5SD7442-1 SIEMENS Combination arrester type 1+2 Requirement class B+C, UC 350V Pluggable protective modules .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

5SD7442-1 SIEMENS Combination arrester type 1+2 Requirement class B+C, UC 350V Pluggable protective modules ..

5SD7442-1

SIEMENS

Combination arrester type 1+2 Requirement class B+C, UC 350V Pluggable protective modules 2-pole, 1+1 circuit for TN-S and TT systems with remote display

Combined unloader, requirement class B and C, types 1 and 2, classes I and II, 2 poles, TT and TN-S networks, 100 kA, 350VAC. Cancelations and returns limited. Consult conditions.

More details


Earthing, lightning and surge protection > Surge protection device for power supply systems

POWER DISTRIBUTION AND LOW VOLTAGE SWITCHGEAR > Other Modular Systems

* Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

Total price: $680.28
Unit price: $680.28

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Combination arrester type 1+2 Requirement class B+C, UC 350V Pluggable protective modules 2-pole, 1+1 circuit for TN-S and TT systems with remote display
General data
standardIEC 61643-11: 2011, EN 61643-11: 2012
product designationSurge protection device
SPD classification / according to EN 61643-11
● Test Class I, Type 1Yes
● Test Class II, Type 2Yes
● Test Class III, Type 3No
number of SPD ports1
Product versionArrester combination
design of pole1/N/PE
designation of the protective pathsL-N, L-PE, N-PE
Accessories1 x 5SD7428-1 + 1 x 5SD7418-0 + 1 x 5SD7448-1
fastening methodDIN rail NS 35
material / of the enclosurePBT
size of surge arrester4 TE
Degree of pollution2
overvoltage category / according to IEC 61010-1III
protection class IP / at connection all terminalsIP20
shock acceleration25 gn
vibrational acceleration / at 5 Hz ... 500 Hz / limited to 2,5 h / per axis5 gn
Ambient temperature / during operation / minimum permissible ... ambient temperature / during operation / maximum permissible-40 °C ... 80 °C
ambient temperature / during storage and transport-40 °C ... 80 °C
relative humidity / during operation5 % ... 95 %
installation altitude / at height above sea level / maximum2 000 m
Width71.5 mm
Height95 mm
depth71.5 mm
net weight693 g
Electrical data
type of distribution systemTT, TN-S
operating voltage230 V
continuous operating voltage
● maximum350 V
● between N and PE350 V
● between L and (PE)N350 V
apparent power consumption / maximum100 mVA
discharge current
● between L and (PE)N / at (8/20) µs25 kA
● between L and PE / at (8/20) µs25 kA
● between N and PE / at (8/20) µs100 kA
lightning current peak value / at (10/350) µs
● lightning current peak value / between L and PE25 kA
● lightning current peak value / between N and PE100 kA
● lightning current peak value / between L and N25 kA
charge of the flash / at (10/350) µs
● charge of the flash / between L and N12.5 A·s
● charge of the flash / between L and PE12.5 A·s
● charge of the flash / between N and PE50 A·s
specific energy of the flash / at (10/350) µs
● between L and N160
● between L and PE160
● between N and PE2 500
follow current extinguishing capability
● between N and PE100 A (350 V AC)
● between L and N25 kA (264 V AC), 3 kA (350 V AC)
short-circuit rating (SCCR) / at 264 V25 kA
protection level
● between L and N1.5 kV
● between L and PE2.2 kV
● between N and PE1.5 kV
residual voltage
● between L and (PE)N
— at rated value of discharge current / maximum1.5 kV
— at 10 kA / maximum1.2 kV
— at 5 kA / maximum1 kV
— at 3 kA / maximum0.9 kV
● between L and PE
— at rated value of discharge current / maximum2.2 kV
— at 10 kA / maximum2 kV
— at 5 kA / maximum1.8 kV
— at 3 kA / maximum1.6 kV
● between N and PE
— at rated value of discharge current / maximum1.5 kV
— at 10 kA / maximum1 kV
— at 5 kA / maximum0.9 kV
— at 3 kA / maximum0.8 kV
response value of the surge voltage / at 6 kV / at (1.2/50) µs
● between L and N1.5 kV
● between L and PE2.2 kV
● between N and PE1.5 kV
● response time / between L and (PE)N25 ns
● response time / between N and PE100 ns
adjustable response factor / of tripping current1.6
fuse protection type / at V-shaped connection125 A AC (gG)
fuse protection type / for T-connector315 A AC (gG)
Connections/ Terminals
type of electrical connectionScrew terminal
stripped length18 mm
tightening torque4.3 ... 4.7
stripped length18 mm
connectable conductor cross-section
● for finely stranded conductor2.5 ... 25
● for rigid conductor2.5 ... 35
● finely stranded2.5 ... 25
AWG number / as coded connectable conductor cross section13 ... 2
design of the thread / of the connection screwM5
signal designOptical, remote signaling contact
Indicator/remote signaling
switching function / of the remote signaling contactsPDT contact
operating voltage / of the remote signaling contacts / at AC12 ... 250
operational current / of the remote signaling contacts / at AC10 mA ... 1 A
connection type of remote signaling contactM2 screw thread
connectable conductor cross-section
● for remote signaling contacts / for rigid conductor0.14 ... 1.5
● for finely stranded conductor / for remote signaling contacts0.14 ... 1.5
AWG number / as coded connectable conductor cross section / for remote signaling contacts / minimum28
AWG number / as coded connectable conductor cross section / for remote signaling contacts / maximum16
tightening torque / for remote signaling contacts0.25 N·m
stripped length / of the cable / for remote signaling contacts7 mm
NEMA/UL - Data
type of surge protective device (SPD) / according to UL4CA
type of distribution system / according to UL1S
type of distribution systemTT, TN-S
designation of the protective paths / according to ULL-N, L-G, N-G
TOV behavior
● at TOV test voltage (L-N)415 V AC (5 s / withstand mode) / 457 V AC (120 min / safe failure mode)
● at TOV test voltage (N-PE)1200 V (200 ms / withstand mode)
Measured Limiting Voltage (MLV) / between L and Ground (GND)1.55 kV
Measured Limiting Voltage (MLV) / between L and N1.34 kV
Measured Limiting Voltage (MLV) / between N and Ground (GND)1.08 kV
Maximum Continuous Operating Voltage (MCOV) / between L and Ground (GND)528 V
Maximum Continuous Operating Voltage (MCOV) / between L and N264 V
Maximum Continuous Operating Voltage (MCOV) / between N and Ground (GND)264 V
leakage current / according to UL20 kA
leakage current / according to UL20 kA
leakage current / according to UL20 kA
AWG number / as coded connectable conductor cross section / for remote signaling contacts / according to UL / minimum30
AWG number / as coded connectable conductor cross section / for remote signaling contacts / according to UL / maximum14
installation altitude above sea level / according to UL6 562 ft
gross weight [lb] / according to UL1.63 lb
net weight [lb] / according to UL1.53 lb
combustibility class according to UL 94V0
standards / according to ULUL 1449 edition 4
operating voltage / of the remote signaling contacts / according to UL125 V
operational current / of the remote signaling contacts / at AC / according to UL1 A
AWG number / as coded connectable conductor cross section / according to UL / minimum12

Downloads and manuals

AWG number / as coded connectable conductor cross section / according to UL / maximum2
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
CAx-Online-Generator


Additional data

Product
Article Number (Market Facing Number)5SD7442-1
Product DescriptionCombination arrester type 1+2 Requirement class B+C, UC 350V Pluggable protective modules 2-pole, 1+1 circuit for TN-S and TT systems with remote display
Product familyBasic devices
Product Lifecycle (PLM)PM300:Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group12G / 1BK
Surcharge for Raw MaterialsNone
Metal FactorL-P-----
Delivery information
Export Control RegulationsAL : N / ECCN : N
Standard lead time ex-works5 Day/Days
Net Weight (kg)0,666 Kg
Packaging Dimension95,00 x 77,00 x 82,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4001869340531
UPCNot available
Commodity Code85363090
LKZ_FDB/ CatalogIDLV10.1
Product Group5524
Group CodeP310
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 01.07.2006
Product classB: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

2-(2H-benzotriazol-2-yl)-4,6-ditertpentylphenol (UV-328)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

2,4-di-tert-butyl-6-(5-chlorobenzotriazol-2-yl)phenol (UV-327)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-13-08-05
eClass7.127-13-08-05
eClass827-13-08-05
eClass927-13-08-05
eClass9.127-13-08-05
ETIM5EC000941
ETIM6EC000941
ETIM7EC000941
ETIM8EC000941

ETIM data

ETIM: EC000941 - Surge protection device for power supply systems

Value Unit
Max. discharge surge current (8/20) (EF012274) -kA
Number of conductors (without earthing) (EF001148) -
System configuration DC (EF009926) 0
System configuration IT (EF009927) 0
System configuration TN (EF009928) 0
System configuration TN-C (EF009929) 0
System configuration TN-C-S (EF009933) 0
System configuration TN-S (EF009930) 0
System configuration TT (EF009931) 0
System configuration other (EF009932) 0
Nominal voltage AC (EF004220) -V
Nominal voltage DC (EF004221) -V
Short-circuit breaking capacity (Isccr) (EF012627) 25.0kA
Max. continuous voltage AC (EF004198) -V
Max. continuous voltage DC (EF004777) -V
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Construction size (EF002566) 4 modular spacing
Max. PV-voltage (EF008795) -V
Max. conductor cross section solid (solid, stranded) (EF008827) 35.0mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 25.0mm²
With remote signalling contact (EF000422) true
Integrated backup fuse (EF008797) false
Signalling at the device (EF004241) Optic
Category type 2 (EF004230) true
Degree of protection (IP) (EF005474) IP20
Nominal discharge surge current (8/20) (EF004214) -kA
Voltage protection level N-PE (EF008796) -kV
Voltage protection level L-N (EF004236) -kV
Voltage protection level (EF003525) -kV


Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.