10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Fitted with:
Internal DC link
PC connection
7-digital display assembly
IGBT inverter
Control unit
Additional PCB protection
Climatic proofing
< 95 average relative humidity (RH), no condensation, no corrosion
Connection to SmartWire-DT
Yes
In conjunction with DX-NET-SWD3 SmartWire DT module
Operating mode
Sensorless vector control (SLV)
U/f control
Speed control with slip compensation
BLDC motors
PM motors
Synchronous reluctance motors
Rated impulse withstand voltage (Uimp)
Altitude
Above 1000 m with 1 % derating per 100 m
Max. 4000 m
Application in domestic and commercial area permitted
Mains switch-on frequency
Maximum of one time every 30 seconds
Ambient operating temperature - max
Ambient operating temperature - min
Relative symmetric net frequency tolerance
Relative symmetric net voltage tolerance
Ambient operating temperature at 150% overload - max
Ambient operating temperature at 150% overload - min
Ambient storage temperature - max
Ambient storage temperature - min
Assigned motor current IM at 110/120 V, 60 Hz, 150% overload
Assigned motor current IM at 115 V, 50 Hz, 150% overload
Application in industrial area permitted
Product category
Variable frequency drives
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Resolution
0.1 Hz (Frequency resolution, setpoint value)
Static heat dissipation, non-current-dependent Pvs
Communication interface
OP-Bus (RS485), built in
Modbus RTU, built in
SmartWire-DT, optional
CANopen®, built in
Assigned motor power at 115/120 V, 60 Hz, 1-phase
Assigned motor power at 230/240 V, 60 Hz, 1-phase
Assigned motor power at 460/480 V, 60 Hz
Assigned motor power at 460/480 V, 60 Hz, 3-phase
Equipment heat dissipation, current-dependent Pvid
Heat dissipation capacity Pdiss
Heat dissipation per pole, current-dependent Pvid
Input current ILN at 150% overload
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload
Assigned motor current IM at 230 V, 50 Hz, 150% overload
Protocol
Other bus systems
EtherNet/IP
MODBUS
CAN
Overload current IL at 150% overload
Rated operational current for specified heat dissipation (In)
Rated operational power at 220/230 V, 50 Hz, 1-phase
Assigned motor current IM at 400 V, 50 Hz, 150% overload
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload
System configuration type
AC supply systems with earthed center point
Braking current
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
Braking torque
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 30 % MN, Standard - Main circuit
Cable length
150 m, unscreened, with motor choke, maximum permissible, Motor feeder
100 m, screened, with motor choke, maximum permissible, Motor feeder
50 m, screened, maximum permissible, Motor feeder
75 m, unscreened, maximum permissible, Motor feeder
Output voltage (U2)
240 V AC, 3-phase
230 V AC, 3-phase
Delay time
< 10 ms, On-delay
< 10 ms, Off-delay
Number of inputs (analog)
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
Number of inputs (digital)
4 (parameterizable, 10 - 30 V DC)
Radio interference class
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
Number of outputs (digital)
Starting current - max
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
Number of relay outputs
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
Number of phases (output)
Rated control supply voltage
Leakage current at ground IPE - max
Nominal output current I2N
Number of HW-interfaces (industrial ethernet)
Number of HW-interfaces (other)
Number of HW-interfaces (parallel)
Number of HW-interfaces (RS-232)
Number of HW-interfaces (RS-422)
Number of HW-interfaces (RS-485)
Number of HW-interfaces (serial TTY)
Number of HW-interfaces (USB)
Number of interfaces (PROFINET)
Number of outputs (analog)
Output at linear load at rated output voltage - max
Output at quadratic load at rated output voltage - max
Short-circuit protection (external output circuits)
Type 1 coordination via the power bus' feeder unit, Main circuit
Suitable for
Branch circuits, (UL/CSA)
Switching frequency
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
Rated operational current (Ie)
2.3 A at 150% overload (at an operating frequency of 16 kHz and an ambient air temperature of +50 °C)
Rated operational voltage
230 V AC, 3-phase
240 V AC, 3-phase
Short-circuit protection rating
6 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
Heat dissipation at current/speed
16 W at 25% current and 0% speed
16 W at 25% current and 50% speed
16 W at 50% current and 0% speed
17 W at 50% current and 50% speed
18 W at 100% current and 0% speed
18 W at 50% current and 90% speed
20 W at 100% current and 50% speed
22 W at 100% current and 90% speed