3RT1517-1AD00 SIEMENS CONTACTOR, AC-3 5.5KW/400 V, AC-1 22 A, AC 42 V, 50 HZ, 4-POLE, 2 NO + 2 NC, SIZE S00.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

3RT1517-1AD00 SIEMENS CONTACTOR, AC-3 5.5KW/400 V, AC-1 22 A, AC 42 V, 50 HZ, 4-POLE, 2 NO + 2 NC, SIZE S00..

3RT1517-1AD00

SIEMENS

Contactor, AC-3, 5.5 kW / 400 V AC-1, 22 A, 42 V AC, 50/60 Hz 4-pole, 2 NO + 2 NC, Size S00 Screw terminal !!! Phased-out product !!! Successor is SIRIUS 3RT2

More details


CONTROL AND CONTACTORS > Contactors for switching motors

* Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



product brand nameSIRIUS
Product designationpower contactor
General technical data:
Size of contactorS00
Insulation voltage
● rated value690 V
Degree of pollution3
Protection class IP
● on the frontIP20
Mechanical service life (switching cycles)
● of contactor typical30 000 000
● of the contactor with added electronics-compatible auxiliary switch block typical5 000 000
● of the contactor with added auxiliary switch block typical10 000 000
Ambient conditions:
Installation altitude at height above sea level maximum2 000 m
Ambient temperature
● during operation-25 ... +60 °C
● during storage-55 ... +80 °C
Main circuit:
Number of NO contacts for main contacts2
Number of NC contacts for main contacts2
Operating current
● at AC-1
— up to 690 V at ambient temperature 40 °C rated value22 A
— up to 690 V at ambient temperature 60 °C rated value20 A
● at AC-2 at AC-3 at 400 V
— per NO contact rated value12 A
— per NC contact rated value12 A
Connectable conductor cross-section in main circuit at AC-1
● at 60 °C minimum permissible2.5 mm²
● at 40 °C minimum permissible2.5 mm²
Operating current
● at 1 current path at DC-1
— at 24 V rated value20 A
— at 110 V rated value2.1 A
— at 220 V rated value0.8 A
— at 440 V rated value0.6 A
● with 2 current paths in series at DC-1
— at 24 V rated value20 A
— at 110 V rated value12 A
— at 220 V rated value1.6 A
— at 440 V rated value0.8 A
Operating current
● at 1 current path at DC-3 at DC-5
— at 24 V per NC contact rated value20 A
— at 24 V per NO contact rated value20 A
— at 110 V per NC contact rated value0.075 A
— at 110 V per NO contact rated value0.15 A
— at 220 V per NC contact rated value0.375 A
— at 220 V per NO contact rated value0.75 A
● with 2 current paths in series at DC-3 at DC-5
— at 110 V per NC contact rated value0.175 A
— at 110 V per NO contact rated value0.35 A
— at 24 V per NC contact rated value20 A
— at 24 V per NO contact rated value20 A
Operating power
● at AC-1
— at 230 V rated value7.5 kW
— at 400 V rated value13 kW
● at AC-2 at AC-3
— at 230 V per NC contact rated value3 kW
— at 230 V per NO contact rated value3 kW
— at 400 V per NC contact rated value5.5 kW
— at 400 V per NO contact rated value5.5 kW
Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor0.7 W
Operating frequency
● at AC-1 maximum1 000 1/h
Control circuit/ Control:
Type of voltage of the control supply voltageAC
Control supply voltage at AC
● at 50 Hz rated value42 V
● at 60 Hz rated value42 V
Operating range factor control supply voltage rated value of magnet coil at AC
● at 50 Hz0.8 ... 1.1
● at 60 Hz0.85 ... 1.1
Apparent pick-up power of magnet coil at AC27 V·A
● at 50 Hz27 V·A
Inductive power factor with closing power of the coil0.8
● at 50 Hz0.8
Apparent holding power of magnet coil at AC4.4 V·A
● at 50 Hz4.4 V·A
Inductive power factor with the holding power of the coil0.27
● at 60 Hz0.27
Closing delay
● at AC8 ... 35 ms
● at DC25 ... 100 ms
Opening delay
● at AC4 ... 30 ms
● at DC7 ... 10 ms
Arcing time10 ... 15 ms
Control version of the switch operating mechanismconventional
Residual current of the electronics for control with signal <0>
● at AC at 230 V maximum permissible0.003 A
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts
— instantaneous contact0
Number of NO contacts
● for auxiliary contacts
— instantaneous contact0
Operating current at AC-12 maximum10 A
Operating current at AC-15
● at 230 V rated value6 A
● at 400 V rated value3 A
Operating current at DC-12
● at 60 V rated value6 A
● at 110 V rated value3 A
● at 220 V rated value1 A
Operating current at DC-13
● at 24 V rated value10 A
● at 60 V rated value2 A
● at 110 V rated value1 A
● at 220 V rated value0.3 A
Contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 requiredfuse gL/gG: 35 A
— with type of assignment 2 requiredfuse gL/gG: 20 A
● for short-circuit protection of the auxiliary switch requiredfuse gL/gG: 10 A
Installation/ mounting/ dimensions:
Mounting positionwith vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back
Mounting typescrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
● Side-by-side mountingYes
Height57.5 mm
Width45 mm
Depth72 mm
Required spacing
● for grounded parts
— at the side6 mm
Connections/Terminals:
Type of electrical connection
● for main current circuitscrew-type terminals
● for auxiliary and control current circuitscrew-type terminals
Type of connectable conductor cross-sections
● for main contacts
— solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
— single or multi-stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for main contacts2x (20 ... 16), 2x (18 ... 14), 1x 12
Type of connectable conductor cross-sections
● for auxiliary contacts
— solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
— single or multi-stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts2x (20 ... 16), 2x (18 ... 14), 1x 12
Safety related data:
Failure rate [FIT]
● with low demand rate acc. to SN 31920100 FIT

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.