocol for TCP/IP (EF003050) false
Supporting protocol for PROFIBUS (EF003052) false
Supporting protocol for CAN (EF003053) false
Supporting protocol for INTERBUS (EF003054) false
Supporting protocol for ASI (EF003051) false
Supporting protocol for KNX (EF003055) false
Supporting protocol for Modbus (EF003057) false
Supporting protocol for Data-Highway (EF003058) false
Supporting protocol for DeviceNet (EF003059) false
Supporting protocol for SUCONET (EF003060) false
Supporting protocol for LON (EF003017) false
Supporting protocol for PROFINET IO (EF007525) false
Supporting protocol for PROFINET CBA (EF007524) false
Supporting protocol for SERCOS (EF006657) false
Supporting protocol for Foundation Fieldbus (EF007522) false
Supporting protocol for EtherNet/IP (EF007521) false
Supporting protocol for AS-Interface Safety at Work (EF007519) false
Supporting protocol for DeviceNet Safety (EF007520) false
Supporting protocol for INTERBUS-Safety (EF006662) false
Supporting protocol for PROFIsafe (EF007526) false
Supporting protocol for SafetyBUS p (EF007527) false
Supporting protocol for other bus systems (EF003062) true
Radio standard Bluetooth (EF007178) false
Radio standard WLAN 802.11 (EF007179) false
Radio standard GPRS (EF008523) false
Radio standard GSM (EF008524) false
Radio standard UMTS (EF008525) false
IO link master (EF007298) false
System accessory (EF004118) true
Degree of protection (IP) (EF005474) IP20
Type of electric connection (EF003961) Flat plug-in connection
Time delay at signal change (EF002382) 0 ms
Fieldbus connection over separate bus coupler possible (EF004002) true
Suitable for rail mounting (EF003972) true
Wall mounting/direct mounting (EF007020) true
Front built-in possible (EF007016) false
Rack-assembly possible (EF007018) false
Suitable for safety functions (EF001597) false
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Appendant operation agent (Ex ia) (EF004141) false
Appendant operation agent (Ex ib) (EF004142) false
Explosion safety category for gas (EF003997) None
Explosion safety category for dust (EF003998) None
Certified for UL hazardous location class I (EF017622) false
Certified for UL hazardous location class II (EF017625) false
Certified for UL hazardous location class III (EF017627) false
Certified for UL hazardous location division 1 (EF017628) false
Certified for UL hazardous location division 2 (EF017629) false
Certified for UL hazardous location group A (acetylene) (EF017632) false
Certified for UL hazardous location group B (hydrogen) (EF017633) false
Certified for UL hazardous location group C (ethylene) (EF017635) false
Certified for UL hazardous location group D (propane) (EF017636) false
Certified for UL hazardous location group E (metal dusts) (EF017637) false
Certified for UL hazardous location group F (carbonaceous dusts) (EF017638) false
Certified for UL hazardous location group G (non-conductive dusts) (EF017639) false
Width (EF000008) 35 mm
Height (EF000040) 90 mm
Depth (EF000049) 102 mm

Datasheet - PDF

Avaliações: (0)

Não há comentários do produto ainda.

Adicionar avaliação
ocultar formulário
Avaliação:
Nome:
Email:
Título:
Opinión:
  Captcha
  Adicionar avaliação

Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.