Product Category
Variable frequency drives
Features
Parameterization: Keypad
Parameterization: Power Xpert inControl
Temperature-controlled fan
Parameterization: Fieldbus
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Fitted with:
IGBT inverter
Setpoint potentiometer
7-digital display assembly
Radio interference suppression filter
Brake chopper
Internal DC link
Breaking resistance
Control unit
PC connection
Climatic proofing
< 95 average relative humidity (RH), no condensation, no corrosion
Connection to SmartWire-DT
Yes
In conjunction with DXG-NET-SWD SmartWire DT module
Operating mode
U/f control
Speed control with slip compensation
Torque regulation
Sensorless vector control (SLV)
PM motors
Altitude
Max. 3000 m
Max. 2000 m for Corner Grounded TN Systems
Max. 1000 m
Above 1000 m with 1 % derating per 100 m
Application in domestic and commercial area permitted
Mains switch-on frequency
Maximum of one time every 60 seconds
Application in industrial area permitted
Ambient operating temperature - max
Ambient operating temperature - min
Ambient storage temperature - max
Ambient storage temperature - min
Assigned motor current IM at 400 V, 50 Hz, 110% overload
Assigned motor current IM at 400 V, 50 Hz, 150% overload
Rated conditional short-circuit current (Iq)
Relative symmetric net frequency tolerance
Relative symmetric net voltage tolerance
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload
Resolution
0.01 Hz (Frequency resolution, setpoint value)
Switch-on threshold for the braking transistor
Communication interface
Ethernet IP, built in
BACnet TCP
Modbus RTU, built in
SmartWire-DT, optional
Modbus TCP, built in
DeviceNet, optional
BACnet MS/TP, built in
CANopen®, optional
PROFIBUS, optional
Protocol
BACnet
CAN
EtherNet/IP
MODBUS
Other bus systems
PROFIBUS
TCP/IP
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload
Assigned motor current IM at 500 V, 50 Hz, 110% overload
Assigned motor current IM at 500 V, 50 Hz, 150% overload
System configuration type
TN-S, TN-C, TN-C-S, TT, IT
Electromagnetic compatibility
1st and 2nd environments (according to EN 61800-3)
Assigned motor power at 460/480 V, 60 Hz
Assigned motor power at 460/480 V, 60 Hz, 110% overload
Equipment heat dissipation, current-dependent Pvid
Input current ILN at 110% overload
Input current ILN at 150% overload
Current limitation
0.1 - 2 x IH (CT), motor, main circuit
Braking torque
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 150 %, DC - Main circuit
Cable length
C2 ≤ 5 m, maximum motor cable length
C3 ≤ 25 m, maximum motor cable length
Functions
4-quadrant operation possible
Output voltage (U2)
500 V AC, 3-phase
400 V AC, 3-phase
480 V AC, 3-phase
Number of inputs (analog)
Number of inputs (digital)
Radio interference class
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C1: with external filter, for conducted emissions only
Number of outputs (digital)
Starting current - max
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
Number of relay outputs
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
Number of phases (output)
Rated control supply voltage
Rated control voltage (Uc)
24 V DC (external, max. 100 mA options incl.)
Nominal output current I2N
Number of HW-interfaces (industrial ethernet)
Number of HW-interfaces (other)
Number of HW-interfaces (parallel)
Number of HW-interfaces (RS-232)
Number of HW-interfaces (RS-422)
Number of HW-interfaces (RS-485)
Number of HW-interfaces (serial TTY)
Number of HW-interfaces (USB)
Number of interfaces (PROFINET)
Number of outputs (analog)
Output at linear load at rated output voltage - max
Output at quadratic load at rated output voltage - max
Overload current IL at 110% overload
Overload current IL at 150% overload
Shock resistance
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
Suitable for
Branch circuits, (UL/CSA)
Switching frequency
4 kHz, 1 - 16 kHz adjustable, fPWM, Power section, Main circuit
Rated operational voltage
500 V AC, 3-phase
480 V AC, 3-phase
400 V AC, 3-phase
Short-circuit protection rating
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
Rated operational current (Ie) at 110% overload
Rated operational current (Ie) at 150% overload
Rated operational current for specified heat dissipation (In)
Rated operational power at 380/400 V, 50 Hz, 110% overload
Rated operational power at 380/400 V, 50 Hz, 3-phase
Rated operational power at 500 V, 50 Hz, 3-phase
Safety function/level
STO (Safe Torque Off, SIL2, PLc Cat 2)
Heat dissipation at current/speed
48 W at 25% current and 0% speed
51 W at 25% current and 50% speed
55 W at 50% current and 50% speed
56 W at 100% current and 50% speed
57 W at 50% current and 90% speed
70 W at 100% current and 0% speed
71 W at 50% current and 0% speed
80 W at 100% current and 90% speed