Product successfully added to your shopping cart
PSR-MM30-2NO-2DO-24DC-SC
2702357
PHOENIX_CONTACT
1
Two-channel zero-speed and over-speed safety relays up to SIL 3, Cat. 4, PL e, 2 safe relay outputs, suitable for connecting HTL, TTL or sine/cosine encoders as well as proximity switches, plug-in screw terminal block, width: 22.5 mm
Safety
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2702357 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 243 (C-6-2019) |
GTIN | 4055626133225 |
Weight per Piece (excluding packing) | 200.000 g |
Custom tariff number | 90328900 |
Country of origin | DE (Germany) |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|
Ambient temperature (operation) | -40 °C ... 55 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Designation | A1/A2 |
---|---|
Rated control circuit supply voltage US | 24 V DC -15 % / +10 % (provide external protection) |
Rated control supply current IS | typ. 74 mA |
Power consumption at US | typ. 1.78 W |
Inrush current | < 18 A (Δt = 500 µs at Us) |
Filter time | 2 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Serial protection against polarity reversal 33 V suppressor diode |
Input name | Operating mode and monitoring inputs |
---|---|
Description of the input | NPN, IEC 61131-2, type 1 |
Number of inputs | 1 (Non-safety-related start input: S34) |
3 (Safety-related operating mode inputs: I1, I2, I3) | |
2 (Safety-related monitoring inputs: MI1, MI2) | |
Input voltage range "0" signal | 0 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Input current range "0" signal | 0 mA ... 1.5 mA |
Inrush current | < 5 mA |
Current consumption | typ. 4 mA (at US) |
Filter time | max. 2 ms (Test pulse width; low test pulses for operating mode and monitoring inputs) |
Test pulse rate = 5 x Test pulse width | |
Max. permissible overall conductor resistance | 150 Ω |
Discrepancy time | 2 s (I1, I2, I3) |
2.5 s (MI1, MI2) | |
Protective circuit/component | 33 V suppressor diode |
Input name | Proximity switch inputs |
---|---|
Description of the input | NPN, IEC 61131-2, type 1 |
Number of inputs | 2 (Safety-related proximity switch inputs: IN1 IN2) |
Precision | ± 2 % (in reference to the parameterized limit value) |
Inrush current | < 12 mA |
Current consumption | typ. 10 mA (at US) |
Input voltage range "0" signal | 0 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Input current range "0" signal | 0 mA ... 1.5 mA |
Max. permissible overall conductor resistance | 150 Ω |
Limit frequency | max. 2 kHz (Minimum pulse duration: 2 µs) |
Protective circuit | 33 V suppressor diode |
Input name | Encoder input |
Description of the input | TTL, HTL, Sin/Cos |
Number of inputs | 1 (Safety-related encoder input, RJ45) |
Precision | ± 2 % (in reference to the parameterized limit value) |
Current consumption | < 3 mA (Per track for US) |
Max. permissible overall conductor resistance | 150 Ω |
Limit frequency | max. 400 kHz |
max. 250 kHz For active diagnostic safety encoder | |
HTL signal form | 0 V DC ... 3 V DC (Low) |
12 V DC ... 30 V DC (High) | |
TTL signal form | 0 V DC ... 0.9 V DC (Low) |
2.5 V DC ... 5 V DC (High) | |
Sine/cosine signal form | 2 V DC ... 3 V DC (1 Vppdifferential signal) |
Output name | Enabling current path |
---|---|
Output description | 2 NO contacts each in series, without delay, floating |
Number of outputs | 2 (safety-related N/O contacts: 13/14, 23/24) |
Contact type | 2 enabling current paths |
Contact material | AgSnO2 |
Switching voltage | min. 12 V AC/DC |
max. 250 V AC/DC (Observe the load curve) | |
Limiting continuous current | 6 A |
Inrush current | min. 3 mA |
max. 6 A | |
Sq. Total current | 72 A2(observe derating) |
Switching capacity | min. 60 mW |
Switching frequency | max. 0.5 Hz |
Mechanical service life | 10x 106cycles |
Switching capacity according to IEC 60947-5-1 | 4 A (24 V (DC13)) |
5 A (250 V (AC15)) | |
Output fuse | 6 A gL/gG |
Output description | PNP |
---|---|
Number of outputs | 2 (Non-safety-related signal outputs: MO1, MO2) |
Voltage | approx. 22 V DC (Us- 2 V) |
Current | max. 100 mA |
Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
Protective circuit/component | 33 V suppressor diode |
Short-circuit protection | no |
Typical response time at US | < 200 ms (For Usautostart) |
---|---|
< 150 ms (For Usmanual, monitored start) | |
Delay time range | 0 s ... 10 s ±10 % (Adjustable switch-on delay for downtime contacts 23/24) |
Restart time | < 1 s (Boot time) |
Recovery time | < 1 s |
Relay type | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
---|---|
Nominal operating mode | 100% operating factor |
Net weight | 196.3 g |
Mounting position | vertical or horizontal |
Mounting type | DIN rail mounting |
Assembly instructions | See derating curve |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Housing material | PBT |
Housing color | yellow |
Operating voltage display | 1 x green LED (PWR) |
Status display | 2x LED green (OUT1, OUT2) |
Connection method | Screw connection |
---|---|
pluggable | Yes |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Torque | 0.5 Nm ... 0.6 Nm |
Stop category | 0 |
---|---|
Designation | IEC 61508 - High demand |
Safety Integrity Level (SIL) | 3 |
Designation | EN ISO 13849 |
Performance level (PL) | e (6 A DC1, 17520 switching cycles/year) |
Category | 4 |
Designation | EN 62061 |
Safety Integrity Level Claim Limit (SIL CL) | 3 |
Designation | Air clearances and creepage distances between the power circuits |
---|---|
Standards/regulations | DIN EN 50178, EN 60947-5-1 |
Rated insulation voltage | 250 V AC |
Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
Safe isolation, reinforced insulation 6 kV between input circuit (A1/A2, I1, I2, I3, MI1, MI2, IN1, IN2, S34, MO1, MO2, RJ45, USB) and the enabling current paths (13/14, 23/24) | |
Degree of pollution | 2 |
Overvoltage category | III |
Shock | 15g |
Vibration (operation) | 10 Hz ... 150 Hz, 2g |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
eCl@ss 4.0 | 27371102 |
---|---|
eCl@ss 4.1 | 27371102 |
eCl@ss 5.0 | 27371901 |
eCl@ss 5.1 | 27371901 |
eCl@ss 6.0 | 27371800 |
eCl@ss 7.0 | 27371811 |
eCl@ss 8.0 | 27371811 |
eCl@ss 9.0 | 27371811 |
UNSPSC 6.01 | 30211901 |
---|---|
UNSPSC 7.0901 | 39121501 |
UNSPSC 11 | 39121501 |
UNSPSC 12.01 | 39121501 |
UNSPSC 13.2 | 39122331 |
UNSPSC 18.0 | 39122331 |
UNSPSC 19.0 | 39122331 |
UNSPSC 20.0 | 39122331 |
UNSPSC 21.0 | 39122331 |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX AUTOMATION EN.pdf | 35 Mbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.