5SD7413-3 SIEMENS Lightning conductor T1/T2, UN 240/400 V, UC 335 V A.C., pluggable protective modules, 3+0 .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

5SD7413-3 SIEMENS Lightning conductor T1/T2, UN 240/400 V, UC 335 V A.C., pluggable protective modules, 3+0 ..

5SD7413-3

SIEMENS

Lightning conductor T1/T2, UN 240/400 V, UC 335 V A.C., pluggable protective modules, 3+0 circuit (TN-C), Width 54 mm with remote signaling

3-POLE SURGE DISCHARGER, FOR TN-C NETWORK SYSTEMS, 37.5 KA (WITH REMOTE WARNING). Manufactured to order. Non-Cancelable Non-Returnable.

More details


Earthing, lightning and surge protection > Surge protection device for power supply systems

POWER DISTRIBUTION AND LOW VOLTAGE SWITCHGEAR > Other Modular Systems

* Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

Total price: $425.99
Unit price: $425.99

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Lightning conductor T1/T2, UN 240/400 V, UC 335 V A.C., pluggable protective modules, 3+0 circuit (TN-C), Width 54 mm with remote signaling
General data
standardIEC 61643-11: 2011, EN 61643-11: 2012
product designationSurge protection device
SPD classification / according to EN 61643-11
● Test Class I, Type 1Yes
● Test Class II, Type 2Yes
● Test Class III, Type 3No
number of SPD ports1
Product versionCombination surge arresters
design of pole3
designation of the protective pathsL-PEN
Accessories3 x 5SD7418-3
fastening methodDIN rail NS 35
material / of the enclosurePA 6.6 / PBT
size of surge arrester3 MW
Degree of pollution2
overvoltage category / according to IEC 61010-1III
protection class IP / at connection all terminalsIP20
shock acceleration30 gn
vibrational acceleration / at 5 Hz ... 500 Hz / limited to 2,5 h / per axis7.5 gn
Ambient temperature / during operation / minimum permissible ... ambient temperature / during operation / maximum permissible-40 °C ... 80 °C
ambient temperature / during storage and transport-40 °C ... 80 °C
relative humidity / during operation5 % ... 95 %
installation altitude / at height above sea level / maximum2 000 m
Width53.4 mm
Height98.7 mm
depth77.5 mm
net weight525 g
Electrical data
type of distribution systemTN-C
operating voltage230 V
continuous operating voltage
● maximum335 V
apparent power consumption / maximum810 mVA
discharge current
● at (8/20) µs12.5 kA
● 1 phase / at (8/20) µs50 kA
● between L and (PE)N / at (8/20) µs12.5 kA
● between L and N / at (8/20) µs50 kA
total discharge current / at (8/20) µs150 kA
total lightning impulse current / at (10/350) µs37.5 kA
lightning current peak value / at (10/350) µs12.5 kA
charge of the flash / at (10/350) µs6.25 A·s
specific energy of the flash / at (10/350) µs39
short-circuit rating (SCCR) / at 264 V25 kA
protection level1.2 kV
● maximum1.2 kV
● between N and L1.6 kV
residual voltage
● at rated value of discharge current / maximum1.2 kV
● at 10 kA / maximum1.1 kV
● at 5 kA / maximum1 kV
● at 3 kA / maximum0.9 kV
● Response time25 ns
adjustable response factor / of tripping current1.6
fuse protection type / at V-shaped connection80 A AC (gG)
fuse protection type / for T-connector160 A AC (gG)
Connections/ Terminals
type of electrical connectionScrew terminal
stripped length16 mm
tightening torque4.3 ... 4.7
stripped length16 mm
connectable conductor cross-section
● for finely stranded conductor1.5 ... 25
● for rigid conductor1.5 ... 35
● finely stranded1.5 ... 25
AWG number / as coded connectable conductor cross section15 ... 2
design of the thread / of the connection screwM5
signal designOptical, remote signaling contact
Indicator/remote signaling
switching function / of the remote signaling contactsPDT contact
operating voltage / of the remote signaling contacts / at AC5 ... 250
operational current / of the remote signaling contacts / at AC5 mA ... 1.5 A
connection type of remote signaling contactM2
connectable conductor cross-section
● for remote signaling contacts / for rigid conductor0.14 ... 1.5
● for finely stranded conductor / for remote signaling contacts0.14 ... 1.5
AWG number / as coded connectable conductor cross section / for remote signaling contacts / minimum28
AWG number / as coded connectable conductor cross section / for remote signaling contacts / maximum16
tightening torque / for remote signaling contacts0.25 N·m
stripped length / of the cable / for remote signaling contacts7 mm
NEMA/UL - Data
type of distribution systemTN-C
TOV behavior
● at TOV test voltage415 V AC (5 s / withstand mode)

Downloads and manuals

combustibility class according to UL 94V0
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
CAx-Online-Generator


Additional data

Product
Article Number (Market Facing Number)5SD7413-3
Product DescriptionLightning conductor T1/T2, UN 240/400 V, UC 335 V A.C., pluggable protective modules, 3+0 circuit (TN-C), Width 54 mm with remote signaling
Product familyBasic devices
Product Lifecycle (PLM)PM300:Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group12G / 1BK
Surcharge for Raw MaterialsNone
Metal FactorL-P-----
Delivery information
Export Control RegulationsAL : N / ECCN : N
Standard lead time ex-works2 Day/Days
Net Weight (kg)0,556 Kg
Packaging Dimension76,00 x 106,00 x 78,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4001869427638
UPCNot available
Commodity Code85363090
LKZ_FDB/ CatalogIDLV10.1
Product Group5524
Group CodeP310
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 01.05.2010
Product classC: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-13-08-05
eClass7.127-13-08-05
eClass827-13-08-05
eClass927-13-08-05
eClass9.127-13-08-05
ETIM5EC000941
ETIM6EC000941
ETIM7EC000941
ETIM8EC000941

ETIM data

ETIM: EC000941 - Surge protection device for power supply systems

Value Unit
Max. discharge surge current (8/20) (EF012274) -kA
Number of conductors (without earthing) (EF001148) -
System configuration DC (EF009926) 0
System configuration IT (EF009927) 0
System configuration TN (EF009928) 0
System configuration TN-C (EF009929) 1
System configuration TN-C-S (EF009933) 0
System configuration TN-S (EF009930) 0
System configuration TT (EF009931) 0
System configuration other (EF009932) 0
Nominal discharge surge current (8/20) (EF004214) 50.0kA
Nominal voltage AC (EF004220) -V
Nominal voltage DC (EF004221) -V
Short-circuit breaking capacity (Isccr) (EF012627) 25.0kA
Max. continuous voltage AC (EF004198) 335V
Max. continuous voltage DC (EF004777) -V
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Construction size (EF002566) 3 modular spacing
Max. PV-voltage (EF008795) -V
Voltage protection level (EF003525) 1200.0kV
Max. conductor cross section solid (solid, stranded) (EF008827) 35.0mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 25.0mm²
Voltage protection level L-N (EF004236) 1.6kV
With remote signalling contact (EF000422) true
Integrated backup fuse (EF008797) false
Signalling at the device (EF004241) Optic
Category type 2 (EF004230) true
Degree of protection (IP) (EF005474) IP20
Voltage protection level N-PE (EF008796) -kV


Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.