Product successfully added to your shopping cart
STEP3-PS/1AC/5DC/3/PT/USB-C
1335698
PHOENIX_CONTACT
1
Primary Switching Power Supplies, STEPPOWER, Push-in Connection, Rail Mount, Input: 1-Phase, Output: 5 VDC / 3 A
Primary-switched power supply unit, STEP POWER, Push-in connection, DIN rail or direct mounting, Integrated cable groove with strain relief, input: 1-phase, output: 5 V DC / 3 A, USB-C up to 15 W
Power Supplies (PS)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
AC operation | |
Supply system configuration | Star network (TN, TT, IT (PE)) |
Input voltage range | 100 V AC ... 240 V AC -15 % ... +10 % |
Typical national grid voltage | 120 V AC |
230 V AC | |
Voltage type of supply voltage | AC |
Inrush current | typ. 30 A (25 °C) |
Inrush current integral (I2t) | typ. 0.14 A2s |
Frequency range (fN) | 50 Hz ... 60 Hz ±10 % |
Mains buffering time | typ. 18 ms (120 V AC) |
typ. 80 ms (230 V AC) | |
Current consumption | 0.3 A (100 V AC) |
0.14 A (240 V AC) | |
Switch-on time | typ. 2 s |
Device mains fuse | 1.25 A internal (device protection), slow-blow |
Recommended breaker for input protection | 6 A ... 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 0.25 mA |
DC operation | |
Input voltage range | 110 V DC ... 250 V DC -20 % ... +10 % |
Voltage type of supply voltage | DC |
Current consumption | 0.17 A (110 V DC) |
0.07 A (250 V DC) |
Efficiency | > 81.5 % (120 V AC) |
> 82 % (230 V AC) | |
Nominal output voltage | 5 V DC |
Nominal output current (IN) | 3 A |
Short-circuit-proof | yes |
No-load proof | yes |
Derating | > 50 °C ... 70 °C (2 % / K) |
Crest factor | typ. 3.3 |
typ. 4.2 | |
Output power (PN) | 15 W |
Connection in parallel | yes, for increasing power and redundancy with diode |
Connection in series | yes, for increased output voltage |
Feedback voltage resistance | ≤ 10 V DC |
Protection against overvoltage at the output (OVP) | < 10 V DC |
Residual ripple | typ. 80 mVPP |
Control deviation | < 1.5 % (Static load change 10 % ... 90 %) |
< 5 % (Dynamic load change 10 % ... 90 %, (10 Hz)) | |
< 0.1 % (change in input voltage ±10 %) | |
Rise time | typ. 100 ms (UOut= 10 % ... 90 %) |
Minimum no-load power dissipation | < 0.1 W (120 V AC) |
Maximum no-load power dissipation | < 0.1 W (230 V AC) |
Minimum nominal load power dissipation | < 3.4 W (120 V AC) |
Power loss nominal load max. | < 3.2 W (230 V AC) |
Input | |
Position | 1.x |
Connection technology | |
Position marking | 1.1, 1.2 (L), 1.3, 1.4 (N) |
Conductor connection | |
Connection method | Push-in connection |
rigid | 0.2 mm² ... 2.5 mm² |
1 mm² (recommended) | |
flexible | 0.2 mm² ... 2.5 mm² |
1 mm² (recommended) | |
flexible with ferrule without plastic sleeve | 0.5 mm² ... 1.5 mm² |
1 mm² (recommended) | |
flexible with ferrule with plastic sleeve | 0.2 mm² ... 1 mm² |
1 mm² (recommended) | |
rigid (AWG) | 24 ... 14 (Cu) |
17 (recommended) | |
Stripping length | 10 mm (rigid/flexible) |
13 mm (Ferrule with plastic sleeve) | |
Output | |
Position | 2.x |
Connection technology | |
Position marking | 2.1 (USB-C) |
LED signaling | |
Types of signaling | LED |
Signal threshold | > 0.9 x UN(UN= 5 V DC) (LED lights up green) |
< 0.9 x UN(UN= 5 V DC) (LED off) |
Number of phases | 1.00 |
Insulation voltage input/output | 4 kV AC (type test) |
3.75 kV AC (routine test) |
Product type | Power supply |
Product family | STEP POWER |
MTBF (IEC 61709, SN 29500) | > 2370000 h (25 °C) |
> 1124000 h (40 °C) | |
> 643000 h (50 °C) | |
Environmental protection directive | RoHS Directive 2011/65/EU |
WEEE | |
Reach | |
Insulation characteristics | |
Protection class | II (in closed control cabinet) |
Degree of pollution | 2 |
Item dimensions | |
Width | 18 mm |
Height | 90 mm |
Depth | 61 mm |
55 mm (Device depth (DIN rail mounting)) | |
Dimensional drawing | |
Horizontal pitch | 1 Div. (DIN 43880) |
Installation dimensions | |
Installation distance right/left | 0 mm / 0 mm |
Installation distance top/bottom | 30 mm / 30 mm |
Mounting type | DIN rail or direct mounting |
Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
With protective coating | No |
Flammability rating according to UL 94 | V0 (Housing, terminal blocks, base latches) |
Housing material | Plastic |
Foot latch material | Polyamid |
Housing material | Polycarbonate |
Ambient conditions | |
Degree of protection | IP20 |
Ambient temperature (operation) | -10 °C ... 70 °C (Derating: > 50 °C; 2 %/K) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Ambient temperature (start-up type tested) | -25 °C |
Maximum altitude | ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Shock (operation) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6) |
15 Hz ... 150 Hz, 2.3g, 90 min. |
Overvoltage category | |
EN 61010-1 | II (≤ 4000 m) |
Overvoltage category | |
EN 62477-1 | III (≤ 2000 m) |
Electrical safety | |
Standard designation | Electrical safety |
Standards/specifications | IEC 61010-1 (SELV) |
Protective extra-low voltage | |
Standard designation | Protective extra-low voltage |
Standards/specifications | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Safe isolation | |
Standard designation | Safe isolation |
Standards/specifications | IEC 61558-2-16 |
Low-voltage power supplies, DC output | |
Standard designation | Low-voltage power supplies, DC output |
Standards/specifications | EN 61204-3 |
Safety requirements for electrical equipment for measurement, control, and laboratory use | |
Standard designation | Safety requirements for electrical equipment for measurement, control, and laboratory use |
Standards/specifications | IEC 61010-1 |
Household and similar electrical appliances - Safety | |
Standard designation | Safety of electrical devices for household use and similar purposes |
Standards/specifications | DIN EN 60335-1 |
UL | |
Identification | UL 1310 Class 2 Power Units |
UL | |
Identification | UL/C-UL Listed UL 61010-1 |
UL | |
Identification | UL/C-UL Listed UL 61010-2-201 |
UL | |
Identification | UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
Noise immunity | Immunity in accordance with EN 61000-6-2 (industrial) |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Harmonic currents | |
Standards/regulations | EN 61000-3-2 |
EN 61000-3-2 (Class A) | |
Flicker | |
Standards/regulations | EN 61000-3-3 |
Frequency range | 0 kHz ... 2 kHz |
Electrostatic discharge | |
Standards/regulations | EN 61000-4-2 |
Electrostatic discharge | |
Contact discharge | 6 kV (Test Level 3) |
Discharge in air | 8 kV (Test Level 3) |
Comments | Criterion A |
Electromagnetic HF field | |
Standards/regulations | EN 61000-4-3 |
Electromagnetic HF field | |
Frequency range | 80 MHz ... 1 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 1 GHz ... 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | |
Standards/regulations | EN 61000-4-4 |
Fast transients (burst) | |
Input | asymmetrical 2 kV (Test Level 3) |
Output | asymmetrical 2 kV (Test Level 3) |
Comments | Criterion A |
Surge voltage load (surge) | |
Standards/regulations | EN 61000-4-5 |
Input | symmetrical 2 kV (Test Level 4) |
asymmetrical 4 kV (Test Level 4) | |
Output | symmetrical 1 kV (Test Level 3) |
asymmetrical 2 kV (Test Level 3) | |
Comments | Criterion A |
Conducted interference | |
Standards/regulations | EN 61000-4-6 |
Conducted interference | |
Input/Output | asymmetrical |
Frequency range | 0.15 MHz ... 80 MHz |
Comments | Criterion A |
Voltage | 10 V (Test Level 3) |
Voltage dips | |
Standards/regulations | EN 61000-4-11 |
Voltage | 230 V AC |
Frequency | 50 Hz |
Voltage dip | 70 % |
Number of periods | 25 periods |
Additional text | Class 3 |
Comments | Criterion A |
Voltage dip | 40 % |
Number of periods | 10 periods |
Additional text | Class 3 |
Comments | Criterion A |
Voltage dip | 0 % |
Number of periods | 1 period |
Additional text | Class 3 |
Comments | Criterion A |
Criteria | |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.