ANUNCIAR
FLT-SEC-P-T1-440/35-P 2905989 PHOENIX CONTACT Type 1 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FLT-SEC-P-T1-440/35-P 2905989 PHOENIX CONTACT Type 1 surge protection plug

FLT-SEC-P-T1-440/35-P

2905989

PHOENIX_CONTACT

Type 1 surge protection plug

Replacement connector for lightning current arresters from the FLASHTRAB SEC PLUS 440 product series, for the L-N and L-PE sections.

More details


Earthing, lightning and surge protection > Accessories/spare parts for surge protection power supply systems

Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $453.05
Unit price: $453.05
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2905989
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 29 (C-4-2017)
GTIN4055626013282
Weight per Piece (excluding packing)241.750 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height46.6 mm
Width35.5 mm
Depth59.4 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

General

IEC test classificationI / II
T1 / T2
EN typeT1 / T2
IEC power supply systemTT
Mode of protectionL-N
L-PE
L-PEN
N-PE (4+0)
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN400 V AC (TN)
400 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC440 V AC
Residual current IPE< 5 µA
Nominal discharge current In(8/20) µs35 kA
Maximum discharge current Imax(8/20) µs50 kA
Impulse discharge current (10/350) µs, charge17.5 As
Impulse discharge current (10/350) µs, specific energy310 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp35 kA
Follow current interrupt rating Ifi50 kA
Short-circuit current rating ISCCR50 kA
Voltage protection level Up≤ 2.5 kV
Residual voltage Ures≤ 2.5 kV (at In)
TOV behavior at UT580 V AC (5 s / withstand mode)
800 V AC (120 min / withstand mode)
1640 V AC (200 ms / safe failure mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring400 A (gG)

Connection data

Connection methodpluggable

UL specifications

SPD Type1CA
Maximum continuous operating voltage MCOV440 V AC
Nom. voltage400 V AC
Mode of protectionL-N
L-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Voltage protection rating VPR1800 V
Nominal discharge current In20 kA
Short-circuit current rating (SCCR)25 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCN,N-dimethylacetamide 127-19-5
Lead 7439-92-1

Classifications


Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.