Power contactor, AC-3 25 A, 11 kW / 400 V 2 NO + 2 NC 220 V DC, 50 Hz 4-pole size S0 screw terminals 1 NO + 1 NC integrated |
product brand name | SIRIUS |
product designation | contactor |
product type designation | 3RT25 |
General technical data |
size of contactor | S0 |
product extension | |
● function module for communication | No |
● auxiliary switch | Yes |
insulation voltage | |
● of main circuit with degree of pollution 3 rated value | 690 V |
● of auxiliary circuit with degree of pollution 3 rated value | 690 V |
surge voltage resistance | |
● of main circuit rated value | 6 kV |
● of auxiliary circuit rated value | 6 kV |
maximum permissible voltage for safe isolation between coil and main contacts according to EN 60947-1 | 400 V |
shock resistance at rectangular impulse | |
● at DC | 10g / 5 ms, 7,5g / 10 ms |
shock resistance with sine pulse | |
● at DC | 15g / 5 ms, 10g / 10 ms |
mechanical service life (switching cycles) | |
● of contactor typical | 10 000 000 |
● of the contactor with added electronically optimized auxiliary switch block typical | 5 000 000 |
● of the contactor with added auxiliary switch block typical | 10 000 000 |
reference code according to IEC 81346-2 | Q |
Substance Prohibitance (Date) | 10/01/2009 |
Ambient conditions |
installation altitude at height above sea level maximum | 2 000 m |
ambient temperature | |
● during operation | -25 ... +60 °C |
● during storage | -55 ... +80 °C |
relative humidity minimum | 10 % |
relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % |
Main circuit |
number of poles for main current circuit | 4 |
number of NO contacts for main contacts | 2 |
number of NC contacts for main contacts | 2 |
operational current | |
● at AC-1 up to 690 V | |
— at ambient temperature 40 °C rated value | 40 A |
— at ambient temperature 60 °C rated value | 35 A |
● at AC-2 at AC-3 at 400 V | |
— per NO contact rated value | 25 A |
— per NC contact rated value | 20 A |
minimum cross-section in main circuit at maximum AC-1 rated value | 10 mm² |
operational current | |
● at 1 current path at DC-1 | |
— at 24 V rated value | 35 A |
— at 110 V rated value | 4.5 A |
— at 220 V rated value | 1 A |
— at 440 V rated value | 0.4 A |
● with 2 current paths in series at DC-1 | |
— at 24 V rated value | 35 A |
— at 110 V rated value | 35 A |
— at 220 V rated value | 5 A |
— at 440 V rated value | 1 A |
● at 1 current path at DC-3 at DC-5 | |
— at 24 V per NC contact rated value | 20 A |
— at 24 V per NO contact rated value | 20 A |
— at 110 V per NC contact rated value | 1.25 A |
— at 110 V per NO contact rated value | 2.5 A |
— at 220 V per NC contact rated value | 0.5 A |
— at 220 V per NO contact rated value | 1 A |
— at 440 V per NC contact rated value | 0.045 A |
— at 440 V per NO contact rated value | 0.09 A |
● with 2 current paths in series at DC-3 at DC-5 | |
— at 24 V per NC contact rated value | 35 A |
— at 24 V per NO contact rated value | 35 A |
— at 110 V per NC contact rated value | 7.5 A |
— at 110 V per NO contact rated value | 15 A |
— at 220 V per NC contact rated value | 1.5 A |
— at 220 V per NO contact rated value | 3 A |
— at 440 V per NC contact rated value | 0.135 A |
— at 440 V per NO contact rated value | 0.27 A |
operating power at AC-2 at AC-3 | |
● at 230 V per NC contact rated value | 5.5 kW |
● at 230 V per NO contact rated value | 5.5 kW |
● at 400 V per NC contact rated value | 7.5 kW |
● at 400 V per NO contact rated value | 11 kW |
short-time withstand current in cold operating state up to 40 °C | |
● limited to 1 s switching at zero current maximum | 200 A; Use minimum cross-section acc. to AC-1 rated value |
● limited to 5 s switching at zero current maximum | 200 A; Use minimum cross-section acc. to AC-1 rated value |
● limited to 10 s switching at zero current maximum | 200 A; Use minimum cross-section acc. to AC-1 rated value |
● limited to 30 s switching at zero current maximum | 128 A; Use minimum cross-section acc. to AC-1 rated value |
● limited to 60 s switching at zero current maximum | 106 A; Use minimum cross-section acc. to AC-1 rated value |
power loss [W] at AC-3 at 400 V for rated value of the operational current per conductor | 1.6 W |
no-load switching frequency | |
● at AC | 5 000 1/h |
● at DC | 1 500 1/h |
operating frequency | |
● at AC-1 maximum | 1 000 1/h |
Control circuit/ Control |
type of voltage of the control supply voltage | DC |
control supply voltage at DC | |
● rated value | 220 V |
operating range factor control supply voltage rated value of magnet coil at DC | |
● initial value | 0.8 |
● full-scale value | 1.1 |
closing power of magnet coil at DC | 5.9 W |
holding power of magnet coil at DC | 5.9 W |
closing delay | |
● at DC | 50 ... 170 ms |
opening delay | |
● at DC | 15 ... 18 ms |
arcing time | 10 ... 10 ms |
Auxiliary circuit |
number of NC contacts for auxiliary contacts instantaneous contact | 1 |
number of NO contacts for auxiliary contacts instantaneous contact | 1 |
operational current at AC-12 maximum | 10 A |
operational current at AC-15 | |
● at 230 V rated value | 10 A |
● at 400 V rated value | 3 A |
● at 500 V rated value | 2 A |
● at 690 V rated value | 1 A |
operational current at DC-12 | |
● at 24 V rated value | 10 A |
● at 48 V rated value | 6 A |
● at 60 V rated value | 6 A |
● at 110 V rated value | 3 A |
● at 125 V rated value | 2 A |
● at 220 V rated value | 1 A |
● at 600 V rated value | 0.15 A |
operational current at DC-13 | |
● at 24 V rated value | 10 A |
● at 48 V rated value | 2 A |
● at 60 V rated value | 2 A |
● at 110 V rated value | 1 A |
● at 125 V rated value | 0.9 A |
● at 220 V rated value | 0.3 A |
● at 600 V rated value | 0.1 A |
contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
UL/CSA ratings |
yielded mechanical performance [hp] | |
● for single-phase AC motor at 230 V rated value | 3 hp |
● for 3-phase AC motor at 460/480 V rated value | 15 hp |
contact rating of auxiliary contacts according to UL | A600 / Q600 |
Short-circuit protection |
design of the fuse link | |
● for short-circuit protection of the main circuit | |
— with type of coordination 1 required | gG: 63 A (690 V, 100 kA) |
— with type of assignment 2 required | gG: 35 A (690 V, 50 kA) |
● for short-circuit protection of the auxiliary switch required | fuse gG: 10 A |
Installation/ mounting/ dimensions |
mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
fastening method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
● side-by-side mounting | Yes |
height | 85 mm |
width | 61 mm |
depth | 107 mm |
required spacing | |
● with side-by-side mounting | |
— forwards | 0 mm |
— backwards | 0 mm |
— upwards | 0 mm |
— downwards | 0 mm |
— at the side | 0 mm |
● for grounded parts | |
— forwards | 0 mm |
— backwards | 0 mm |
— upwards | 0 mm |
— at the side | 6 mm |
— downwards | 0 mm |
● for live parts | |
— forwards | 0 mm |
— backwards | 0 mm |
— upwards | 0 mm |
— downwards | 0 mm |
— at the side | 6 mm |
Connections/ Terminals |
type of electrical connection | |
● for main current circuit | screw-type terminals |
● for auxiliary and control circuit | screw-type terminals |
● at contactor for auxiliary contacts | Screw-type terminals |
● of magnet coil | Screw-type terminals |
type of connectable conductor cross-sections | |
● for main contacts | |
— solid | 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²) |
— solid or stranded | 2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²) |
— finely stranded with core end processing | 2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm² |
● at AWG cables for main contacts | 2x (16 ... 12), 2x (14 ... 8) |
type of connectable conductor cross-sections | |
● for auxiliary contacts | |
— solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
— solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
— finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
● at AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) |
AWG number as coded connectable conductor cross section for main contacts | 16 ... 8 |
Safety related data |
product function | |
● mirror contact according to IEC 60947-4-1 | Yes |
● positively driven operation according to IEC 60947-5-1 | No |
protection class IP on the front according to IEC 60529 | IP20 |
touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
Certificates/ approvals |
Downloads and manuals |
|
Further information |
Information- and Downloadcenter (Catalogs, Brochures,…) |
Industry Mall (Online ordering system) |
Cax online generator |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) |
Characteristic: Tripping characteristics, I²t, Let-through current |
Further characteristics (e.g. electrical endurance, switching frequency) |
|
|
|
last modified: | 12/1/2021 |