VAL-MS-T1/T2 335/12.5/1+1-FM 2800186 PHOENIX CONTACT Lightning/surge arrester type 1/2 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS-T1/T2 335/12.5/1+1-FM 2800186 PHOENIX CONTACT Lightning/surge arrester type 1/2

VAL-MS-T1/T2 335/12.5/1+1-FM

2800186

PHOENIX_CONTACT

Lightning/surge arrester type 1/2

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $299.36
Unit price: $299.36

Quantity Price
1+$299.36
2+$285.92
3+$285.92
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2800186
Packing unit1 pc
Catalog pagePage 37 (C-4-2017)
GTIN4046356518574
Weight per Piece (excluding packing)329.700 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height96.8 mm
Width35.6 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationI / II
T1 / T2
T1
EN typeT1 / T2
T1
IEC power supply systemTT
TN-S
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240 V AC (TN-S)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)335 V AC
Maximum continuous operating voltage UC(L-PE)335 V AC
Maximum continuous voltage UC(N-PE)264 V AC
Rated load current IL80 A
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 270 mVA
Nominal discharge current In(8/20) µs (L-N)12.5 kA
Nominal discharge current In(8/20) µs (L-PE)12.5 kA
Nominal discharge current In(8/20) µs (N-PE)50 kA
Maximum discharge current Imax(8/20) µs50 kA
Impulse discharge current (10/350) µs (L-N), charge6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy39 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp12.5 kA
Impulse discharge current (10/350) µs (L-PE), charge6.25 As
Impulse discharge current (10/350) µs (L-PE), specific energy39 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge25 As
Impulse discharge current (10/350) µs (N-PE), specific energy625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp50 kA
Total discharge current Itotal(8/20) µs50 kA
Total discharge current Itotal(10/350) µs25 kA
Follow current interrupt rating Ifi(N-PE)100 A
Short-circuit current rating ISCCR25 kA
Voltage protection level Up(L-N)≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20 µs)
Voltage protection level Up(L-PE)≤ 2 kV
Voltage protection level Up(N-PE)≤ 1.7 kV
Residual voltage Ures(L-N)≤ 1.2 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Residual voltage Ures(L-PE)≤ 2 kV (at In)
≤ 1.5 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Residual voltage Ures(N-PE)≤ 0.6 kV (at In)
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.4 kV (at 3 kA)
TOV behavior at UT(L-N)415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Max. backup fuse with V-type through wiring80 A (gG - 16 mm²)
Max. backup fuse with branch wiring160 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 1.5 A AC
1 A DC
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)335 V AC
Maximum continuous operating voltage MCOV (L-G)335 V AC
Maximum continuous operating voltage MCOV (N-G)264 V AC
Nom. voltage240 V AC
Mode of protectionL-N
L-G
N-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)2630 V
Measured limiting voltage MLV (L-G)3600 V
Measured limiting voltage MLV (N-G)2600 V
Nominal discharge current In(L-N)20 kA
Nominal discharge current In(L-G)20 kA
Nominal discharge current In(N-G)20 kA

UL indicator/remote signaling

Operating voltage125 V AC
Operating current1 A AC
Tightening torque4 lbf-in.
Conductor cross section AWG30 ... 14

UL connection data

Conductor cross section AWG10 ... 2
Tightening torque30 lbf-in.

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.