MACX MCR-EX-AP-RTD-RTD-SP 1291955 PHOENIX CONTACT Ex i, Resistance Isolating Transformer is used for the int.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MACX MCR-EX-AP-RTD-RTD-SP 1291955 PHOENIX CONTACT Ex i, Resistance Isolating Transformer is used for the int..

MACX MCR-EX-AP-RTD-RTD-SP

1291955

PHOENIX_CONTACT

Ex i, Resistance Isolating Transformer is used for the intrinsically safe service of Pt 100 resistance thermometers in the technology of 2, 3 or 4 resistance conductors and transmitters. The measured values at the input Ex i are transmitted 1:1 to the output at non-Ex i. 3-Way Separation, Push-in Connection

Ex i-Resistance isolator for intrinsically safe operation of Pt 100 resistance thermometers in 2, 3, or 4-conductor technology and resistance-type sensors. The values measured at the Ex i input are transmitted 1:1 to the non Ex i output. Standard configuration, 3-way isolation, Push-in connection

More details


Home > PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $585.23
Unit price: $585.23

Quantity Price
1+$585.23
2+$552.57
3+$552.57
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Technical data

Notes
GeneralAccuracy, typically specified as a percentage of the basic measuring range at UN, 23°C
GeneralInstallation conditions influence the ambient temperature.
Please refer to the “Control cabinet installation instructions”.
GeneralSensor set via DIP switches
General2-conductor comparison set via DIP switch ADJ

Product properties
Product typeTemperature transmitter
Product familyMACX Analog
No. of channels1

Electrical properties
No. of channels1
Electrical isolation3-way isolation
Signal transmission behaviorIn = Out
Temperature coefficient, typical≤ 0.1 % (10 K)
Reverse polarity protectionyes
Electrical isolation Input/output IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Input/power supply IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Input/error message output IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Input/configuration interface IEC/EN 60079-11
Standards/regulationsIEC/EN 60079-11
Rated insulation voltage375 VPP
Electrical isolation Output 1/output 2
Test voltage350 V (50 Hz, 60 s)
Electrical isolation Output/supply
Test voltage350 V (50 Hz, 60 s)
Electrical isolation Output/configuration interface
Test voltage350 V (50 Hz, 60 s)
Electrical isolation Output/supply/error message output
Test voltage350 V (50 Hz, 60 s)
Supply
Nominal supply voltage24 V DC
Supply voltage range18 V ... 31.2 V
Power dissipation≤ 600 mW
Power consumption≤ 650 mW

Input data
Measurement
Description of the inputIntrinsically safe
Sensor types (RTD) that can be usedPt 100
Connection technology2-, 3-, 4-conductor
Linear resistance measuring range18 Ω ... 391 Ω (Pt 100)
Max. permissible overall conductor resistance≤ 50 Ω (per wire, 2-conductor circuit)
≤ 100 Ω (per wire, 3-, 4-conductor circuit)

Output data
Analog: Resistance thermometer
Output signal Voltage2 V DC (Nominal voltage)
Output signal Current5 mA (Nominal current)
Output signal Resistance400 Ω
Output signal Resistance range18 Ω ... 391 Ω (Pt 100)
Settling time< 10 ms (10% ... 90%, multiplexer mode)
Setting range< 1 s (Input/output)
Sensor input current200 µA ... 5 mA
Connection technology2-, 3-, 4-conductor
Signal: Error message output
Maximum switching voltage30 V
Max. switching current100 mA

Connection data
Cross section AWG(converted acc. to IEC)
Connection methodPush-in connection
Stripping length8 mm
Conductor cross section rigid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 16

Ex data
Ex installation (EPL)Gc
Ex i circuits (EPL)Ga
Da
Ma
Safety data
Max. internal inductance Linegligible
Max. internal capacitance Cinegligible
Max. output voltage Uo6.5 V
Max. output current Io16.5 mA
Max. output power Po27 mW
Safety-related maximum voltage Um253 V AC
IIA (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co900 mH / 1000 µF
IIB/IIIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co450 mH / 570 µF
IIC (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co120 mH / 25 µF
I (simple circuit): Max. external inductivity Lo/ Max. external capacitance Co1000 mH / 1000 µF
IIB/IIIC (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co100 mH / 5.3 µF, 20 mH / 6.9 µF, 2 mH / 11 µF, 0.5 mH / 15 µF
IIC (mixed circuit): Max. external inductivity Lo/ Max. external capacitance Co50 mH / 1.1 µF, 5 mH / 1.7 µF, 1 mH / 2.3 µF, 0.2 mH / 3.4 µF

Signaling
Status displayGreen LED (supply voltage)
Red LED (line errors)

Dimensions
Dimensional drawingkrbhdfxwui.jpg
Width17.5 mm
Height107.8 mm
Depth113.7 mm
Depth NS 35/7,5114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)

Material specifications
Flammability rating according to UL 94V0
Housing materialPolyamide (PA 6.6)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (Terminal blocks)
IP30 (Housing)
Ambient temperature (operation)-20 °C ... 70 °C (Stand-alone device: any mounting position)
-20 °C ... 60 °C (Group assembly: vertical DIN rail without circulating air)
-20 °C ... 65 °C (Group assembly: vertical DIN rail with circulating air)
-20 °C ... 65 °C (Group assembly: horizontal DIN rail without circulating air)
-20 °C ... 70 °C (Group assembly: horizontal DIN rail with circulating air)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m
Permissible humidity (operation)≤ 95 % (non-condensing)

Approvals
ATEX
Identification II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
 I (M1) [Ex ia Ma] I
IECEx
Identification[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA nC [ia Ga] IIC T4 Gc
[Ex ia Ma] I

EMC data
Electromagnetic compatibilityTested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21

Standards and regulations
Electrical isolation3-way isolation

Mounting
Mounting typeNS 35/15, NS 35/7,5
Mounting positionvertical, horizontal

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.