PLT-SEC-T3-230-FM 2905229 PHOENIX CONTACT Type 3 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PLT-SEC-T3-230-FM 2905229 PHOENIX CONTACT Type 3 surge protection device

PLT-SEC-T3-230-FM

2905229

PHOENIX_CONTACT

Type 3 surge protection device

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Go to successor article: PLT-SEC-T3-230-FM-UT 2907919

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2905229
Packing unit1 pc
Catalog pagePage 71 (C-4-2017)
GTIN4046356939881
Weight per Piece (excluding packing)73.330 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height90 mm
Width17.7 mm
Depth74.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 150 Hz/20 cycles/axis/X, Y, Z)

General

EN typeT3
IEC power supply systemTT
TN-S
Number of portsOne
Mode of protectionL-N
L-PE
N-PE
(L+) - (L-)
(L+/L-) - PE
Mounting typeDIN rail: 35 mm
Colorlight grey RAL 7035
traffic grey A RAL 7042
Housing materialPA 6.6-FR 20% GF
PA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN230 V AC (TN-S)
230 V AC (TT - only in use with RCD)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
230 V DC
Rated load current IL26 A (30 °C)
Residual current IPE≤ 5 µA
Nominal discharge current In(8/20) µs3 kA
Standby power consumption PC≤ 275 mVA (at UREF)
≤ 300 mVA (at UC)
Reference test voltage UREF255 V AC
Combination wave UOC6 kV
Voltage protection level Up(L-N)≤ 1.35 kV
Voltage protection level Up(L-PE)≤ 1.5 kV
Voltage protection level Up(N-PE)≤ 1.5 kV
TOV behavior at UT(L-N)440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
TOV behavior at UT(L-PE)440 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
1455 V AC (200 ms / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / safe failure mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Short-circuit current rating ISCCR1.5 kA AC
0.25 kA DC
Max. backup fuse with branch wiringnot required
Maximum backup fuse for through wiring25 A (gG / B / C)

Indicator/remote signaling

Switching functionN/C contact
Operating voltage250 V AC
125 V DC (200 mA DC)
Operating current3 A AC
1 A DC (30 V DC)
Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm

Connection data

Connection methodScrew connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV255 V AC
230 V DC
Nominal voltage230 V DC
Rated load current IL25 A
Mode of protectionL-N
L-G
N-G
(L+) - (L-)
(L+) - G
(L-) - G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1290 V
Measured limiting voltage MLV (L-G)1310 V
Measured limiting voltage MLV (N-G)1310 V
Measured limiting voltage MLV (L+) - (L-)1290 V
Measured limiting voltage MLV (L+) - G1310 V
Measured limiting voltage MLV (L-) - G1310 V
Nominal discharge current In3 kA

UL indicator/remote signaling

Tightening torque5 lbf-in. ... 7 lbf-in.
Conductor cross section AWG14 ... 12

UL connection data

Conductor cross section AWG14 ... 12
Tightening torque5 lbf-in. ... 7 lbf-in.

Standards and Regulations

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.