UK 5 N-TG 3000604 PHOENIX CONTACT Disconnect terminal block, Connection type: Screw connection, Cross sectio.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UK 5 N-TG 3000604 PHOENIX CONTACT Disconnect terminal block, Connection type: Screw connection, Cross sectio..

UK 5 N-TG

3000604

PHOENIX_CONTACT

50

Available

Ship on today

Disconnect terminal block, Connection type: Screw connection, Cross section: 0.2 mm² - 6 mm², AWG: 24 - 10, Nominal current: 16 A, Nominal voltage: 500 V, Length: 42.5 mm, Width: 6.2 mm, Color: gray, Assembly: NS 35/7,5, NS 35/15, NS 32

More details


CLIPLINE 1 rail terminals - PHOENIX CONTACT

Universal rail terminal screen UK and SK - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
50+1,86 €
100+1,81 €
200+1,77 €
250+1,76 €
350+1,74 €
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



General

NoteCurrent and voltage are determined by the plug used.
Number of levels1
Number of connections2
Nominal cross section4 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0

General

Rated surge voltage6 kV
Pollution degree3
Overvoltage categoryIII
Insulating material groupI
Connection in acc. with standardIEC 60947-7-1
Nominal current IN16 A
Maximum load current16 A (with 1.5 mm² conductor cross section)
Nominal voltage UN500 V
Open side panelja
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint7.3 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.5 mm² / 0.3 kg
4 mm² / 0.9 kg
6 mm2 / 1.4 kg
Tensile test resultTest passed
Conductor cross section tensile test0.5 mm²
Tractive force setpoint40 N
Conductor cross section tensile test4 mm²
Tractive force setpoint120 N
Conductor cross section tensile test6 mm²
Tractive force setpoint160 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 32/NS 35
Setpoint1 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 6,4 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing1.5 mm²
Short-time current0.18 kA
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 1, class B, body mounted
Test frequencyf1 = 5 Hz to f2 = 150 Hz
ASD level1.857 (m/s2)2/Hz
Acceleration0.8g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration5 g
Shock duration30 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))130 °C
Static insulating material application in cold-60 °C

Dimensions

Width6.2 mm
Length42.5 mm
Height NS 35/7,547 mm
Height NS 35/1554.5 mm
Height NS 3252 mm

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.10
Conductor cross section flexible, with ferrule without plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.4 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.2.5 mm²
2 conductors with same cross section, solid min.0.2 mm²
2 conductors with same cross section, solid max.1.5 mm²
2 conductors with same cross section, stranded min.0.2 mm²
2 conductors with same cross section, stranded max.1.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.0.25 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.1.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.2.5 mm²
Cross section with insertion bridge, solid max.4 mm²
Cross section with insertion bridge, stranded max.4 mm²
Connection methodScrew connection
Stripping length8 mm
Internal cylindrical gageA4
Screw threadM3
Tightening torque, min0.6 Nm
Tightening torque max0.8 Nm

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-3000604-UK 5 N-TG English 105 Kbytes PHOENIX CONTACT-3000604-UK 5 N-TG