ELR W2+1-230AC/500AC-37 2297387 PHOENIX CONTACT Three-phase solid-state reversing contactor with 230 V AC in.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ELR W2+1-230AC/500AC-37 2297387 PHOENIX CONTACT Three-phase solid-state reversing contactor with 230 V AC in..

ELR W2+1-230AC/500AC-37

2297387

PHOENIX_CONTACT

Available

Ship on today

Three-phase solid-state reversing contactor with 230 V AC input, 37 A output current, zero voltage switch, optionally with thermal fuse

More details


Programmable Logic Controllers Plcs

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Solid state relays and power electronics. Relay - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+273,07 €
2+268,84 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Width147.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 70 °C
Ambient temperature (storage/transport)-25 °C ... 70 °C
Degree of protectionIP20

Input data

Input nameDevice supply
Mains frequency50 Hz
60 Hz
Protective circuitSurge protection Varistor
Status displayYellow LED
IndicationRed LED
Input nameControl input right/left
Rated actuating voltage UC230 V AC (Ensure phase balance)
Voltage range with reference to UC0.4 ... 1.1
Rated actuating current IC11.2 mA
Switching threshold48 V AC (“0” signal)
96 V AC (“1” signal)

Output data

Output nameAC output
Nominal output voltage500 V AC
Nominal output voltage range48 V AC ... 575 V AC
Periodic peak reverse voltage1200 V
Rated operating current at AC-5137 A
Rated operating current at AC-53a25 A
Leakage current6 mA
Residual voltage< 1.5 V
Surge current1300 A (t = 10 ms)
Max. load value9000 A2s
Type of protectionRCV circuit
Surge voltage protection> 575 V AC

Connection data, control circuit

Connection nameControl circuits
Connection methodScrew connection
Stripping length8 mm
Screw threadM4
Conductor cross section solid0.5 mm² ... 16 mm²
Conductor cross section flexible0.5 mm² ... 16 mm²
Conductor cross section AWG20 ... 6

General

Test voltage input/output5 kVrms
Switching frequencymax. 1 Hz
Mounting positionVertical (horizontal DIN rail)
Assembly instructionsCan be aligned with spacing = 40 mm
Operating mode100% operating factor
DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178
InsulationBasic insulation
Pollution degree2
Overvoltage categoryIII
DesignationStandards/regulations
Standards/regulationsEN 60947
Reversing frequency≤ 2 Hz

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2297387-ELR W2+1-230AC/500AC-37English120 KbytesPHOENIX CONTACT-2297387-ELR W2+1-230AC/500AC-37