3VA5225-6EC31-0AA0 SIEMENS circuit breaker 3VA5 UL frame 250 breaking capacity class H 65kA @ 480V 3-pole, l.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

3VA5225-6EC31-0AA0 SIEMENS circuit breaker 3VA5 UL frame 250 breaking capacity class H 65kA @ 480V 3-pole, l..

3VA5225-6EC31-0AA0

SIEMENS

circuit breaker 3VA5 UL frame 250 breaking capacity class H 65kA @ 480V 3-pole, line protection TM230, FTAM, In=250A overload protection Ir=250A fixed short-circuit protection Ii=5...10 x In without connection

AUTOMATIC SWITCH 3VA5 UL size 250 CUTTING POWER CLASS H 65KA @ 480 V 3 POLES, PROTEC. DISTRIBUTIONS TM230, FTAM, IN=250A OVERLOAD PROTECTION IR=250A FIXEDLY ADJUSTED SHORT CIRCUIT PROTECTION II=5...10 X IN WITHOUT ELEMENT. CONNECTION. Manufactured to order. Non-Cancelable Non-Returnable.

More details


POWER DISTRIBUTION AND LOW VOLTAGE SWITCHGEAR > Moulded Case Circuit Breakers 3VA SENTRON

* Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

Total price: $1,110.16
Unit price: $1,110.16

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Additional data

Product
Article Number (Market Facing Number)3VA5225-6EC31-0AA0
Product Descriptioncircuit breaker 3VA5 UL frame 250 breaking capacity class H 65kA @ 480V 3-pole, line protection TM230, FTAM, In=250A overload protection Ir=250A fixed short-circuit protection Ii=5...10 x In without connection
Product family3VA Molded Case Circuit Breakers up to 1000 A, UL / IEC
Product Lifecycle (PLM)PM300:Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group12P / 1CB
Surcharge for Raw MaterialsNone
Metal FactorLOA-----
Delivery information
Export Control RegulationsAL : N / ECCN : EAR99
Standard lead time ex-works40 Day/Days
Net Weight (kg)2,048 Kg
Packaging Dimension150,00 x 245,00 x 160,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4042948853290
UPC804766308161
Commodity Code85362090
LKZ_FDB/ CatalogIDLV10
Product Group5385
Group CodeP360
Country of originCzech Republic
Compliance with the substance restrictions according to RoHS directiveSince: 01.01.2016
Product classC: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates
There is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
Classifications
VersionClassification
eClass627-37-04-09
eClass7.127-37-04-09
eClass827-37-04-09
eClass927-37-04-09
eClass9.127-37-04-09
ETIM5EC000228
ETIM6EC000228
ETIM7EC000228
ETIM8EC000228
IDEA44850
UNSPSC1539-12-16-01

ETIM data

ETIM: EC000228 - Power circuit-breaker for trafo/generator/installation protection

Value Unit
Rated permanent current Iu (EF001389) 250.0A
Rated voltage (EF003977) ['690', '690']V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (EF007048) 70.0kA
Overload release current setting (EF002336) ['-', '-']A
Adjustment range short-term delayed short-circuit release (EF007129) ['-', '-']A
Adjustment range undelayed short-circuit release (EF007131) ['-', '-']A
Integrated earth fault protection (EF007296) false
Type of electrical connection of main circuit (EF006819) Other
Device construction (EF008240) Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting (EF007250) true
DIN rail (top hat rail) mounting optional (EF008904) true
Number of auxiliary contacts as normally closed contact (EF001377) 0
Number of auxiliary contacts as normally open contact (EF001376) 0
Number of auxiliary contacts as change-over contact (EF003531) 0
With switched-off indicator (EF007006) -
With under voltage release (EF007518) -
Number of poles (EF001391) 3
Position of connection for main current circuit (EF006671) Other
Type of control element (EF006976) Rocker lever
Complete device with protection unit (EF008906) true
Motor drive integrated (EF006697) false
Motor drive optional (EF007386) true
Degree of protection (IP) (EF005474) IP40


Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.