Type
Front mounting auxiliary contact
Features
Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L)
Fitted with:
Interlocked opposing contacts
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Ambient operating temperature - max
Ambient operating temperature - min
Ambient operating temperature (enclosed) - max
Ambient operating temperature (enclosed) - min
Ambient storage temperature - max
Ambient storage temperature - min
Conventional thermal current ith at 60°C (3-pole, open)
Conventional thermal current ith of auxiliary contacts (1-pole, open)
Number of contacts (change-over contacts)
Number of contacts (normally closed contacts)
Number of contacts (normally open contacts)
Number of switches (fault signal)
Rated impulse withstand voltage (Uimp)
Control circuit reliability
λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
Functions
For standard applications
Safe isolation
400 V AC, Between coil and auxiliary contacts, According to EN 61140
400 V AC, Between auxiliary contacts, According to EN 61140
Rated operational current (Ie)
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series)
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
Lifespan, electrical
1,300,000 Operations (at 230 V, AC-15, 3 A)
Switching capacity (auxiliary contacts, general use)
10 A, 600 V AC, (UL/CSA)
1 A, 250 V DC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA)
Lifespan, mechanical
10,000,000 Operations (DC operated)
10,000,000 Operations (AC operated)
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Short-circuit protection rating without welding
10 A gG/gL, 500 V, Max. Fuse, Contacts
Rated insulation voltage (Ui)
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V
Rated operational current (Ie) at AC-15, 500 V
Rated operational current (Ie) at DC-13, 110 V
Rated operational current (Ie) at DC-13, 220 V, 230 V
Rated operational current (Ie) at DC-13, 24 V
Rated operational current (Ie) at DC-13, 60 V
Rated operational voltage (Ue) at AC - max
Terminal capacity (flexible with ferrule)
1 x (0.5 - 1.5) mm²
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm², Push-in terminals, ferrule to DIN 46228-1
1 x (0.5 - 1.5) mm², Push-in terminals, ferrule to DIN 46228-4
Terminal capacity (solid)
1 x (0.5 - 0.25) mm²
2 x (0.5 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)
Terminal capacity (flexible)
1 x (0.5 - 2.5) mm²
2 x (0.5 - 2.5) mm²
Shock resistance
5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
7 g, N/O auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms