3RU1146-4LD1 SIEMENS OVERLOAD RELAY, 70...90 A, 1NO+1NC, SIZE S3, MAIN CUR.: SCREW CONNECTION AUX. CUR..: C.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

3RU1146-4LD1 SIEMENS OVERLOAD RELAY, 70...90 A, 1NO+1NC, SIZE S3, MAIN CUR.: SCREW CONNECTION AUX. CUR..: C..

3RU1146-4LD1

SIEMENS

Overload relay 70...90 A For motor protection Size S3, Class 10 Stand-alone installation Main circuit: Screw terminal Auxiliary circuit: Spring-type terminal Manual-Automatic-Reset !!! Phased-out product !!! Successor is SIRIUS 3RU2 Preferred successor type is >>3RU2146-4LD1<<

More details


CONTROL AND CONTACTORS > Thermal relays

Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



product brand name SIRIUS
Product designation thermal overload relay
General technical data:
Size of overload relay S3
Size of contactor can be combined company-specific S3
Power loss [W] total typical 16.5 W
Insulation voltage with degree of pollution 3 rated value 1 000 V
Surge voltage resistance rated value 8 kV
Protection class IP
● on the front IP20
Shock resistance 8g / 10 ms
Type of protection DMT 98 ATEX G 001
Protection against electrical shock finger-safe
Equipment marking acc. to DIN EN 81346-2 F
Ambient conditions:
Installation altitude at height above sea level maximum 2 000 m
Ambient temperature
● during operation -20 ... +70 °C
● during storage -55 ... +80 °C
● during transport -55 ... +80 °C
Relative humidity during operation 100 %
Main circuit:
Number of poles for main current circuit 3
Adjustable pick-up value current of the current-dependent overload release 70 ... 90 A
Operating voltage
● at AC-3 rated value maximum 1 000 V
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts 1
Number of NO contacts
● for auxiliary contacts 1
Number of CO contacts
● for auxiliary contacts 0
Operating current of auxiliary contacts at AC-15
● at 24 V 3 A
● at 110 V 3 A
● at 120 V 3 A
● at 125 V 3 A
● at 230 V 2 A
● at 400 V 1 A
Operating current of auxiliary contacts at DC-13
● at 24 V 1 A
● at 110 V 0.22 A
● at 125 V 0.22 A
● at 220 V 0.11 A
Protective and monitoring functions:
Trip class CLASS 10
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required gG: 250 A
— with type of assignment 2 required gG: 160 A
● for short-circuit protection of the auxiliary switch required fuse gL/gG: 6 A, quick: 10 A
Installation/ mounting/ dimensions:
Mounting position with vertical mounting surface +/-135° rotatable, with vertical mounting surface +/- 45° tiltable to the front and back
Mounting type stand-alone installation
Height 120 mm
Width 70 mm
Depth 140 mm
Required spacing
● with side-by-side mounting
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 0 mm
● for grounded parts
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— at the side 6 mm
— downwards 0 mm
● for live parts
— forwards 0 mm
— Backwards 0 mm
— upwards 0 mm
— downwards 0 mm
— at the side 6 mm
Connections/Terminals:
Product function
● removable terminal for auxiliary and control circuit No
Type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control current circuit Cage Clamp terminals
Type of connectable conductor cross-sections
● for main contacts
— solid 2x (2.5 ... 16 mm²)
— stranded 2x (10 ... 50 mm²), 10 ... 70 mm²
— finely stranded with core end processing 2x (2.5 ... 35 mm²), 2.5 ... 50 mm²
● at AWG conductors for main contacts 2x (10 ... 1/0), 1x (10 ... 2/0)
Type of connectable conductor cross-sections
● for auxiliary contacts
— solid 2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²)
— finely stranded without core end processing 2x (0.5 ... 1.5 mm²)
● at AWG conductors for auxiliary contacts 2x (20 ... 14)

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.