3UG4822-1AA40 SIEMENS Digital monitoring relay Current monitoring, 22.5 mm for IO-Link 0.05...10.0 A AC/DC O.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

3UG4822-1AA40 SIEMENS Digital monitoring relay Current monitoring, 22.5 mm for IO-Link 0.05...10.0 A AC/DC O..

3UG4822-1AA40

SIEMENS

Digital monitoring relay Current monitoring, 22.5 mm for IO-Link 0.05...10.0 A AC/DC Overcurrent and undercurrent Transformer scaling factor Hysteresis 0.01 to 5.0 A ON-delay time Tripping delay time 1 change-over contact, screw terminal

More details


Relays > Current monitoring relay

CONTROL AND CONTACTORS > Function relays

* Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

Total price: $218.01
Unit price: $218.01

Quantity Price
1+$218.01
2+$210.81
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Technical data

Digital monitoring relay Current monitoring, 22.5 mm for IO-Link 0.05...10.0 A AC/DC Overcurrent and undercurrent Transformer scaling factor Hysteresis 0.01 to 5.0 A ON-delay time Tripping delay time 1 change-over contact, screw terminal
product brand nameSIRIUS
product designationCurrent monitoring relay with digital setting
product type designation3UG4
General technical data
product functionCurrent monitoring relay
design of the displayLCD
insulation voltage for overvoltage category III according to IEC 60664
● with degree of pollution 2 rated value690 V
degree of pollution2
surge voltage resistance rated value6 kV
maximum permissible voltage for safe isolation
● between control and auxiliary circuit690 V
protection class IPIP20
shock resistance according to IEC 60068-2-27sinusoidal half-wave 15g / 11 ms
vibration resistance according to IEC 60068-2-61 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
mechanical service life (switching cycles) typical10 000 001
electrical endurance (switching cycles) at AC-15 at 230 V typical100 000
thermal current of the switching element with contacts maximum5 A
reference code according to IEC 81346-2K
relative repeat accuracy1 %
Substance Prohibitance (Date)05/01/2012
Product Function
product function
● overcurrent detection 1 phaseYes
● overcurrent detection 3 phaseNo
● undercurrent detection 1 phaseYes
● undercurrent detection 3 phasesNo
● overcurrent detection DCYes
● undercurrent detection DCYes
● current window recognition DCYes
● voltage window recognition 1 phaseNo
● voltage window recognition 3 phaseNo
● adjustable open/closed-circuit current principleYes
● external resetYes
● auto-RESETYes
Supply voltage
type of voltage of the supply voltageDC
supply voltage 1 at DC18 ... 30 V
supply voltage 1 at DC rated value24 V
Measuring circuit
type of current for monitoringAC/DC
measurable current0.05 ... 10 A
measurable line frequency500 ... 40 Hz
adjustable current response value current
● 10.05 ... 10 A
● 20.05 ... 10 A
adjustable response delay time
● when starting0 ... 999.9 s
● with lower or upper limit violation0 ... 999.9 s
adjustable switching hysteresis for measured current value5 ... 10 mA
accuracy of digital display+/-1 digit
relative temperature-related measurement deviation5 %
internal resistance of the measuring circuit5 mΩ
Precision
relative metering precision5 %
Communication/ Protocol
protocol is supported IO-Link protocolYes
IO-Link transfer rateCOM2 (38,4 kBaud)
point-to-point cycle time between master and IO-Link device minimum10 ms
type of voltage supply via input/output link masterYes
data volume
● of the address range of the inputs with cyclical transfer total4 byte
● of the address range of the outputs with cyclical transfer total2 byte
Auxiliary circuit
number of NC contacts delayed switching0
number of NO contacts delayed switching0
number of CO contacts delayed switching1
operating frequency with 3RT2 contactor maximum5 000 1/h
Main circuit
number of poles for main current circuit1
operating voltage rated value24 ... 24 V
ampacity of the output relay at AC-15
● at 250 V at 50/60 Hz3 A
● at 400 V at 50/60 Hz3 A
ampacity of the output relay at DC-13
● at 24 V1 A
● at 125 V0.2 A
● at 250 V0.1 A
ampacity of the semiconductor output in SIO mode200 mA
operational current at 17 V minimum0.01 A
continuous current of the DIAZED fuse link of the output relay4 A
Electromagnetic compatibility
conducted interference
● due to burst according to IEC 61000-4-42 kV
● due to conductor-earth surge according to IEC 61000-4-52 kV
● due to conductor-conductor surge according to IEC 61000-4-51 kV
field-based interference according to IEC 61000-4-310 V/m
electrostatic discharge according to IEC 61000-4-26 kV contact discharge / 8 kV air discharge
Galvanic isolation
design of the electrical isolationProtective separation
galvanic isolation
● between input and outputYes
● between the voltage supply and other circuitsYes
Connections/ Terminals
product component removable terminal for main circuitYes
product component removable terminal for auxiliary and control circuitYes
type of electrical connection
● for main current circuitscrew-type terminals
● for auxiliary and control circuitscrew-type terminals
type of connectable conductor cross-sections
● solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
● finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
● at AWG cables solid2x (20 ... 14)
● at AWG cables stranded2x (20 ... 14)
connectable conductor cross-section
● solid0.5 ... 4 mm²
● finely stranded with core end processing0.5 ... 2.5 mm²
AWG number as coded connectable conductor cross section
● solid20 ... 14
● stranded20 ... 14
tightening torque with screw-type terminals0.8 ... 1.2 N·m
Installation/ mounting/ dimensions
mounting positionany
fastening methodsnap-on mounting
height92 mm
width22.5 mm
depth91 mm
required spacing
● with side-by-side mounting
— forwards0 mm
— backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
● for grounded parts
— forwards0 mm
— backwards0 mm
— upwards0 mm
— at the side0 mm
— downwards0 mm
● for live parts
— forwards0 mm
— backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
Ambient conditions
installation altitude at height above sea level maximum2 000 m
ambient temperature
● during operation-25 ... +60 °C
● during storage-40 ... +85 °C
● during transport-40 ... +85 °C
Certificates/ approvals

Downloads and manuals

General Product ApprovalEMC

CCC

Confirmation

Manufacturer Declaration

UL

EAC

RCM

Declaration of ConformityTest CertificatesMarine / ShippingotherRailway

EC/EU-Declaration of Conformity

Type Test Certificates/Test Report

Special Test Certificate

DNV-GL

Confirmation

Vibration and Shock

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Cax online generator
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
Characteristic: Derating
last modified:1/8/2021
Date
5/3/2022
Subject to change without notice
© Copyright Siemens 2022


Additional data

Product
Article Number (Market Facing Number)3UG4822-1AA40
Product DescriptionDigital monitoring relay Current monitoring, 22.5 mm for IO-Link 0.05...10.0 A AC/DC Overcurrent and undercurrent Transformer scaling factor Hysteresis 0.01 to 5.0 A ON-delay time Tripping delay time 1 change-over contact, screw terminal
Product familyCurrent monitoring
Product Lifecycle (PLM)PM300:Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group41H / 41H
Surcharge for Raw MaterialsNone
Metal FactorLAO-----
Delivery information
Export Control RegulationsAL : N / ECCN : N
Standard lead time ex-works2 Day/Days
Net Weight (kg)0,147 Kg
Packaging Dimension37,00 x 100,00 x 111,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4011209895805
UPC040892871807
Commodity Code85364900
LKZ_FDB/ CatalogIDCC-IC10
Product Group5885
Group CodeR711
Country of originCzech Republic
Compliance with the substance restrictions according to RoHS directiveSince: 01.05.2012
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead monoxide (lead oxide)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Dicyclohexyl phthalate (DCHP)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Tris(2-chloroethyl) phosphate (TCEP)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-37-18-02
eClass7.127-37-18-02
eClass827-37-18-02
eClass927-37-18-02
eClass9.127-37-18-02
ETIM5EC001440
ETIM6EC001440
ETIM7EC001440
ETIM8EC001440
IDEA44727
UNSPSC1439-12-15-21
UNSPSC1539-12-15-21

ETIM data

ETIM: EC001440 - Current monitoring relay

Value Unit
External current transformer (EF001923) -
Type of electric connection (EF003961) Screw connection
With detachable clamps (EF003340) true
Single-phase under current possible (EF003405) true
Three-phase under current possible (EF003406) false
Single-phase over current possible (EF003407) true
Three-phase over current possible (EF003408) false
Single-phase hysteresis possible (EF003394) false
Three-phase hysteresis possible (EF003395) false
Contains function DC-voltage under current (EF003409) true
Contains function DC-voltage over current (EF003410) true
Function DC-current hysteresis (EF003411) true
Rated control supply voltage Us at AC 50HZ (EF003978) ['-', '-']V
Rated control supply voltage Us at AC 60HZ (EF003979) ['-', '-']V
Rated control supply voltage Us at DC (EF003980) ['18', '30']V
Voltage type for actuating (EF008242) DC
Current measurement range (EF000417) ['0.05', '750.0']A
Min. adjustable delay-on energization time (EF008190) 0s
Max. permitted delay-on energization time (EF008189) 999.9s
Min. adjustable off-delay time (EF008192) 0s
Max. permitted off-delay time (EF008191) 999.9s
Number of contacts as normally closed contact (EF008255) 0
Number of contacts as normally open contact (EF008256) 0
Number of contacts as change-over contact (EF008257) 1
Width (EF000008) 22.5mm
Height (EF000040) 92.0mm
Depth (EF000049) 91.0mm


Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.