Product successfully added to your shopping cart
TTC-6P-2X1-F-48DC-UT-I
2908208
PHOENIX_CONTACT
1
Surge protection, consisting of protective plug and base element, with integrated status indicator for two signal wires with common reference potential, e.g., Digital IN/OUT. Indirect grounding via gas-filled surge arrester.
Trabtech (TT)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2908208 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 129 (C-4-2019) |
GTIN | 4055626282916 |
Weight per Piece (excluding packing) | 40.000 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | -40 °C ... 85 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % |
Altitude | ≤ 4000 m (amsl (above mean sea level)) |
Degree of protection | IP20 |
Housing material | PBT |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | traffic grey A RAL 7042 |
light grey RAL 7035 | |
Mounting type | DIN rail: TH 35 - 7.5 mm |
Type | DIN rail module, two-section, divisible |
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 48 V DC |
Maximum continuous voltage UC | 53 V DC |
30 V AC | |
Rated current | 220 mA DC (75 °C) |
600 mA AC (56 °C) | |
Operating effective current ICat UC | ≤ 5 µA |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Nominal discharge current In(8/20) µs (line-signal ground) | 5 kA |
Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
Pulse discharge current Iimp(10/350) µs (line-signalground) | 0.5 kA |
Total discharge current Itotal(8/20) µs | 10 kA |
Voltage protection level Up(line-earth) | ≤ 750 V (C1 - 1 kV/500 A) |
≤ 750 V (C2 - 10 kV / 5 kA) | |
≤ 800 V (C3 - 25 A) | |
≤ 1.1 kV (C3 - 50 A) | |
Voltage protection level Up(line-signalground) | ≤ 110 V (C1 - 1 kV/500 A) |
≤ 150 V (C2 - 10 kV / 5 kA) | |
≤ 80 V (C3 - 25 A) | |
≤ 90 V (C3 - 50 A) | |
Voltage protection level Upstatic (line-earth) | ≤ 750 V (C1 - 1 kV/500 A) |
≤ 750 V (C2 - 10 kV / 5 kA) | |
Voltage protection level Upstatic (line-signalground) | ≤ 105 V (C1 - 1 kV/500 A) |
≤ 150 V (C2 - 10 kV / 5 kA) | |
Response time tA(line-signalground) | ≤ 1 ns |
Response time tA(line-earth) | ≤ 100 ns |
Input attenuation aE, asym. | typ. 0.3 dB (≤ 480 kHz / 150 Ω) |
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 1.7 MHz |
Capacity (line-signalground) | typ. 5 pF |
Capacity (line-earth) | typ. 1.2 nF |
Resistance per path | 1.65 Ω ±20 % |
Max. required back-up fuse | 160 mA DC (FF) |
630 mA AC (FF) | |
Impulse durability (line-earth) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA | |
C3 - 57 A | |
D1 - 500 A | |
Impulse durability (line-signalground) | C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA | |
C3 - 57 A | |
D1 - 500 A | |
Pulse reset time (line-earth) | ≤ 30 ms |
Pulse reset time (line-signalground) | ≤ 600 ms |
Connection method | Screw connection |
---|---|
Screw thread | M3 |
Tightening torque | 0.5 Nm ... 0.6 Nm |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section solid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
---|---|
EN 61643-21 2001 + A1:2009 + A2:2013 |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 4.0 | 27140201 |
---|---|
eCl@ss 4.1 | 27130801 |
eCl@ss 5.0 | 27130801 |
eCl@ss 5.1 | 27130801 |
eCl@ss 6.0 | 27130800 |
eCl@ss 7.0 | 27130807 |
eCl@ss 8.0 | 27130807 |
eCl@ss 9.0 | 27130807 |
UNSPSC 6.01 | 30212010 |
---|---|
UNSPSC 7.0901 | 39121610 |
UNSPSC 11 | 39121610 |
UNSPSC 12.01 | 39121610 |
UNSPSC 13.2 | 39121620 |
UNSPSC 18.0 | 39121620 |
UNSPSC 19.0 | 39121620 |
UNSPSC 20.0 | 39121620 |
UNSPSC 21.0 | 39121620 |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.