VAL-US 240 ST 2800740 PHOENIX CONTACT Surge protection connector type 2 with high-capacity varistor for VAL-.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-US 240 ST 2800740 PHOENIX CONTACT Surge protection connector type 2 with high-capacity varistor for VAL-..

VAL-US 240 ST

2800740

PHOENIX_CONTACT

10

Available

Ship on today

Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 240 V AC

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
10+$44.75
20+$43.68
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g
Vibration (operation)5g

General

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012
IEC test classificationII
T2
EN typeT2
SPD designVoltage-limiting type
Mode of protectionL-PEN
L-N
Mounting typeOn base element
Colorblack
Housing materialPA 6.6
Pollution degree2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
Nominal frequency fN60 Hz (50 Hz)
Maximum continuous voltage UC275 V AC
Residual current IPE≤ 0.45 mA
Standby power consumption PC≤ 120 mVA
Nominal discharge current In (8/20) µs20 kA
Maximum discharge current Imax (8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.35 kV
Residual voltage Ures≤ 1.35 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
TOV behavior at UT335 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A AC (gG)

Connection data

Connection methodVALVETRAB plug-in system

UL specifications

SPD Type4 (for Type 2 applications)
Maximum continuous operating voltage MCOV (L-N)275 V AC
Nom. voltage240 V AC
Mode of protectionL-N
Power distribution system1
Nominal frequency50/60 Hz
Voltage protection rating VPR (L-N)0.9 kV
Nominal discharge current In (L-N)20 kA

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2800740-VAL-US 240 ST English 110 Kbytes PHOENIX CONTACT-2800740-VAL-US 240 ST

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.