6ES7677-2AA41-0FL0

SIEMENS

SIMATIC ET 200SP Open Controllers, CPU 1515SP PC. +HMI 512PT, 4 GB RAM, 30 GB CFAST with WES 7 P 64 bit pre-installed, with S7-1500 software controller CPU 1505SP F pre-installed, with WinCC Runtime Advanced V14 pre-installed with 512 PowerTags license, Interfaces: 1x slot CFAST, 1x slot SD/MMC, 1x connection for ET 200SP bus adapter PROFINET 1x 10/100/1000 Mbit/s Ethernet, 3x USB, 1x DVI-I graphics card connection, Documentation on DVD, Restore DVD

More details


AUTOMATION SYSTEMS > SIMATIC S7-1500 / F Safety / RH Redundant / Open Controller / Software Controller (without I / O)

Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



ETIM: EC001603 - Fieldbus, decentr. periphery - basic appliance

Value Unit
Category according to EN 954-1 (EF006782) -
With potential separation (EF003272) -
Supporting protocol for TCP/IP (EF003050) -
SIL according to IEC 61508 (EF009889) -
Type of electric connection (EF003961) -
Max. input current DC (EF007362) -A
Number of slots (EF003077) -
Performance level according to EN ISO 13849-1 (EF007399) -
With integrated power supply (EF003338) true
Input voltage at AC 50 Hz (EF007118) ['-', '-']V
Input voltage at AC 60 Hz (EF007119) ['-', '-']V
Input voltage at DC (EF007120) ['19.2', '28.8']V
Type of voltage (input voltage) (EF003033) DC
Max. input current AC 50 Hz (EF007360) -A
Max. input current AC 60 Hz (EF007361) -A
Output voltage at AC 50 Hz (EF006999) ['-', '-']V
Output voltage at AC 60 Hz (EF007000) ['-', '-']V
Output voltage at DC (EF007001) ['-', '-']V
Type of output voltage (EF008222) -
Max. output current AC 50 Hz (EF007351) -A
Max. output current AC 60 Hz (EF007352) -A
Max. output current DC (EF007353) -A
Number of HW-interfaces industrial Ethernet (EF003020) 2
Number of interfaces PROFINET (EF006932) 1
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) 1
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces USB (EF003025) 3
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces Wireless (EF006933) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) -
Supporting protocol for PROFIBUS (EF003052) true
Supporting protocol for CAN (EF003053) false
Supporting protocol for INTERBUS (EF003054) false
Supporting protocol for ASI (EF003051) false
Supporting protocol for KNX (EF003055) false
Supporting protocol for Modbus (EF003057) true
Supporting protocol for Data-Highway (EF003058) false
Supporting protocol for DeviceNet (EF003059) false
Supporting protocol for SUCONET (EF003060) false
Supporting protocol for LON (EF003017) false
Supporting protocol for SERCOS (EF006657) false
Supporting protocol for PROFINET IO (EF007525) true
Supporting protocol for PROFINET CBA (EF007524) false
Supporting protocol for Foundation Fieldbus (EF007522) false
Supporting protocol for EtherNet/IP (EF007521) false
Supporting protocol for AS-Interface Safety at Work (EF007519) false
Supporting protocol for DeviceNet Safety (EF007520) false
Supporting protocol for INTERBUS-Safety (EF006662) false
Supporting protocol for PROFIsafe (EF007526) false
Supporting protocol for SafetyBUS p (EF007527) false
Supporting protocol for other bus systems (EF003062) false
Radio standard Bluetooth (EF007178) false
Radio standard WLAN 802.11 (EF007179) false
Radio standard GPRS (EF008523) false
Radio standard GSM (EF008524) false
Radio standard UMTS (EF008525) false
IO link master (EF007298) false
System accessory (EF004118) true
Degree of protection (IP) (EF005474) IP20
With pluggable modules, digital I/O (EF003078) true
With pluggable modules, analogue I/O (EF003079) true
With pluggable modules, communication modules (EF003080) true
With pluggable modules, function and technology modules (EF003081) true
With pluggable modules, central modules (EF003082) true
With pluggable modules, others (EF003083) true
Fieldbus connection over separate bus coupler possible (EF004002) true
With bus coupler for modular station connection (EF003990) true
Rail mounting possible (EF003972) true
Wall mounting/direct mounting (EF007020) true
Front build in possible (EF007016) -
Rack-assembly possible (EF007018) -
Suitable for safety functions (EF001597) false
Appendant operation agent (Ex ia) (EF004141) false
Appendant operation agent (Ex ib) (EF004142) false
Explosion safety category for gas (EF003997) ATEX gas-ex-protection, Cat. 3G
Explosion safety category for dust (EF003998) None
Width (EF000008) 160.0mm
Height (EF000040) 117.0mm
Depth (EF000049) 75.0mm


SIMATIC ET 200SP Open Controllers, CPU 1515SP PC. +HMI 512PT, 4 GB RAM, 30 GB CFAST with WES 7 P 64 bit pre-installed, with S7-1500 software controller CPU 1505SP F pre-installed, with WinCC Runtime Advanced V14 pre-installed with 512 PowerTags license, Interfaces: 1x slot CFAST, 1x slot SD/MMC, 1x connection for ET 200SP bus adapter PROFINET 1x 10/100/1000 Mbit/s Ethernet, 3x USB, 1x DVI-I graphics card connection, Documentation on DVD, Restore DVD
General information
Product type designationCPU 1515SP PC
HW functional statusFS05
Firmware versionV2.1
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionV14 SP1
Installed software
● VisualizationWinCC Runtime Advanced V14 SP1
● ControlS7-1500 Software Controller CPU 1505SP V2.1
Configuration control
via datasetYes
Control elements
Mode selector switch1
Supply voltage
Type of supply voltage24 V DC
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Mains buffering
● Mains/voltage failure stored energy time5 ms
Input current
Current consumption (rated value)1.5 A; Full processor load, incl. ET 200SP modules and using USB
Current consumption (in no-load operation), typ.0.6 A
Inrush current, max.4.7 A; Rated value
Power
Active power input, max.36 W; incl. ET 200SP modules and using USB
Infeed power to the backplane bus8.75 W
Power loss
Power loss, typ.15 W; without ET 200SP modules and without using USB
Processor
Processor typeDual-Core 1 GHz, AMD G Series APU T40E
Memory
Type of memoryDDR3-SDRAM
Main memory4 GB RAM
CFast memory cardYes; 30 GB flash memory
SIMATIC memory card requiredNo
Work memory
● integrated (for program)1 Mbyte
● integrated (for data)5 Mbyte
● integrated (for CPU function library of CPU Runtime)10 Mbyte
Load memory
● integrated (on PC mass storage)320 Mbyte
Backup
● with UPSYes; all memory areas declared retentive
● with non-volatile memoryYes
CPU processing times
for bit operations, typ.10 ns
for word operations, typ.12 ns
for fixed point arithmetic, typ.16 ns
for floating point arithmetic, typ.64 ns
CPU-blocks
Number of elements (total)6 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements
DB
● Number, max.5 999; Number range: 1 to 65535
● Size, max.5 Mbyte
FB
● Number, max.5 998; Number range: 1 to 65535
● Size, max.512 kbyte
FC
● Number, max.5 999; Number range: 1 to 65535
● Size, max.512 kbyte
OB
● Size, max.1 048 kbyte
● Number of free cycle OBs100
● Number of time alarm OBs20
● Number of delay alarm OBs20
● Number of cyclic interrupt OBs20
● Number of process alarm OBs50
● Number of DPV1 alarm OBs3
● Number of isochronous mode OBs1
● Number of technology synchronous alarm OBs2
● Number of startup OBs100
● Number of asynchronous error OBs4
● Number of synchronous error OBs2
● Number of diagnostic alarm OBs1
Nesting depth
● per priority class24
Counters, timers and their retentivity
S7 counter
● Number2 048
Retentivity
— adjustableYes
IEC counter
● NumberAny (only limited by the main memory)
Retentivity
— adjustableYes
S7 times
● Number2 048
Retentivity
— adjustableYes
IEC timer
● NumberAny (only limited by the main memory)
Retentivity
— adjustableYes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.410 kbyte; For storage in NVRAM; for storage in mass storage 5 242 020 bytes
Flag
● Number, max.16 kbyte
● Number of clock memories8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
● Retentivity adjustableYes
● Retentivity presetNo
Local data
● per priority class, max.64 kbyte; max. 16 KB per block
Address area
Number of IO modules8 192
I/O address area
● Inputs32 kbyte; All inputs are in the process image
● Outputs32 kbyte; All outputs are in the process image
of which per assigned PC interface
— Inputs (volume)8 kbyte
— Outputs (volume)8 kbyte
Subprocess images
● Number of subprocess images, max.32
Hardware configuration
Integrated power supplyYes
Number of distributed IO systems20
Number of DP masters
● Via CM1
Rack
● Modules per rack, max.64; CPU 1515SP PC + 64 modules + server module
● Number of lines, max.1
PtP CM
● Number of PtP CMsthe number of connectable PtP CMs is only limited by the number of available slots
Time of day
Clock
● TypeHardware clock
● Hardware clock (real-time)Yes; Resolution: 1 s
● Backup time6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max.10 s; Typ.: 2 s
Clock synchronization
● supportedYes
● to DP, masterNo
● on Ethernet via NTPYes
● on Windows clock, slaveYes
Interfaces
Number of industrial Ethernet interfaces2
Number of PROFINET interfaces1
Number of PROFIBUS interfaces1
Number of RS 485 interfaces1; Via CM DP module
Number of USB interfaces3; 3x USB 2.0 on the front, 500 mA each - of which 2x 500 mA and 1x 100 mA simultaneously
Number of SD card slots1
Video interfaces
● Graphics interface1x DVI-I
1. Interface
Interface typePROFINET
automatic detection of transmission rateYes
AutonegotiationYes
AutocrossingYes
Number of connections88
Interface types
● Number of ports2
● integrated switchYes
● RJ 45 (Ethernet)Yes; Via BusAdapter BA 2x RJ45
— Transmission rate, max.100 Mbit/s
— Industrial Ethernet status LEDYes
● BusAdapter (PROFINET)Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC
Protocols
● PROFINET IO ControllerYes
● PROFINET IO DeviceYes
● SIMATIC communicationYes
● Open IE communicationYes
● Web serverYes
PROFINET IO Controller
Services
— Isochronous modeYes
— shortest clock pulse500 µs
— IRTYes
— MRPYes
— MRPDYes
— Prioritized startupYes; Max. 32 PROFINET devices
— Number of connectable IO Devices, max.128
— Of which IO devices with IRT, max.64
— of which in line, max.64
— Number of connectable IO Devices for RT, max.128
— of which in line, max.128
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— IO Devices changing during operation (partner ports), supportedYes
— Number of IO Devices per tool, max.8
— Updating timesThe minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data
Update time for IRT
— for send cycle of 500 µs500 µs to 8 ms
— for send cycle of 1 ms1 ms to 16 ms
— for send cycle of 2 ms2 ms to 32 ms
— for send cycle of 4 ms4 ms to 64 ms
— With IRT and parameterization of "odd" send cyclesUpdate time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs)
Update time for RT
— for send cycle of 500 µs500 µs to 256 ms
— for send cycle of 1 ms1 ms to 512 ms
— for send cycle of 2 ms2 ms to 512 ms
— for send cycle of 4 ms4 ms to 512 ms
PROFINET IO Device
Services
— Isochronous modeNo
— IRTYes
— MRPYes
— MRPDYes
— Prioritized startupYes
— Shared deviceYes
— Number of IO Controllers with shared device, max.4
2. Interface
Interface typeIntegrated Ethernet interface
automatic detection of transmission rateYes
AutonegotiationYes
AutocrossingYes
Interface types
● Number of ports1
● RJ 45 (Ethernet)Yes; Integrated
— Transmission rate, max.1 000 Mbit/s
— Industrial Ethernet status LEDNo
3. Interface
Interface typePROFIBUS with CM DP
Number of connections via this interface44
Interface types
● RS 485Yes
Protocols
● PROFIBUS DP masterYes
● PROFIBUS DP slaveYes
● SIMATIC communicationYes
PROFIBUS DP master
● Number of DP slaves, max.125
Services
— EquidistanceNo
— Isochronous modeNo
Interface types
RS 485
● Transmission rate, max.12 Mbit/s
Protocols
Number of connections
● Number of connections, max.88
● Number of connections reserved for ES/HMI/web10
● Number of S7 routing paths16
Redundancy mode
Media redundancy
— Switchover time on line break, typ.200 ms
— Number of stations in the ring, max.50
SIMATIC communication
● PG/OP communicationYes
● S7 routingYes
● S7 communication, as serverYes
● S7 communication, as clientYes
● User data per job, max.64 kbyte
Open IE communication
● TCP/IPYes
— Data length, max.64 kbyte
● ISO-on-TCP (RFC1006)Yes
— Data length, max.64 kbyte
● UDPYes
— Data length, max.1 472 kbyte
● SNMPYes
● DCPYes
● LLDPYes
Web server
● HTTPYes; Via Windows and PROFINET interface
● HTTPSYes; Only via PROFINET interface
OPC UA
● OPC UA ServerYes; Data access (read, write, subscribe), runtime license required
— Application authenticationYes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
— Security policiesYes; Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256
— User authenticationYes; "anonymous" or by user name & password
Further protocols
● MODBUSYes; MODBUS TCP
S7 message functions
Number of login stations for message functions, max.32
Program alarmsYes
Number of configurable program messages, max.10 000
Number of simultaneously active program alarms
● Number of program alarms1 000
● Number of alarms for system diagnostics200
● Number of alarms for motion technology objects160
Test commissioning functions
Joint commission (Team Engineering)Yes; Parallel online access possible for up to 8 engineering systems
Status blockYes; up to 8 simultaneously
Single stepNo
Status/control
● Status/control variableYes
● VariablesInputs, outputs, memory bits, DB, times, counters
● Number of variables, max.
— of which status variables, max.200
— of which control variables, max.200
Forcing
● ForcingYes
● Forcing, variablesInputs, outputs
● Number of variables, max.200
Diagnostic buffer
● presentYes
● Number of entries, max.1 000
— of which powerfail-proof300
Traces
● Number of configurable Traces4
● Memory size per trace, max.512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LEDYes
● ERROR LEDYes
● MAINT LEDYes
Supported technology objects
Motion ControlYes
● Number of available Motion Control resources for technology objects2 400
● Required Motion Control resources
— per speed-controlled axis40; per axis
— per positioning axis80; per axis
— per synchronous axis160; per axis
— per external encoder80; per external encoder
— per output cam20; per cam
— per cam track160; per cam track
— per probe40; per probe
● Positioning axis
— Number of positioning axes at motion control cycle of 4 ms (typical value)5
— Number of positioning axes at motion control cycle of 8 ms (typical value)12
Controller
● PID_CompactYes; Universal PID controller with integrated optimization
● PID_3StepYes; PID controller with integrated optimization for valves
● PID-TempYes; PID controller with integrated optimization for temperature
Counting and measuring
● High-speed counterYes
Standards, approvals, certificates
CE markYes
CSA approvalYes
cULusYes
FM approvalYes
RCM (formerly C-TICK)Yes
Ambient conditions
Ambient temperature during operation
● min.0 °C
● max.Up to 60 °C with max. 32 ET 200SP modules and 3x 100 mA USB load; up to 55 °C with max. 64 ET 200SP modules and 2x max. 500 mA and 1x max. 100 mA USB load
● horizontal installation, min.0 °C
● horizontal installation, max.60 °C
● vertical installation, min.0 °C
● vertical installation, max.50 °C; With max. 32 ET 200SP modules and 3x 100 mA USB load
Ambient temperature during storage/transportation
● min.-40 °C
● max.70 °C
Vibrations
● Operation, tested according to IEC 60068-2-6Yes
● Transport, tested acc. to IEC 60068-2-6Yes
Shock testing
● tested according to IEC 60068-2-6Yes
● tested according to IEC 60068-2-27Yes
● tested according to IEC 60068-2-29Yes
● Storage/transport, tested acc. to IEC 60068-2-27Yes
Operating systems
pre-installed operating systemWindows Embedded Standard 7 P 64-bit
Configuration
Programming
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCNo
— GRAPHYes
Know-how protection
● User program protection/password protectionYes
● Copy protectionYes
● Block protectionYes
Access protection
● Protection level: Write protectionYes
● Protection level: Read/write protectionYes
● Protection level: Complete protectionYes
Cycle time monitoring
● lower limitadjustable minimum cycle time
● upper limitadjustable maximum cycle time
Open Development interfaces
● Size of ODK SO file, max.3.8 Mbyte
Peripherals/Options
SD cardOptionally for additional mass storage
Dimensions
Width160 mm
Height117 mm
Depth75 mm
Weights
Weight, approx.0.83 kg
last modified:08/24/2020


Product
Article Number (Market Facing Number)6ES7677-2AA41-0FL0
Product DescriptionSIMATIC ET 200SP Open Controllers, CPU 1515SP PC. +HMI 512PT, 4 GB RAM, 30 GB CFAST with WES 7 P 64 bit pre-installed, with S7-1500 software controller CPU 1505SP F pre-installed, with WinCC Runtime Advanced V14 pre-installed with 512 PowerTags license, Interfaces: 1x slot CFAST, 1x slot SD/MMC, 1x connection for ET 200SP bus adapter PROFINET 1x 10/100/1000 Mbit/s Ethernet, 3x USB, 1x DVI-I graphics card connection, Documentation on DVD, Restore DVD
Product familyCPU 1515SP PC
Product Lifecycle (PLM)PM300:Active Product
PLM Effective DateProduct phase-out since: 01.10.2020
Price data
Price Group215
Surcharge for Raw MaterialsNone
Metal FactorNone
Delivery information
Export Control RegulationsAL : N / ECCN : 5A992
Standard lead time ex-works5 Day/Days
Net Weight (kg)1,078 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension14,20 x 18,90 x 9,20
Package size unit of measureCM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4047623405054
UPC804766001666
Commodity Code85371091
LKZ_FDB/ CatalogIDSTWINAC
Product Group4A62
Group CodeR111
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 05.02.2015
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

4,4'-isopropylidenediphenol (Bisphenol A, BPA)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-24-26-07
eClass7.127-24-26-07
eClass827-24-26-07
eClass927-24-26-07
eClass9.127-24-26-07
ETIM5EC001603
ETIM6EC001603
ETIM7EC001603
IDEA43565
UNSPSC1443-21-15-12
UNSPSC1532-15-17-05

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.