ANUNCIAR
5SV4414-0 SIEMENS Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 100 mA, Un AC: 230 V View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

5SV4414-0 SIEMENS Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 100 mA, Un AC: 230 V

5SV4414-0

SIEMENS

Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 100 mA, Un AC: 230 V

Differential switch 5SV, 70mm, AC class, 2 poles, 40A, 100mA

More details


POWER DISTRIBUTION AND LOW VOLTAGE SWITCHGEAR > Tertiary differential switches up to 80 A

Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

Total: $177.95
Unit price: $177.95
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



ETIM: EC000003 - Residual current circuit breaker (RCCB)

Value Unit
Number of poles (EF001391) 2
Rated voltage (EF000228) 230V
Rated current (EF000227) 40A
Rated fault current (EF002358) 0.1mA
Rated insulation voltage Ui (EF001366) -V
Mounting method (EF000003) DIN rail
Leakage current type (EF002560) AC
Selective protection (EF002561) false
Short-time delayed tripping (EF003604) false
Short-circuit breaking capacity (Icw) (EF002562) 10.0kA
Frequency (EF005455) 50 Hz
Additional equipment possible (EF008148) true
With interlocking device (EF007385) true
Degree of protection (IP) (EF005474) IP20
Width in number of modular spacings (EF002950) 2
Built-in depth (EF000218) 70.0mm
Ambient temperature during operating (EF007515) ['-25', '45']°C
Pollution degree (EF002570) -
Connectable conductor cross section multi-wired (EF007343) ['0.75', '35.0']mm²
Connectable conductor cross section solid-core (EF007337) ['0.75', '35.0']mm²
Surge current capacity (EF002564) -kA
Rated impulse withstand voltage Uimp (EF011980) -kV


Residual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 100 mA, Un AC: 230 V
Model
product brand nameSENTRON
Product designationRCCB
Design of the productInstantaneous
General technical data
number of poles2
Size of installation devices / acc. to DIN 438801
Protection against electrical shockFinger and back-of-hand safe
Short-circuit current / of series fuse / maximum permissible63 A
Short-circuit current rating10 kA
Mechanical service life (switching cycles) / typical10 000
Switching function / short-term delayedNo
overvoltage categoryIII
Supply voltage
Operating current / at AC / rated value40 A
Supply voltage
● at AC / rated value230/400 V
● for testing equipment / minimum100 V
Operating frequency50 Hz
● Supply voltage frequency / rated value50 Hz
Protection class
Protection class IPIP20, if the distribution board is installed, with connected conductors
Switching capacity
Switching capacity current
● acc. to EN 60898 / rated value0.5 kA
● according to IEC 61008-1 / rated value0.5 kA
Dissipation
● Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole1.6 W
● power loss [W] / maximum3.2 W
Current
Tripping residual current / rated value100 mA
Type of fault currentAC
Operating current
● at 40 °C / rated value40 A
● at 45 °C / rated value38.1 A
● at 50 °C / rated value35.59 A
● at 55 °C / rated value32.29 A
● at 60 °C / rated value28.19 A
● at 65 °C / rated value23.3 A
● at 70 °C / rated value17.62 A
Product details
product feature / silicon-freeYes
Product extension / can be installed / supplementary devicesYes
Connections
connectable conductor cross-section / solid
● minimum0.75 mm²
● maximum35 mm²
Connectable conductor cross-section / stranded
● minimum0.75 mm²
● maximum35 mm²
Tightening torque / with screw-type terminals
● minimum2.5 N·m
● maximum3 N·m
Position / of power supply cordtop or bottom
Mechanical Design
Height90 mm
Width36 mm
Depth70 mm
installation depth70 mm
number of width units2
Mounting typeDIN rail (REG)
mounting positionany
net weight197 g
Environmental conditions
Ambient temperature
● minimum-25 °C
● maximum45 °C
Ambient temperature / during storage
● minimum permissible-40 °C
● maximum permissible75 °C
Number of test cycles / for environmental testing / acc. to IEC 60068-2-3028
Certificates
● reference code / acc. to DIN EN 61346-2F
● Reference code / acc. to DIN EN 81346-2F
General Product ApprovalEMCDeclaration of Conformityother

CCC

IMQ

Miscellaneous

RCM

EC/EU-Declaration of Conformity

Miscellaneous

Railway

Vibration and Shock

Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
CAx-Online-Generator
Tender specifications


Product
Article Number (Market Facing Number)5SV4414-0
Product DescriptionResidual current operated circuit breaker, 2-pole, Type AC, In: 40 A, 100 mA, Un AC: 230 V
Product familyNot available
Product Lifecycle (PLM)PM300:Active Product
Price data
Price Group194
Surcharge for Raw MaterialsNone
Metal FactorL-A-----
Delivery information
Export Control RegulationsECCN : N / AL : N
Standard lead time ex-works2 Day/Days
Net Weight (kg)0,185 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension97,00 x 42,00 x 85,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4001869429823
UPCNot available
Commodity Code85362010
LKZ_FDB/ CatalogIDLV10.1
Product Group5510
Group CodeP310
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 01.06.2006
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
Not available

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.