Plug-in surge arrester free of leakage current for 1-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE).

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+106,58 €
2+103,53 €
4+101,05 €
6+99,82 €
8+99,36 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height90 mm
Width35.6 mm
Depth58 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012
IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-S
TT
Lightning protection classII
Number of portsOne
SPD designCombination type
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Pollution degree2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N)350 V AC
Maximum continuous voltage UC (N-PE)260 V AC
Rated load current IL80 A
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 2 mVA
Nominal discharge current In (8/20) µs (L-N)10 kA
Nominal discharge current In (8/20) µs (L-PE)10 kA
Nominal discharge current In (8/20) µs (N-PE)20 kA
Maximum discharge current Imax (8/20) µs (L-N)20 kA
Maximum discharge current Imax (8/20) µs (L-PE)20 kA
Maximum discharge current Imax (8/20) µs (N-PE)40 kA
Follow current interrupt rating Ifi (N-PE)100 A (260 V)
Short-circuit current rating ISCCR25 kA
Voltage protection level Up (L-N)≤ 1.5 kV
Voltage protection level Up (L-PE)≤ 2 kV
Voltage protection level Up (N-PE)≤ 1.5 kV
Residual voltage Ures (L-N)≤ 1.2 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1.1 kV (at 5 kA)
Residual voltage Ures (L-PE)≤ 1.35 kV (at In)
≤ 1.35 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
Residual voltage Ures (N-PE)≤ 0.4 kV (at In)
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-N)≤ 1.5 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PE)≤ 2 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)≤ 1.5 kV
TOV behavior at UT (L-N)415 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
TOV behavior at UT (N-PE)1200 V AC (200 ms / withstand mode)
Response time tA (L-N)≤ 100 ns
Response time tA (N-PE)≤ 100 ns
Max. backup fuse with branch wiring125 A AC (gG)
Max. backup fuse with V-type through wiring80 A AC (gG)

Connection data

Connection methodScrew connection
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.1.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG15 ... 2
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)700 V AC
Maximum continuous operating voltage MCOV (L-G)350 V AC
Maximum continuous operating voltage MCOV (N-G)260 V AC
Nom. voltage240/350 V AC
Mode of protectionL-N
L-G
N-G
Power distribution system1
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1610 V
Measured limiting voltage MLV (L-G)2030 V
Measured limiting voltage MLV (N-G)870 V
Nominal discharge current In (L-N)20 kA
Nominal discharge current In (L-G)20 kA
Nominal discharge current In (N-G)20 kA

Datasheet - PDF