6AG1132-6BF00-7CA0 SIEMENS SIPLUS ET 200SP -40...+70°C start up temperature: -25°C with conformal coating ba.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

6AG1132-6BF00-7CA0 SIEMENS SIPLUS ET 200SP -40...+70°C start up temperature: -25°C with conformal coating ba..

6AG1132-6BF00-7CA0

SIEMENS

SIPLUS ET 200SP -40...+70°C start up temperature: -25°C with conformal coating based on 6ES7132-6BF00-0CA0 . digital output module, DQ 8x 24VDC/0.5A High Feature suitable for BU type A0, Color code CC02, channel diagnostics

SIPLUS ET 200SP -40...+70 ° C temp. boot: -25 ° C with coating formed based on 6ES7132-6BF00-0CA0 . Digital output, DQ 8X24VDC/0.5 A HIGH FEATURE, Suitable for type BU A0, color code CC02, channel diagnosis

More details


AUTOMATION SYSTEMS > SIPLUS Extreme (LOGO, S7-1200, S7-1500, etc)

Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



ETIM: EC001599 - Fieldbus, decentr. periphery - digital I/O module

Value Unit
Supply voltage AC 60 Hz (EF007533) -V
Type of digital output (EF003601) -
Type of electric connection (EF003961) -
Permitted voltage at output (EF007553) -V
Type of output voltage (EF008222) -
Performance level according to EN ISO 13849-1 (EF007399) -
Category according to EN 954-1 (EF006782) -
Explosion safety category for gas (EF003997) -
Explosion safety category for dust (EF003998) -
Degree of protection (IP) (EF005474) -
SIL according to IEC 61508 (EF009889) -
Supply voltage AC 50 Hz (EF007532) -V
Supply voltage DC (EF007534) ['19.2', '28.8']V
Voltage type of supply voltage (EF002991) DC
Number of digital inputs (EF001992) 0
Number of digital outputs (EF001993) 8
Digital inputs configurable (EF008516) -
Digital outputs configurable (EF008520) true
Input current at signal 1 (EF001428) -mA
Permitted voltage at input (EF007554) ['-', '-']V
Type of voltage (input voltage) (EF003033) -
Output current (EF003202) 0.5A
Short-circuit protection, outputs available (EF003203) -
Number of HW-interfaces industrial Ethernet (EF003020) 0
Number of interfaces PROFINET (EF006932) -
Number of HW-interfaces RS-232 (EF003021) 0
Number of HW-interfaces RS-422 (EF003022) 0
Number of HW-interfaces RS-485 (EF003023) -
Number of HW-interfaces serial TTY (EF003024) 0
Number of HW-interfaces parallel (EF003026) 0
Number of HW-interfaces Wireless (EF006933) 0
Number of HW-interfaces USB (EF003025) 0
Number of HW-interfaces other (EF003027) 0
With optical interface (EF003028) false
Supporting protocol for TCP/IP (EF003050) false
Supporting protocol for PROFIBUS (EF003052) -
Supporting protocol for CAN (EF003053) false
Supporting protocol for INTERBUS (EF003054) false
Supporting protocol for ASI (EF003051) false
Supporting protocol for KNX (EF003055) false
Supporting protocol for Modbus (EF003057) false
Supporting protocol for Data-Highway (EF003058) false
Supporting protocol for DeviceNet (EF003059) false
Supporting protocol for SUCONET (EF003060) false
Supporting protocol for LON (EF003017) false
Supporting protocol for PROFINET IO (EF007525) -
Supporting protocol for PROFINET CBA (EF007524) false
Supporting protocol for SERCOS (EF006657) false
Supporting protocol for Foundation Fieldbus (EF007522) false
Supporting protocol for EtherNet/IP (EF007521) false
Supporting protocol for AS-Interface Safety at Work (EF007519) false
Supporting protocol for DeviceNet Safety (EF007520) false
Supporting protocol for INTERBUS-Safety (EF006662) false
Supporting protocol for PROFIsafe (EF007526) -
Supporting protocol for SafetyBUS p (EF007527) false
Supporting protocol for other bus systems (EF003062) false
Radio standard Bluetooth (EF007178) false
Radio standard WLAN 802.11 (EF007179) false
Radio standard GPRS (EF008523) false
Radio standard GSM (EF008524) false
Radio standard UMTS (EF008525) false
IO link master (EF007298) false
System accessory (EF004118) true
Fieldbus connection over separate bus coupler possible (EF004002) -
Rail mounting possible (EF003972) true
Wall mounting/direct mounting (EF007020) false
Front build in possible (EF007016) true
Rack-assembly possible (EF007018) true
Suitable for safety functions (EF001597) -
Appendant operation agent (Ex ia) (EF004141) -
Appendant operation agent (Ex ib) (EF004142) -
Width (EF000008) 15.0mm
Height (EF000040) 73.0mm
Depth (EF000049) 58.0mm
Time delay at signal exchange (EF002382) -ms


SIPLUS ET 200SP -40...+70°C start up temperature: -25°C with conformal coating based on 6ES7132-6BF00-0CA0 . digital output module, DQ 8x 24VDC/0.5A High Feature suitable for BU type A0, Color code CC02, channel diagnostics
General information
Product type designationDQ 8x24 V DC/0.5 A HF
Firmware versionV1.2
● FW update possibleYes
usable BaseUnitsBU type A0
Color code for module-specific color identification plateCC02
Product function
● I&M dataYes; I&M0 to I&M3
● Isochronous modeYes
Engineering with
● PROFIBUS from GSD version/GSD revisionGSD Revision 5
● PROFINET from GSD version/GSD revisionGSDML V2.3
Operating mode
● DQYes
● DQ with energy-saving functionNo
● PWMNo
● OversamplingNo
● MSOYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.45 mA; without load
Output voltage
Rated value (DC)24 V
Power loss
Power loss, typ.1 W
Address area
Address space per module
● Address space per module, max.1 byte; + 1 byte for QI information
Digital outputs
Number of digital outputs8
Current-sinkingNo
Current-sourcingYes
Digital outputs, parameterizableYes
Short-circuit protection
● Response threshold, typ.0.7 to 1.3 A
Limitation of inductive shutdown voltage toTyp. L+ (-50 V)
Controlling a digital inputYes
Switching capacity of the outputs
● with resistive load, max.0.5 A
● on lamp load, max.5 W
Load resistance range
● lower limit48 Ω
● upper limit12 kΩ
Output current
● for signal "1" rated value0.5 A
● for signal "0" residual current, max.0.1 mA
Output delay with resistive load
● "0" to "1", typ.50 µs
● "1" to "0", typ.100 µs
Parallel switching of two outputs
● for upratingNo
● for redundant control of a loadYes
Switching frequency
● with resistive load, max.100 Hz
● with inductive load, max.2 Hz
● on lamp load, max.10 Hz
Total current of the outputs
● Current per channel, max.0.5 A
● Current per module, max.4 A
Total current of the outputs (per module)
horizontal installation
— up to 60 °C, max.4 A
vertical installation
— up to 60 °C, max.4 A
Cable length
● shielded, max.1 000 m
● unshielded, max.600 m
Isochronous mode
Execution and activation time (TCO), min.48 µs
Bus cycle time (TDP), min.500 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
● Diagnostic alarmYes
Diagnoses
● Monitoring the supply voltageYes
● Wire-breakYes; channel by channel
● Short-circuitYes; channel by channel
● Group errorYes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
● Channel status displayYes; green LED
● for channel diagnosticsYes; red LED
● for module diagnosticsYes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channelsNo
● between the channels and backplane busYes
Permissible potential difference
between different circuits75 V DC/60 V AC (base isolation)
Isolation
Isolation tested with707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
● horizontal installation, max.70 °C; = Tmax; > +60 °C max. total current 1.0 A
● vertical installation, min.-40 °C; = Tmin
● vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
● Installation altitude above sea level, max.5 000 m
● Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
● Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
● Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
● Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.30 g
last modified:08/29/2020


Product
Article Number (Market Facing Number)6AG1132-6BF00-7CA0
Product DescriptionSIPLUS ET 200SP -40...+70°C start up temperature: -25°C with conformal coating based on 6ES7132-6BF00-0CA0 . digital output module, DQ 8x 24VDC/0.5A High Feature suitable for BU type A0, Color code CC02, channel diagnostics
Product familySIPLUS digital outputs
Product Lifecycle (PLM)PM300:Active Product
Price data
Price Group473
Surcharge for Raw MaterialsNone
Metal FactorNone
Delivery information
Export Control RegulationsAL : N / ECCN : EAR99H
Standard lead time ex-works37 Day/Days
Net Weight (kg)0,036 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension6,50 x 7,70 x 2,30
Package size unit of measureCM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4047618068721
UPC804766490606
Commodity Code85389091
LKZ_FDB/ CatalogIDA&DSE/SIP ADD
Product Group4257
Group CodeR740
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 14.12.2012
Product classB: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

4,4'-isopropylidenediphenol (Bisphenol A, BPA)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-24-26-04
eClass7.127-24-26-04
eClass827-24-26-04
eClass927-24-26-04
eClass9.127-24-26-04
ETIM5EC001599
ETIM6EC001599
ETIM7EC001599
IDEA43566
UNSPSC1532-15-17-05

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.