6AG1153-1AA03-2XB0 SIEMENS SIPLUS DP ET200M IM153-1 -40...+70°C start up Temp -25°C with conformal coating b.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

6AG1153-1AA03-2XB0 SIEMENS SIPLUS DP ET200M IM153-1 -40...+70°C start up Temp -25°C with conformal coating b..

6AG1153-1AA03-2XB0

SIEMENS

SIPLUS DP ET200M IM153-1 -40...+70°C start up Temp -25°C with conformal coating based on 6ES7153-1AA03-0XB0 . INTERFACE FOR ET 200M, FOR MAX. 8 S7-300 MODULES

SIPLUS ET 200 interface module for ET 200M IM153-1, working temperature of -25 to +60 degrees C, based on 6ES7153-1AA03-0XB0

More details


AUTOMATION SYSTEMS > SIPLUS Extreme (LOGO, S7-1200, S7-1500, etc)

Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



ETIM: EC001604 - Fieldbus, decentr. periphery - communication module

Value Unit
Supporting protocol for Foundation Fieldbus (EF007522) -
Supply voltage AC 50 Hz (EF007532) ['-', '-']V
Supply voltage AC 60 Hz (EF007533) ['-', '-']V
Supply voltage DC (EF007534) ['20.4', '28.8']V
Voltage type of supply voltage (EF002991) DC
Supporting protocol for TCP/IP (EF003050) NO DATA
Supporting protocol for PROFIBUS (EF003052) true
Supporting protocol for CAN (EF003053) false
Supporting protocol for INTERBUS (EF003054) false
Supporting protocol for ASI (EF003051) false
Supporting protocol for KNX (EF003055) false
Supporting protocol for Modbus (EF003057) false
Supporting protocol for Data-Highway (EF003058) false
Supporting protocol for DeviceNet (EF003059) false
Supporting protocol for SUCONET (EF003060) false
Supporting protocol for LON (EF003017) false
Supporting protocol for SERCOS (EF006657) false
Supporting protocol for PROFINET IO (EF007525) false
Supporting protocol for PROFINET CBA (EF007524) false
Supporting protocol for EtherNet/IP (EF007521) false
Supporting protocol for AS-Interface Safety at Work (EF007519) false
Supporting protocol for DeviceNet Safety (EF007520) false
Supporting protocol for INTERBUS-Safety (EF006662) false
Supporting protocol for PROFIsafe (EF007526) false
Supporting protocol for SafetyBUS p (EF007527) false
Supporting protocol for other bus systems (EF003062) false
Radio standard Bluetooth (EF007178) false
Radio standard WLAN 802.11 (EF007179) false
Radio standard GPRS (EF008523) false
Radio standard GSM (EF008524) false
Radio standard UMTS (EF008525) false
IO link master (EF007298) false
System accessory (EF004118) true
Degree of protection (IP) (EF005474) IP20
With potential separation (EF003272) true
Fieldbus connection over separate bus coupler possible (EF004002) false
Rail mounting possible (EF003972) true
Wall mounting/direct mounting (EF007020) true
Front build in possible (EF007016) true
Rack-assembly possible (EF007018) false
Suitable for safety functions (EF001597) false
Category according to EN 954-1 (EF006782) -
SIL according to IEC 61508 (EF009889) -
Performance level according to EN ISO 13849-1 (EF007399) -
Appendant operation agent (Ex ia) (EF004141) false
Appendant operation agent (Ex ib) (EF004142) false
Explosion safety category for gas (EF003997) ATEX gas-ex-protection, Cat. 3G
Explosion safety category for dust (EF003998) None
Width (EF000008) 40.0mm
Height (EF000040) 125.0mm
Depth (EF000049) 117.0mm


SIPLUS DP ET200M IM153-1 -40...+70°C start up Temp -25°C with conformal coating based on 6ES7153-1AA03-0XB0 . INTERFACE FOR ET 200M, FOR MAX. 8 S7-300 MODULES
General information
Product type designationIM 153-1 DP ST
Vendor identification (VendorID)801Dh
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
external protection for power supply lines (recommendation)not necessary
Mains buffering
● Mains/voltage failure stored energy time5 ms
Input current
Current consumption, max.350 mA; At 24 V DC
Inrush current, typ.2.5 A
I²t0.1 A²·s
Output voltage
Rated value (DC)5 V
Output current
for backplane bus (5 V DC), max.1 A
Power loss
Power loss, typ.3 W
Address area
Addressing volume
● Inputs128 byte
● Outputs128 byte
Hardware configuration
Number of modules per DP slave interface, max.8
Interfaces
Transmission procedureRS 485
Transmission rate, max.12 Mbit/s
1. Interface
automatic detection of transmission rateYes
Interface types
● Output current of the interface, max.90 mA
● Design of the connection9-pin sub D socket
PROFIBUS DP slave
● GSD file(for DPV1) SIEM801D.GSD; SI01801D.GSG
● automatic baud rate searchYes
Protocols
Bus protocol/transmission protocolPROFIBUS DP to EN 50170
Protocols (Ethernet)
● TCP/IPNo
PROFIBUS DP
● Number of node addresses, max.1 to 125 permitted
Services
— SYNC capabilityYes
— FREEZE capabilityYes
— Direct data exchange (slave-to-slave communication)Yes; Sender
Potential separation
Potential separation existsYes
Isolation
Isolation tested withIsolation voltage 500 V
Degree and class of protection
IP degree of protectionIP20
Ambient conditions
Ambient temperature during operation
● min.-40 °C; = Tmin
● max.70 °C; = Tmax; 60 °C @ UL/cUL, ATEX and FM use
● At cold restart, min.-25 °C
Ambient temperature during storage/transportation
● min.-40 °C
● max.70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.5 000 m
● Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Configuration
Configuration software
● STEP 7STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file
Dimensions
Width40 mm
Height125 mm
Depth117 mm
Weights
Weight, approx.360 g
last modified:08/24/2020


Product
Article Number (Market Facing Number)6AG1153-1AA03-2XB0
Product DescriptionSIPLUS DP ET200M IM153-1 -40...+70°C start up Temp -25°C with conformal coating based on 6ES7153-1AA03-0XB0 . INTERFACE FOR ET 200M, FOR MAX. 8 S7-300 MODULES
Product familySIPLUS ET 200M IM 153-1/153-2
Product Lifecycle (PLM)PM300:Active Product
Price data
Price Group473
Surcharge for Raw MaterialsNone
Metal FactorNone
Delivery information
Export Control RegulationsAL : N / ECCN : N
Standard lead time ex-works33 Day/Days
Net Weight (kg)0,282 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension12,90 x 15,20 x 5,10
Package size unit of measureCM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4025515136309
UPC662643199468
Commodity Code85389091
LKZ_FDB/ CatalogIDA&DSE/SIP ADD
Product Group4646
Group CodeR740
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 01.09.2014
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-24-26-08
eClass7.127-24-26-08
eClass827-24-26-08
eClass927-24-26-08
eClass9.127-24-26-08
ETIM4EC001604
ETIM5EC001604
ETIM6EC001604
ETIM7EC001604
IDEA43564
UNSPSC1432-15-17-05
UNSPSC1532-15-17-05

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.