ANUNCIAR
FLT-SEC-H-T1-264/25-P 2905968 PHOENIX CONTACT Type 1 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FLT-SEC-H-T1-264/25-P 2905968 PHOENIX CONTACT Type 1 surge protection plug

FLT-SEC-H-T1-264/25-P

2905968

PHOENIX_CONTACT

Type 1 surge protection plug

Replacement connector for lightning current arresters from the FLASHTRAB SEC HYBRID 264 product series, for the L-N and L-PEN sections.

More details


Earthing, lightning and surge protection > Accessories/spare parts for surge protection power supply systems

Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $470.95
Unit price: $470.95
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2905968
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 28 (C-4-2017)
GTIN4055626012032
Weight per Piece (excluding packing)335.780 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height113.4 mm
Width35.5 mm
Depth64.2 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC test classificationI / II
T1 / T2
EN typeT1 / T2
IEC power supply systemTN-C
Mode of protectionL-PEN
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240 V AC (TN)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Nominal discharge current In(8/20) µs25 kA
Maximum discharge current Imax(8/20) µs50 kA
Impulse discharge current (10/350) µs, charge12.5 As
Impulse discharge current (10/350) µs, specific energy160 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp25 kA
Follow current interrupt rating Ifi50 kA
Short-circuit current rating ISCCR50 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
≤ 2.5 kV (at 50 kA)
≤ 1.2 kV (at 12.5 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 2.5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
460 V AC (120 min / withstand mode)
Response time tA≤ 100 ns

Additional technical data

Follow current interrupt rating Ifi100 kA
Short-circuit current rating ISCCR100 kA
Maximum discharge current Imax(8/20) µs100 kA (AS NZS 1768:2007)
Maximum continuous voltage UC275 V AC

Connection data

Connection methodpluggable

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications


ETIM for 2905968 Earthing, lightning and surge protection (EC002496)
Feature Name Feature Value
Type of accessory/spare part (EF000215) Other
Accessory (EF013236) Yes
Spare part (EF013237) No

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.