FLT-MB-T1-264/25-3+1-UT 1461303 PHOENIX CONTACT Combined lightning and surge arrester type 1+2+3 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FLT-MB-T1-264/25-3+1-UT 1461303 PHOENIX CONTACT Combined lightning and surge arrester type 1+2+3

FLT-MB-T1-264/25-3+1-UT

1461303

PHOENIX_CONTACT

Combined lightning and surge arrester type 1+2+3

High-performance, spark gap-based non-pluggable lightning current arrester / surge protective device for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), for lightning protection levels I and II.

More details


Home > PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $900.39
Unit price: $900.39

Quantity Price
1+$900.39
2+$900.39
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Technical data

Product properties
IEC test classificationT1 + T2 + T3
I + II + III
EN typeT1 + T2 + T3
IEC power supply systemTN-S
TT
TypeDIN rail module, one-piece
Product typeCombination type
Surge protection fault messageoptical
Insulation characteristics
Overvoltage categoryIV
Pollution degree2

Electrical properties
Nominal frequency fN50 Hz (60 Hz)

Connection data
Cross section AWG(converted acc. to IEC)
Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (2,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length18 mm
Conductor cross section flexible2.5 mm² ... 25 mm²
Conductor cross section rigid2.5 mm² ... 35 mm²
Conductor cross section AWG13 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible2.5 mm² ... 25 mm²

Dimensions
Dimensional drawingibnayzvfge.jpg
Width72 mm
Height89.8 mm
Depth76.6 mm (incl. DIN rail 7.5 mm)
Horizontal pitch4 Div.

Material specifications
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPBT
Material groupI
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Mode of protectionL-N
L-PE
N-PE
Nominal voltage UN240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC264 V AC
Rated load current IL80 A (< 55 °C)
Residual current IPE≤ 0.01 mA
Nominal discharge current In(8/20) µs (L-N)25 kA
Nominal discharge current In(8/20) µs (L-PE)25 kA
Nominal discharge current In(8/20) µs (N-PE)100 kA
Combination wave UOC6 kV
Impulse discharge current (10/350) µs (L-N), charge12.5 As
Impulse discharge current (10/350) µs (L-N), specific energy156 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp25 kA
Impulse discharge current (10/350) µs (L-PE), charge12.5 As
Impulse discharge current (10/350) µs (L-PE), specific energy156 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp25 kA
Impulse discharge current (10/350) µs (N-PE), charge50 As
Impulse discharge current (10/350) µs (N-PE), specific energy2500 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp100 kA
Total discharge current Itotal(10/350) µs100 kA
Follow current quenching capacity Ifi(L-N)25 kA
Follow current interrupt rating Ifi(N-PE)100 A
Short-circuit current rating ISCCR25 kA
Voltage protection level Up(L-N)≤ 1.5 kV
Voltage protection level Up(L-PE)≤ 2.5 kV
Voltage protection level Up(N-PE)≤ 1.5 kV
Residual voltage Ures(L-N)≤ 1.5 kV (at In)
≤ 1.3 kV (at 12.5 kA)
≤ 1.1 kV (at 5 kA)
≤ 1 kV (at 2.5 kA)
Residual voltage Ures(L-PE)≤ 1.7 kV (at In)
≤ 1.5 kV (at 12.5 kA)
≤ 1.3 kV (at 5 kA)
≤ 1.2 kV (at 2.5 kA)
Residual voltage Ures(N-PE)≤ 1.5 kV (at In)
≤ 1.3 kV (at 50 kA)
≤ 1.1 kV (at 20 kA)
≤ 1 kV (at 10 kA)
TOV behavior at UT(L-N)457 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with V-type through wiring80 A (gG)
Max. backup fuse with branch wiring315 A (gG)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (Installed)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 5000 m
Permissible humidity (operation)5 % ... 95 %
Shock (operation)2g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)0,5g (9 … 200 Hz / 2.5 h / X, Y, Z)

Standards and regulations
Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012

Mounting
Mounting typeDIN rail: 35 mm

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.