TT-SLKK5-F/110AC 2765602 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

TT-SLKK5-F/110AC 2765602 PHOENIX CONTACT Surge protection device

TT-SLKK5-F/110AC

2765602

PHOENIX_CONTACT

Surge protection device

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2765602
Packing unit50 pc
NoteMade to Order (non-returnable)
Catalog pagePage 123 (C-6-2013)
GTIN4017918066468
Weight per Piece (excluding packing)18.100 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height66.5 mm
Width6.2 mm
Depth69.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20 (with end cover)

General

Housing materialPA 6.6
Flammability rating according to UL 94V-2
Colorjet black RAL 9005
Standards for cearances and creepage distancesVDE 0110-1
Mounting typeDIN rail: 35 mm
TypeSingle-level terminal block – separate PE connection
Number of positions1
Direction of actionLine-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN110 V AC
30 V DC
Maximum continuous voltage UC30 V DC
110 V AC
Rated current2 A AC
300 mA DC
Operating effective current ICat UC≤ 2 µA
Residual current IPE≤ 1.5 µA
Nominal discharge current In(8/20) µs (line-earth)5 kA
Total discharge current Itotal(8/20) µs5 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)5 kA
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 650 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 650 V
Response time tA(line-earth)≤ 100 ns
Capacity (line-earth)typ. 1 pF
Surge protection fault messagenone
Max. required back-up fuse2 A AC (F)
315 mA DC (F)
Alternating current carrying capacity (line-earth)2.5 A - 1 s

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsIEC 61643-21 2000
EN 61643-21 2001

Environmental Product Compliance

REACh SVHC4-Nonylphenol, ethoxylated
Lead 7439-92-1

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.