Product successfully added to your shopping cart
VAL-MS-T1/T2 48/12.5/2+0/1U/FM
2907042
PHOENIX_CONTACT
1
Lightning/surge arrester type 1/2
Trabtech (TT)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2907042 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
GTIN | 4055626248974 |
Weight per Piece (excluding packing) | 251.160 g |
Custom tariff number | 85363030 |
Country of origin | DE (Germany) |
Degree of protection | IP20 (only when all terminal points are used) |
---|---|
Ambient temperature (operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
IEC test classification | I / II |
---|---|
T1 / T2 | |
I | |
EN type | T1 / T2 |
IEC power supply system | TN-S |
Mode of protection | L-PE |
N-PE | |
Mounting type | Panel mount |
Color | gray |
Housing material | PA 6.6 |
PBT | |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Surge protection fault message | Optical, remote indicator contact |
Note | For installation into a touch protected cabinet. For applications with UC> 500 V distances at the side and distances at the connection area must be minimum of 5 mm between different active parts including earthed parts. |
---|
Nominal voltage UN | 60 V AC ±10 % (TN-S) |
---|---|
-48 V DC ±10 % (RRH) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 75 V AC |
100 V DC | |
Rated load current IL | 80 A |
Residual current IPE | ≤ 0.6 mA |
Standby power consumption PC | ≤ 45 mVA |
Nominal discharge current In(8/20) µs | 12.5 kA |
Maximum discharge current Imax(8/20) µs | 30 kA |
Impulse discharge current (10/350) µs, charge | 6.25 As |
Impulse discharge current (10/350) µs, specific energy | 39 kJ/Ω |
Impulse discharge current (10/350) µs, peak value limp | 12.5 kA |
Total discharge current Itotal(8/20) µs | 50 kA |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up | ≤ 0.4 kV |
Residual voltage Ures | ≤ 0.4 kV (at In) |
≤ 0.35 kV (at 10 kA) | |
≤ 0.3 kV (at 5 kA) | |
≤ 0.275 kV (at 4 kA) | |
≤ 0.25 kV (at 3 kA) | |
TOV behavior at UT | 100 V AC (5 s / withstand mode) |
130 V DC (5 s / withstand mode) | |
Response time tA | ≤ 25 ns |
Max. backup fuse with V-type through wiring | 80 A AC (gG - 16 mm²) |
Max. backup fuse with branch wiring | 160 A AC (gG) |
Switching function | PDT contact |
---|---|
Operating voltage | 5 V AC ... 250 V AC |
125 V AC (UL) | |
125 V DC (200 mA DC) | |
Operating current | 5 mA AC ... 1.5 A |
1 A (UL) | |
1 A (30 V DC) | |
Connection method | Push-in spring connection |
Stripping length | 6 mm |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 0.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 0.5 mm² |
Conductor cross section solid min. | 0.14 mm² |
Conductor cross section solid max. | 0.5 mm² |
Conductor cross section solid | 0.14 mm² ... 0.5 mm² |
Conductor cross section AWG | 24 ... 20 (UL) |
Connection method | Screw connection |
---|---|
Screw thread | M5 |
Tightening torque | 2.5 Nm ... 3 Nm |
22 lbf-in. ... 26.5 lbf-in. (UL) | |
Stripping length | 16 mm |
Conductor cross section flexible min. | 1.5 mm² |
Conductor cross section flexible max. | 25 mm² |
Conductor cross section solid min. | 1.5 mm² |
Conductor cross section solid max. | 35 mm² |
Conductor cross section flexible | 1.5 mm² ... 25 mm² |
Conductor cross section solid | 1.5 mm² ... 35 mm² |
Conductor cross section AWG | 15 ... 2 |
10 ... 2 (UL) |
SPD Type | 1CA |
---|---|
Maximum continuous operating voltage MCOV (L-N) | 75 V AC |
100 V DC | |
Nominal voltage | 60 V DC |
Mode of protection | N-G |
L-G | |
(L+) - (L-) | |
(L+) - G | |
(L-) - G |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.