MACX MCR-EX-SL-2NAM-T-SP 2924090 PHOENIX CONTACT Isolation amplifier View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MACX MCR-EX-SL-2NAM-T-SP 2924090 PHOENIX CONTACT Isolation amplifier

MACX MCR-EX-SL-2NAM-T-SP

2924090

PHOENIX_CONTACT

Isolation amplifier

More details


INTERFACE Components (IF)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $241.44
Unit price: $241.44

Quantity Price
1+$241.44
2+$219.17
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Viewed products


More info



Key Commercial Data

Orderkey2924090
Packing unit1 pc
Catalog pagePage 156 (C-5-2017)
GTIN4046356337335
Weight per Piece (excluding packing)133.100 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width12.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2

Input data

Non-load voltage~ 8 V DC
Switching points (attenuated)< 1.2 mA (blocking)
Switching points (unattenuated)> 2.1 mA (conductive)
Signal inputIntrinsically safe
Available input sourcesNAMUR proximity sensors (EN 60947-5-6)
Short-circuit current~ 8 mA
Switching hysteresis< 0.2 mA
Line fault detectionBreak 0.05 mA < IIN < 0.35 mA
Short circuit 100 Ω < RSensor < 360 Ω

Output data

Switching output1 transistor output, passive (per channel)
Minimum switching voltage3 V DC
Maximum switching voltage30 V DC
Min. contact current5 mA (short-circuit-proof)
Max. switching current50 mA (short-circuit-proof)
Switching frequency≤ 5 kHz

Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption< 34 mA (24 V DC)
Power dissipation≤ 1000 mW
Power consumption0.8 W

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm
Connection methodPush-in connection

General

No. of channels2
Status displayGreen LED (supply voltage)
LED yellow (switching state)
Red LED (line errors)
Flammability rating according to UL 94V0
Degree of pollution2
Overvoltage categoryII
Electromagnetic compatibilityConformance with EMC directive
Interference emissionEN 61000-6-4
Housing materialPA 6.6-FR
Colorgray
DesignationInput/output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/output/supply, DIN rail connector
Electrical isolation300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
DesignationInput/supply, DIN rail connector
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationOutput 1/output 2
Electrical isolation50 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, basic insulation as per EN 61010-1))
1 kV (50 Hz, 1 min., test voltage)
ConformanceCE-compliant, additionally EN 61326
ATEX II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
IECEx[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
UL, USA/CanadaClass I Div 2; IS for Class I, II, III Div 1
SIL2

Safety characteristic data

Safety Integrity Level (SIL)1
1

Safety data

Max. internal inductance Linegligible
Max. internal capacitance Ci1.1 nF
Max. output voltage Uo9.6 V
Max. output current Io10 mA
Max. output power Po25 mW
GroupIIC
Max. external inductivity Lo300 mH
Max. external capacity Co3.6 µF
GroupIIB/IIIC
Max. external inductivity Lo1000 mH
Max. external capacity Co26 µF
Safety-related maximum voltage Um253 V AC (125 V DC)

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Evaluation criterionA
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Evaluation criterionA
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Evaluation criterionA

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Evaluation criterionA
Standards/regulationsEN 61000-4-4
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Evaluation criterionA
Flammability rating according to UL 94V0
ConformanceCE-compliant, additionally EN 61326
ATEX II (1) G [Ex ia Ga] IIC
 II (1) D [Ex ia Da] IIIC
 II 3 (1) G Ex nA [ia Ga] IIC T4 Gc
IECEx[Ex ia Ga] IIC
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
UL, USA/CanadaClass I Div 2; IS for Class I, II, III Div 1
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCB
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board
GroupIIC
IIB/IIIC

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.